Technical Instructions Document No. 155-318P25 EA GEB-1 August, 27, 2007 OpenAir™ GEB Series Non-spring Return Rotary Electronic Damper Actuators Description Features Application The OpenAir direct-coupled, 24 Vac, non-spring return electronic actuator is designed for modulating and three-position control of building HVAC dampers.
Technical Instructions Document Number 155-318P25 August 27, 2007 OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators Product Numbers Table 1. Plenum Standard Position Feedback Dual Auxiliary Switches Offset and Span Input Signal Selectable 0 – 10 Vdc or 2-10 Vdc Built-in Control Options 3-position Cable Modulating (0 to 10 Vdc) Control 24 Vac ±20% Operating Voltage GEB131.1P GEB131.1U GEB132.1U ● ● ● – – – ● ● ● ● – – – ● ● – – ● – – – – – – – – – GEB136.1U GEB161.
OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators Specifications Power Supply 24 Vac Operating voltage Frequency Power consumption Running: GEB16x GEB13x Holding: GEB 16x Equipment rating Control Signal Input signal (wires 8-2) GEB16x Voltage-input Input resistance Feedback signal Mounting Position output signal (wires 9-2) GEB16x Voltage-output Maximum output current Running torque Maximum torque Runtime for 90° opening or closing 60 Hz 50 Hz Nominal angle of rotation Maximum angular
Technical Instructions Document Number 155-318P25 August 27, 2007 Auxiliary features OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators Control signal adjustment Offset (start point) Span Dual auxiliary switches AC rating DC rating Between 0 to 5V Between 2 to 30V 24 to 250 Vac AC 6A resistive, AC 2A general purpose 12 to 30 Vdc DC 2A Switch Range Switch A Recommended range usage Factory setting Switch B Recommended range usage Factory setting Switching hysteresis Feedback potentiometer
OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators Actuator Components Technical Instructions Document Number 155-318P25 August 27, 2007 12 1 11 2 10 9 14 3 1. Actuator housing 2. Positioning scale for angle of rotation 3. DIP switches and cover 4. Span adjustment 5. Offset (start point) adjustment 6. Mounting bracket 7. Connection cable for power and control signals 4 5 6 13 8 EA0956R1 EA0957R1 15 Legend 8. Connection cable for auxiliary switches or feedback potentiometer 9.
Technical Instructions Document Number 155-318P25 August 27, 2007 NOTE: The auxiliary switches, control signal adjustment, and feedback potentiometer cannot be added in the field. Order the product number that includes the option(s). 4614Z19 Accessories OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators ASK71.11 For in-the-air-stream applications: Anywhere a foot-mounted actuator can be mounted.
OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators Technical Instructions Document Number 155-318P25 August 27, 2007 985-093 Standard shaft adapter 985-098 Adjustment Tool EA0891R1 985-094P10 Position indicators (10/pkg.) EA0889R1 EA0499R1 EA0888R1 Service Parts 985-092 Anti-rotation (mounting) bracket. Figure 6. Miscellaneous Service Parts. Operation GEB16x Apply a 0 to 10 Vdc control signal between wire 8 (Y) and wire 2 (G0) to operate the damper actuator.
Technical Instructions Document Number 155-318P25 August 27, 2007 OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators Table 2. Total Torque Actuator <44lb-in (5Nm) GDE >44lb-in <88lb-in (>5Nm <10Nm) GLB >88lb-in <132lb-in (>10Nm <15Nm) GEB >132lb-in <177lb-in (>15Nm <20 Nm) GBB >177lb-in <310lb-in (>20Nm <35Nm) GIB >310lb-in <620lb-in (>35Nm <70Nm) Use tandem-mounting bracket ASK73.2U with any combination of GIB161 AND GIB166 actuators or use Master/Slave Actuators.
OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators The angular rotation is adjustable between 0 and 90° at 5-degree intervals. The range of shaft movement is limited by mounting the shaft adapter: 1. Loosen the shaft adapter from the damper shaft and remove the actuator from the damper shaft. 2. Remove the clip and shaft adapter from the actuator. 1 2 EA0947R1 Mechanical Range Adjustment Technical Instructions Document Number 155-318P25 August 27, 2007 Figure 8.
Technical Instructions Document Number 155-318P25 August 27, 2007 The offset (start point) and span of the control signal can be adjusted. The offset, Uo, can be adjusted between 0 to 5 Vdc. The span, ΔU, can be adjusted between 2 to 30 Vdc. GEB164.1U (Offset and Span) YS (%) 100 1) 3) % OPEN Control signal adjustment OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators 2) Uo U V 2 10 16 Ys Yu Uo ΔU 0 2 5 UO 30 ΔU (max.
OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators Technical Instructions Document Number 155-318P25 August 27, 2007 Control Signal Uo = 2; ΔU = 16V Adjustment, continued YS (%) 100 Umin = minimum control signal Umax = maximum control signal 50 0 EA0412R1 2 Uo 10 18 YU (v) ΔU (16 V) Umax Umin Figure 13. Example. Dual auxiliary switch ← Actuator scale: Clockwise -2,5 GEB164.1U, GEB136.
Technical Instructions Document Number 155-318P25 August 27, 2007 DIP Switch Functionality GEB161 GEB164 OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators Description Label Description Clockwise Counterclockwise Active 0 Off 2-10 Vdc 2-10 0-10 0…10 Vdc Offset 0-5V Span 2-30V ADJ 0-10 0...10 Vdc Function Rotary angle direction Self-adaptation to mechanical range GEB161: Positioning control signal 2-10 or 0-10 GEB164: Positioning signal.
OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators Wiring Technical Instructions Document Number 155-318P25 August 27, 2007 All wiring must conform to NEC and local codes and regulations. Use earth ground isolating step-down Class 2 transformers. Do not use autotransformers. The maximum rating for a Class 2 step-down transformer is 100 VA. Determine the supply transformer rating by summing the VA ratings of all actuators and all other components used.
Technical Instructions Document Number 155-318P25 August 27, 2007 OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators Wire Designations 8 Each wire has the standard symbol printed on it. See Table 3. S1 A EA0284R1 P1 S4 B M S2 S3 EA0952R1 M 1 7 6 9 S5 S6 2 P2 P3 S1 S4 A B S2 S3 S5 S6 1000 1 Figure 16. Modulating 0 to 10 Vdc Control. Figure 17. 3-Position Control. 24 Vac Power Supply 24 Vac Power Supply Table 3.
OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators Start-Up/ Commissioning Technical Instructions Document Number 155-318P25 August 27, 2007 1. Check Operation: Non-spring Return Modulating Control (0-10 Vdc) 24 Vac 2. 3. a. Connect wires 1 (red) and 2 (black) to the 24 Vac power supply. b. Set the Digital Multimeter (DMM) dial to Vdc for the actuator input signal. c. Connect wires 2 (black) and 8 (gray) to a Digital Multimeter (DMM). d.
Technical Instructions Document Number 155-318P25 August 27, 2007 Non-spring Return 1. 3-Position 24 Vac OpenAir GEB Non-Spring Return Rotary Electronic Damper Actuators Check Operation: a. Apply a control signal (24 Vac) to wires 1 (red) and 6 (violet). b. Allow the actuator shaft coupling to rotate from 0 to 90°. c. Stop applying a control signal to wires 1 (red) and 6 (violet). d. Apply a control signal (24 Vac) to wires 1 (red) and 7 (orange). e.
OpenAir GEB Non-spring Return Rotary Electric Damper Actuators Service Technical Instructions Document Number 155-318P25 August 27, 2007 WARNING: Do not open the actuator. If the actuator is inoperative, replace the unit. Troubleshooting WARNING: To avoid injury or loss of life, pay attention to any hazardous voltage (Example: 120 Vac) when performing checks. • Check that the wires are connected correctly. • Check that auxiliary switches, DIP-switches, and Offset/Span are set correctly.