© Siemens AG 2007 PROFINET/ Industrial Ethernet according to IEEE 802.
© Siemens AG 2007 PROFINET/Industrial Ethernet Active network components Overview 2 ■ Overview Industrial Ethernet Switches SCALANCE X is the product range of Industrial Ethernet switches from SIMATIC NET. Switches are active network components that specifically distribute data to the relevant addressees. The SCALANCE X product group comprises various product lines that complement each other and are carefully tuned to the specific automation task.
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches Overview ■ Overview 2 SCALANCE X Real-Time Isochronous Real-Time X414-3E X-400 X-300 X310 X308-2 X308-2 LD X-200 X208 X216 X224 X108 X116 X124 X204-2/ X206-1/ X212-2/ X204-2LD X206-1LD X212-2 LD X104-2 X106-1 X201-3P IRT X202-2IRT X202-2P IRT X200-4P IRT X204IRT X112-2 X005 G_IK10_XX_10212 Entry Level X408-2 X208PRO X-100 Unmanaged P e r f o r m a n c e Managed r a n g e Managed plus X005 Modular Ove
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches Overview ■ Overview (continued) Type and number of ports 2 2 4) X408-2 4 4 X310 3 X308-2 1 2 5) 7 X308-2LD 1 2 5) 7 4) 20 3) 4 12 3) 12 3) 4 4 1) Layer 3 switching IGMP RSTP IT features VLAN Digital inputs Modular design Gigabit technology IRT capability Standby redundancy Ring redundancy with RM C-PLUG slot X-300 7 X204IRT 4 X202-2IRT 2 X202-2P IRT 2 2 X201-3P IRT 1 3 2 X200-4P IRT 2
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-100 unmanaged ■ Overview ■ Benefits 2 • Ideal solution for configuring Industrial Ethernet star and line topologies • Space-saving installation in the cabinet thanks to the compact design in S7-300 format • Secure data communication by means of industry-standard device interface using PROFINET-compliant plug-in connector (IE FC RJ45 Plug 180) and additional strain relief by latching the connector to the housing • Ins
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-100 unmanaged ■ Design The SCALANCE Industrial Ethernet switches with a rugged metal housing are optimized for mounting on a standard rail and an S7-300 rail. Direct wall mounting in various positions is also possible. Due to the dimensions of the housing that conform to those of SIMATIC S7-300, the devices are optimized for integration in an automation solution with S7-300 components.
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-100 unmanaged ■ Function (continued) 2 S7-400 with CP 443-1 Advanced IPC with CP 1613 A2 MP 370 S7-300 with CP 343-1 S7-300-1/MP 370 with CP 343-1 S7-200 with CP 243-1 IE/PB Link Switch SCALANCE X108 IE FC RJ45 Plug Switch SCALANCE X104-2 SCALANCE X112-2 electrical network optical network Switch SCALANCE X106-1 G_IK10_XX_10203 Switching cabinet S7-400 with CP 443-1 Advanced 10/100 Mbit/s Industrial Ethernet
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-100 unmanaged ■ Function (continued) SCALANCE X414-3E Fiber Optic SCALANCE X106-1 SCALANCE X106-1 SCALANCE X106-1 S7-300 S7-300 S7-300 ET 200S ET 200S ET 200S S7-400 S7-400 ET 200S ET 200S Optical star topology with SCALANCE X106-1 Diagnostics The following information is displayed by LEDs on site: • Power • Port status • Data traffic The Industrial Ethernet switches of the SCALANCE X-100 line can also be
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-100 unmanaged ■ Technical specifications 2 Type SCALANCE X104-2 SCALANCE X106-1 SCALANCE X108 Data transmission rates 10/100 Mbit/s 10/100 Mbit/s 10/100 Mbit/s • Communication connection, electrical 4 x RJ45 sockets (10/100 Mbit/s; TP) 6 x RJ45 sockets (10/100 Mbit/s; TP) 8 x RJ45 sockets (10/100 Mbit/s; TP) • Communication connection, optical 2 x BFOC sockets (100 Mbit/s) 1 x BFOC sockets (100 Mbit/s)
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-100 unmanaged 2 ■ Technical specifications (continued) N SCALANCE X116 N SCALANCE X124 N Type SCALANCE X112-2 Data transmission rates 10/100 Mbit/s 10/100 Mbit/s 10/100 Mbit/s • Communication connection, electrical 12 x RJ45 sockets (10/100 Mbit/s; TP) 16 x RJ45 sockets (10/100 Mbit/s; TP) 24 x RJ45 sockets (10/100 Mbit/s; TP) • Communication connection, optical 2 x BFOC sockets (100 Mbit/s) – – • C
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-100 unmanaged ■ Ordering data Order No. Order No.
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed 2 ■ Overview ■ Benefits • The managed Industrial Ethernet switches of the SCALANCE X-200 product line are optimized for installing Industrial Ethernet networks with 10/100 Mbit/s in a line, star and ring topology • Integrated redundancy manager for constructing Fast Ethernet ring topologies (excluding SCALANCE X208 PRO) • Electrical or optical connection to stations or network in accordance with the port
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed ■ Application The SCALANCE X-200 Industrial Ethernet switches permit costeffective configuration of Industrial Ethernet line, star or ring topologies with switching functionality for networks in which high availability or remote diagnostics options are required. The devices with degree of protection IP30 have been designed for use in the control cabinet.
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed ■ Application (continued) SNMP/Web-based Management Diagnosis of individual SCALANCE X208 Switches by means of web browser through SIMATIC Field PG 100 Mbit/s Switching cabinet FO-Ring S7-400 with CP 443-1 Advanced S7-300-1/MP 370 IE/PB Link IPC with CP 1613 A2 Switch SCALANCE X204-2 IE FC Outlet RJ45 Switch SCALANCE X208 Switch SCALANCE X208 Diagnosis using the network electrical network optical n
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed ■ Function • Configuring electrical and optical Industrial Ethernet line, star and ring topologies • Fast redundancy in the ring with High Speed Redundancy (HSR); up to 0.3 seconds for reconfiguration of the ring with 50 switches in the ring • The functioning of the ring is continuously monitored by the integrated redundancy manager (with the exception of SCALANCE X208 PRO).
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed ■ Function (continued) ET 200pro Small switching cabinet S7-300 with CP 343-1 ET 200pro PG screwed cable gland Control & monitoring PG screwed cable gland PG-screwed cable gland Power Supply PS791-1PRO IPC with CP 1616 SCALANCE X208PRO Field PG ET 200S Access Point SCALANCE W788-1PRO 230 V AC Mobile Panel 277 IWLAN 24 V DC with PS791-1PRO Power Supply 24 V DC G_IK10_XX_10078 2 230 V AC PROFI
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed ■ Function (continued) 2 S7-400 Operator Station S7-400 S7-300 Industrial Ethernet SCALANCE X400 IRT PC S7-400 SCALANCE X206-1 SCALANCE X206-1 Industrial Ethernet S7-300 IPC SCALANCE X208 PC S7-400 S7-300 S7-400 Maximum cable length for 100 Mbit/s: electrical ring circuit: 100 m optical ring circuit (multimode): 3000 m G_IK10_XX_10113 IPC S7-400 High-speed redundancy in mixed ring with fiber
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed 2 ■ Technical specifications Type SCALANCE X204-2 SCALANCE X204-2LD Data transmission rate 10/100 Mbit/s 10/100 Mbit/s • Communication connection, electrical 4 x RJ45 (10/100 Mbit/s; TP) 4 x RJ45 (10/100 Mbit/s; TP) • Communication connection, optical 2 x BFOC sockets (100 Mbit/s) 2 x BFOC sockets (100 Mbit/s) • Connection for supply voltage 1 x 4-pole terminal block 1 x 4-pole terminal block
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed ■ Technical specifications (continued) 2 Type SCALANCE X206-1 SCALANCE X206-1LD Data transmission rate 10/100 Mbit/s 10/100 Mbit/s • Communication connection, electrical 6 x RJ45 (10/100 Mbit/s; TP) 6 x RJ45 (10/100 Mbit/s; TP) • Communication connection, optical 1 x BFOC sockets (100 Mbit/s) 1 x BFOC sockets (100 Mbit/s) • Connection for supply voltage 1 x 4-pole terminal block 1 x 4-pole te
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed 2 ■ Technical specifications (continued) N SCALANCE X212-2LD N Type SCALANCE X212-2 Data transmission rate 10/100 Mbit/s 10/100 Mbit/s • Communication connection, electrical 12 x RJ45 (10/100 Mbit/s; TP) 12 x RJ45 (10/100 Mbit/s; TP) • Communication connection, optical 2 x BFOC sockets (100 Mbit/s) 2 x BFOC sockets (100 Mbit/s) • Connection for supply voltage 1 x 4-pole terminal block 1 x 4
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed ■ Technical specifications (continued) 2 Type SCALANCE X208 SCALANCE X208PRO Data transmission rate 10/100 Mbit/s 10/100 Mbit/s • Communication connection, electrical 8 x RJ45 (10/100 Mbit/s; TP) 8 x 4-pole M12 sockets (10/100 Mbit/s; D-coded) • Communication connection, optical – – • Connection for supply voltage 1 x 4-pole terminal block 2 x 4-pole M12 interface • Connection for signaling
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed 2 ■ Technical specifications (continued) N SCALANCE X224 N Type SCALANCE X216 Data transmission rate 10/100 Mbit/s 10/100 Mbit/s • Communication connection, electrical 16 x RJ45 (10/100 Mbit/s; TP) 24 x RJ45 (10/100 Mbit/s; TP) • Communication connection, optical – – • Connection for supply voltage 1 x 4-pole terminal block 1 x 4-pole terminal block • Connection for signaling contact 1 x
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-200 managed ■ Ordering data Order No. Order No.
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-300 managed plus 2 • Rugged, industry-standard node connections with PROFINETcompliant RJ45 connectors that are latched onto the housing to provide additional strain and bending relief • Redundant power supply for protection against power failure • Diagnostics on the device by means of LEDs (power, link status, data traffic, fault, redundancy manager) • Fault signaling contact, can be easily set by means of the SELECT/
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-300 managed plus ■ Application SCALANCE X-300 products enable the establishment of switched networks both at the field level and at the control level where high data transfer speeds are required in addition to high network availability and extensive diagnostics facilities. The switches are designed in degree of protection IP30 for installation in control cabinets.
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-300 managed plus ■ Application (continued) PC PC SCALANCE X414-3E SCALANCE X414-3E Industrial Ethernet Industrial Ethernet Switching cabinet Switching cabinet SCALANCE X308-2 SCALANCE X308-2 SCALANCE X308-2 S7-400 S7-400 S7-400 Switching cabinet S7-400 ET 200S S7-400 S7-400 ET 200S ET 200S G_IK10_XX_101215 2 Connection of control cabinets with SCALANCE X308-2 in an optical gigabit ring ■ Design T
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-300 managed plus ■ Function • Increase of the network performance; by filtering the data traffic on the basis of the Ethernet (MAC) address of the data terminals, the local data traffic remains local; only data intended for users of another subnetwork are forwarded by the switch.
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-300 managed plus 2 ■ Function (continued) Commissioning and diagnosis Network management Setting options on the device itself: • Redundancy manager RM; to establish a ring, a SCALANCE X-300 is switched to RM mode. The Gigabit ports (electrical or optical) are preferably used as ring ports. • Signal mask; the signal mask is set to the current status of the SCALANCE X-300 (setpoint) by pushbutton operation.
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-300 managed plus ■ Technical specifications 2 Type SCALANCE X310 SCALANCE X308-2 SCALANCE X308-2LD Transfer rate 10/100/1000 Mbit/s 10/100/1000 Mbit/s 10/100/1000 Mbit/s • Communication connection, electrical • 3 x RJ45 (10/100/1000 Mbit/s; TP) • 7 x RJ45 (10/100 Mbit/s; TP) • 1 x RJ45 (10/100/1000 Mbit/s; TP) • 7 x RJ45 (10/100 Mbit/s; TP) • 1 x RJ45 (10/100/1000 Mbit/s; TP) • 7 x RJ45 (10/100 Mbit/s; TP)
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-300 managed plus 2 ■ Ordering data Order No. SCALANCE X-300 Industrial Ethernet switches Managed plus Industrial Ethernet switches; RJ45 ports for establishing electrical and/or optical Industrial Ethernet networks; integral Redundancy Manager, IT functions (RSTP, VLAN, etc.), network management via SNMP and web server; C-PLUG included in the scope of supply Order No.
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular ■ Overview • Through learning the Multicast sources and targets (IGMP (Internet Group Management Protocol snooping), SCALANCE X-400 switches can also filter Multicast data traffic and therefore limit the load in the network.
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular 2 ■ Application SCALANCE X-400 products permit the configuration of switched networks at the control level, which not only demands high availability of the network and extensive diagnostic options, but also a high number of ports, high transfer rate and the support of fiber optic and twisted-pair transmission media.
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular ■ Design (continued) 2 SCALANCE X-400 extender module (EM), only for SCALANCE X414-3E TP-Ports Fast Ethernet Gigabit Fast Ethernet MM492-2 MM491-2 MM491-2 12 13 14 15 EM496-4 extender module 2 3 4 5 6 7 8 9 10 11 12 13 14 15 MM491-2LD MM491-2 2 3 4 5 6 7 8 9 10 11 SCALANCE X414-3E MM491-2 MM491-2 MM491-2 MM491-2LD oder MM491-2 EM496-4 extender module MM491-2LD oder MM491-2 SCALANCE X414-3E
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular 2 ■ Function • Increasing the network performance; by filtering the data traffic on the basis of the Ethernet (MAC) address of the data terminals, the local data traffic remains local; only data intended for users of another subnetwork are forwarded by the switch.
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular ■ Function (continued) 2 Operator Station Operator Stations S7-300 SCALANCE X408-2 SCALANCE X414-3E 1000 Mbit/s Industrial Ethernet SCALANCE X408-2 S7-300 Stand-by Master S7-300 Stand-by Slave 1000 Mbit/s Non-Siemens device SCALANCE X408-2 Industrial Ethernet 1000 Mbit/s SCALANCE X414-3E S7-300 SCALANCE X414-3E S7-300 IPC G_IK10_XX_10182 PC HMI S7-400 Optical redundant connection of t
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular ■ Function (continued) When configuring the network, it is necessary to observe the following boundary conditions: • Maximum line length between two modules for multi-mode fiber-optic conductors: - 3000 m at 100 Mbit/s - 750 m at 1 Gbit/s • Maximum line length between two modules for single-mode fiber-optic conductors: - 26 km at 100 Mbit/s - 10 km at 1 Gbit/s • Maximum length of installation cable: - 100 m
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular ■ Function (continued) ■ Integration 2 Network management If faults occur in the network, the SCALANCE X-400 switch can send error messages (traps) to a network management system or also e-mails to a predefined network administrator. The remote monitoring (RMON) offers the following functions: The SCALANCE X-400 switch can collect statistics information according to the RMON groups 1 through 4.
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular ■ Integration (continued) Operator Station (OS) OS SIMATIC Batch SIMATIC IT OS Engineering Station (ES) Terminal Bus SCALANCE X408-2 SCALANCE X408-2 1000 Mbit/s Industrial Ethernet IPC SCALANCE X310 OS Server (redundant) 1000 Mbit/s OS Server (redundant) SCALANCE X408-2 SCALANCE X408-2 Plant bus Industrial Ethernet IPC 1000 Mbit/s SCALANCE X308-2 SCALANCE X414-3E SCALANCE X414-3E SCALA
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular ■ Technical specifications N 2 Type SCALANCE X408-2 SCALANCE X414-3E Transfer rate 10/100/1000 Mbit/s 10/100/1000 Mbit/s • Communication connection, electrical 4 x RJ45 (10/100/1000 Mbit/s; TP); 4 x RJ45 (10/100 Mbit/s; TP) In the basic unit: 2 x RJ45 (10/100/1000 Mbit/s; TP); 12 x RJ45 (10/100 Mbit/s; TP); with extender modules: 8 x RJ45 (10/100 Mbit/s; TP) via EM495-8 • Communication connection
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular 2 ■ Technical specifications (continued) Type SCALANCE X408-2 N SCALANCE X414-3E Approvals • Radio interference level EN 61000-6-4 Class A EN 61000-6-4 Class A • Interference immunity EN 61000-6-2 EN 61000-6-2 • ATEX Zone 2 EN 50021 EN 50021 • C-Tick AS/NZS 2064 (Class A) AS/NZS 2064 (Class A) • CE EN 61000-6-2, EN 61000-6-4 EN 61000-6-2, EN 61000-6-4 • Approvals for use in marine vessels
© Siemens AG 2007 PROFINET/Industrial Ethernet Industrial Ethernet switches SCALANCE X-400 modular ■ Ordering data Order No. Order No. Industrial Ethernet Switches SCALANCE X-400 Modular Industrial Ethernet switches with integral RJ45 ports for constructing electrical and/or optical Industrial Ethernet networks; integral redundancy manager, IT functions (RSTP, VLAN, etc.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-300 CPU 319F-3 PN/DP 2 ■ Overview ■ Technical specifications 6ES7 318-3FL00-0AB0 Supply voltages Rated value • DC 24 V Yes • permissible range, lower limit (DC) 20.4 V • permissible range, upper limit (DC) 28.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-300 CPU 319F-3 PN/DP ■ Technical specifications (continued) 6ES7 318-3FL00-0AB0 Digital channels Times/counters and their remanence S7 counter • Number 2,048 • Remanence - adjustable Yes • Counting range - adjustable - lower limit - upper limit Yes 0 999 IEC counter • present Yes S7 times • Inputs 65,536 • Outputs 65,536 • Inputs, of which central 1,024 • Outputs, of which central 1,024 Analog channels • Inputs 4,096 •
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-300 CPU 319F-3 PN/DP 2 ■ Technical specifications (continued) 6ES7 318-3FL00-0AB0 6ES7 318-3FL00-0AB0 PROFINET CBA (at set setpoint communication load) Test commissioning functions Status/control • Setpoint for the CPU communication load 20% • Number of remote interconnection partners 32 14 • Number of functions, master/slave 50 • Forcing Yes • Total of all master/slave connections 3,000 • Number of variables, max.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-300 CPU 319F-3 PN/DP ■ Technical specifications (continued) 6ES7 318-3FL00-0AB0 DP slave 1st interface isolated Yes Power supply to interface (15 to 30 V DC), max. 150 mA MPI • Services - Routing - Global data communication - S7 basic communication - S7 communication - S7 communication, as client - S7 communication, as server - direct data exchange (cross traffic) - DPV1 • Number of connections • Transmission speeds, max.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-300 CPU 319F-3 PN/DP 2 ■ Technical specifications (continued) 6ES7 318-3FL00-0AB0 DP slave • Services - PG/OP communication - Routing - Global data communication - S7 basic communication - S7 communication, as client - S7 communication, as server - direct data exchange (cross traffic) - DPV1 Programming language Yes Yes No Yes No Yes Yes No The current GSD file can be obtained from: http://www.siemens.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-300 CPU 319F-3 PN/DP ■ Ordering data CPU 319F-3 PN/DP Main memory 1.4 MB, power supply 24 V DC, combined MPI/ PROFIBUS DP master/slave interface, PROFIBUS DP master/slave interface, Ethernet/PROFINET interface; MMC required Order No. 6ES7 318-3FL00-0AB0 Distributed Safety V5.4 programming tool Task: Software for configuring fail-safe user programs for SIMATIC S7-300F, S7-400F, ET 200S Requirement: STEP 7 V5.3 SP3 and higher Order No.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-300 CPU 319F-3 PN/DP 2 ■ Ordering data Order No. Order No.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 414-3 PN/DP ■ Overview ■ Technical specifications 2 6ES7 414-3EM05-0AB0 Product status Hardware product status 1 Firmware version V 5.0 associated programming package From STEP7 V 5.4 SP1 or higher Voltages and currents Feeding of external buffer voltage to CPU 5 to 15 V DC Current consumption from backplane bus DC 5 V, max. 1.4 A from interface DC 5 V, max. 90 mA; At each DP interface Power loss, typ. 5.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 414-3 PN/DP 2 ■ Technical specifications (continued) 6ES7 414-3EM05-0AB0 6ES7 414-3EM05-0AB0 Digital channels Times/counters and their remanence • Inputs 65,536 S7 counter • Outputs 65,536 • Inputs, of which central 65,536 • Outputs, of which central 65,536 • Number 2,048 • Remanence - adjustable - lower limit - upper limit - preset • Counting range - lower limit - upper limit Yes 0 2,047 From Z 0 to Z 7 0 999 IEC
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 414-3 PN/DP ■ Technical specifications (continued) 6ES7 414-3EM05-0AB0 S7 message functions Number of login stations for message functions, max. Number of connections 31; Max. 31 with alarm_S and alarm_D (OP’s); max. 8 with alarm_8 and alarm_P (e.g. WinCC) Symbol-related messages Yes Number of messages • overall, max.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 414-3 PN/DP 2 ■ Technical specifications (continued) 6ES7 414-3EM05-0AB0 1st interface 6ES7 414-3EM05-0AB0 2nd interface Physics RS 485 / PROFIBUS + MPI Physics Ethernet isolated Yes isolated Yes Functionality Functionality • MPI Yes • DP master No • DP master Yes • DP slave No • DP slave Yes • PROFINET IO controller Yes • PROFINET CBA Yes • Point-to-point coupling No MPI • Number of connections 32; If
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 414-3 PN/DP ■ Technical specifications (continued) 6ES7 414-3EM05-0AB0 DP master • Number of connections, max. • Services - PG/OP communication - Routing - Global data communication - S7 basic communication - S7 communication - Equidistance support - SYNC/FREEZE - Activation/deactivation of DP slaves - Direct data exchange Isochronous mode 16 Useful data per isochronoous slave, max.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 414-3 PN/DP 2 ■ Ordering data CPU 414-3 PN/DP Main memory 2.8 MB, power supply 24 V DC, MPI/PROFIBUS DP master interface, PROFINET interface, slot for memory card, module slot for 1 IF module, incl. slot number labels Order No. 6ES7 414-3EM05-0AB0 Order No. Manual "SIMATIC S7-400 programmable controller" incl.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 414-3 PN/DP ■ Ordering data Order No. Order No. PROFIBUS bus components PROFINET bus components RS 485 bus connector with 90° cable outlet Max.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416-3 PN/DP 2 ■ Overview ■ Technical specifications 6ES7 416-3ER05-0AB0 Product status Firmware version V 5.0 associated programming package From STEP7 V 5.4 SP1 or higher Voltages and currents Feeding of external buffer voltage to CPU 5 to 15 V DC Current consumption from backplane bus DC 5 V, max. 1.4 A from interface DC 5 V, max. 90 mA; At each DP interface Power loss, typ. 5.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416-3 PN/DP ■ Technical specifications (continued) 6ES7 416-3ER05-0AB0 Times/counters and their remanence S7 counter 2 6ES7 416-3ER05-0AB0 Digital channels • Inputs • Outputs • Inputs, of which central • Outputs, of which central 131,072 131,072 131,072 131,072 • Number 2,048 • Remanence - adjustable - lower limit - upper limit - preset Yes 0 2,047 From Z 0 to Z 7 • Counting range - lower limit - upper limit Analog channel
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416-3 PN/DP 2 ■ Technical specifications (continued) 6ES7 416-3ER05-0AB0 S7 message functions Number of login stations for message functions, max. 63; Max. 63 with alarm_S and alarm_D (OP’s); max. 12 with alarm_8 and alarm_P (e.g.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416-3 PN/DP ■ Technical specifications (continued) 6ES7 416-3ER05-0AB0 MPI PROFINET IO controller • Number of connections 44 • Services - PG/OP communication - Routing - Global data communication - S7 basic communication - S7 communication Yes Yes Yes Yes Yes • Transmission speeds, max. 12 Mbit/s DP master • Number of connections, max.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416-3 PN/DP 2 ■ Technical specifications (continued) 6ES7 416-3ER05-0AB0 • Useful data per DP slave - Useful data per DP slave, max. - Inputs, max. - Outputs, max. - Slots, max. - per slot, max. 244 Byte 244 Byte 244 Byte 244 128 Byte DP slave ■ Ordering data CPU 416-3 PN/DP Main memory 11.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416-3 PN/DP ■ Ordering data Order No.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 SIPLUS CPU 416-3 PN/DP 2 ■ Overview ■ Ordering data Order No. CPU 416-3 PN/DP Main memory 11.2 MByte, power supply 24 V DC, MPI/PROFIBUS DP master interface, PROFINET interface, module slot for 1 IF submodule, slot for memory card, incl. slot number labels 6AG1 416-3ER05-4AB0 Accessories see ordering data to CPU 416-3 PN/DP ■ More information For technical documentation to SIPLUS see: http://www.siemens.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416F-3 PN/DP ■ Overview ■ Technical specifications 2 6ES7 416-3FR05-0AB0 Product status Firmware version V 5.0 associated programming package From STEP7 V 5.4 SP1 or higher Voltages and currents Feeding of external buffer voltage to CPU 5 to 15 V DC Current consumption from backplane bus DC 5 V, max. 1.4 A from interface DC 5 V, max. 90 mA; At each DP interface Power loss, typ. 5.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416F-3 PN/DP 2 ■ Technical specifications (continued) 6ES7 416-3FR05-0AB0 6ES7 416-3FR05-0AB0 Times/counters and their remanence Digital channels • Inputs 131,072 S7 counter • Outputs 131,072 • Inputs, of which central 131,072 • Outputs, of which central 131,072 • Number 2,048 • Remanence - adjustable - lower limit - upper limit - preset • Counting range - lower limit - upper limit Yes 0 2,047 From Z 0 to Z 7 0 999
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416F-3 PN/DP ■ Technical specifications (continued) 6ES7 416-3FR05-0AB0 S7 message functions Number of login stations for message functions, max. 63; Max. 63 with alarm_S and alarm_D (OP’s); max. 12 with alarm_8 and alarm_P (e.g. WinCC) Symbol-related messages Yes Number of messages • overall, max.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416F-3 PN/DP 2 ■ Technical specifications (continued) 6ES7 416-3FR05-0AB0 MPI 6ES7 416-3FR05-0AB0 PROFINET CBA • Number of connections 44 • Services - PG/OP communication - Routing - Global data communication - S7 basic communication - S7 communication Yes Yes Yes Yes Yes • Transmission speeds, max. 12 Mbit/s DP master • Number of connections, max.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416F-3 PN/DP ■ Technical specifications (continued) 6ES7 416-3FR05-0AB0 • Useful data per DP slave - Useful data per DP slave, max. - Inputs, max. - Outputs, max. - Slots, max. - per slot, max. 244 Byte 244 Byte 244 Byte 244 128 Byte DP slave • Number of connections 32 • Services - Routing - Programming - Status/control Yes; When interface active Yes; When interface active Yes; When interface active ■ Ordering data Order No.
© Siemens AG 2007 PROFINET/Industrial Ethernet CPUs for SIMATIC S7-400 CPU 416F-3 PN/DP 2 ■ Ordering data Order No. S7-400 operation list Order No.
© Siemens AG 2007 PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 343-1 Lean ■ Overview PN ISO ■ Benefits TCP/IP UDP PG S7 S5 IT FTP • Interface for the SIMATIC S7-300 to Industrial Ethernet (not for SINUMERIK) - 2 x RJ45 interface for 10/100 Mbit/s full/half duplex connection (with Autosensing for automatic switchover and Autocrossover function) - Integral 2-port real-time switch ERTEC - Multi-protocol operation with TCP and UDP transport protocol and PROFINET IO -
© Siemens AG 2007 PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 343-1 Lean 2 Open IE and S5-compatible communication ■ Design The CP 343-1 Lean offers all the advantages of SIMATIC S7-300 system design: • Compact design; the rugged plastic casing features on the front: - two RJ45 sockets for connecting to Industrial Ethernet with automatic detection of data transfer rate by means of Autosensing; RJ45 sockets have an industry-compatible design with additional securing colla
© Siemens AG 2007 PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 343-1 Lean ■ Integration ■ Technical specifications 2 Technical specifications S7-400 with CP 443-1 Advanced as IO controller Transfer rate MP 270 10/100 Mbit/s Autosensing Interfaces PG/PC Supervisor • Communication connection, electrical 2 x RJ45 socket (10/100 Mbit/s; TP) Autonegotiation/Autocrossover function • Connection for supply voltage 1 x 2-pin plug-in terminal block Supply voltage +24 V
© Siemens AG 2007 PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 343-1 Lean 2 ■ Ordering data Order No.
© Siemens AG 2007 PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 343-1 ■ Overview PN ISO ■ Benefits TCP/IP UDP PG S7 S5 IT FTP • Connection of SIMATIC S7-300/SINUMERIK 840D powerline to Industrial Ethernet - 2 x RJ45 interface for 10/100 Mbit/s full/half duplex connection with Autosensing/Autonegotiation and Autocrossover function - Integral 2-port real-time switch ERTEC - Multi-protocol operation with ISO, TCP and UDP transport protocol and PROFINET IO - Adjustable
© Siemens AG 2007 PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 343-1 2 Open IE and S5-compatible communication ■ Design The CP 343-1 offers all the advantages of SIMATIC S7-300 system design: • Compact design; on the front, the rugged plastic housing features: - Two RJ45 sockets for connection to Industrial Ethernet with automatic sensing of the data transmission rate by means of Autosensing/Autonegotiation; the RJ45 sockets are industrially compatible and designed with a
© Siemens AG 2007 PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 343-1 ■ Integration SIMATIC S7-300 with CP 343-1 as IO controller 2 PG/PC Supervisor SIMATIC S7-300 with CP 343-1 or CP 343-1 Lean as IO device S7-400 with CP 443-1 as IO controller PROFINET Industrial Ethernet PROFINET Industrial Ethernet ET 200pro Line structure with CP 343-1 with integrated real-time switch as a PROFINET IO controller or IO device IO devices Machine S7-300 with Vision CP 343-1 IE/PB
© Siemens AG 2007 PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 343-1 2 ■ Ordering data Order No.
© Siemens AG 2007 PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 443-1 ■ Overview PN ISO ■ Benefits TCP/IP UDP PG S7 S5 IT FTP • Connection of SIMATIC S7-400 to Industrial Ethernet - 2 x RJ45 interface for 10/100 Mbit/s full/half duplex connection with Autosensing/Autonegotiation and Autocrossover function - Integral real-time switch ERTEC with two ports - Multi-protocol operation with ISO, TCP and UDP transport protocol and PROFINET IO - Adjustable Keep Alive funct
© Siemens AG 2007 PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 443-1 2 ■ Function The CP 443-1 independently handles data traffic over Industrial Ethernet. The module has its own powerful processor and can be put into service directly using the unique preset Ethernet address (MAC) via the network.
© Siemens AG 2007 PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 443-1 ■ Integration 2 S7-400 with CP 443-1 as IO controller PG/PC Supervisor PG/PC Supervisor PROFINET Industrial Ethernet Industrial Ethernet SCALANCE S ET 200S IE/AS-i LINK PN IO as Proxy PROFIBUS AS-Interface Interfacing to higher-level network with CP 443-1 as PROFINET IO controller S7-400 S7-400 G_IK10_XX_10220 Machine S7-300 with Vision CP 343-1 IO devices IE/PB Link PN IO as Proxy G_IK10_
© Siemens AG 2007 PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 443-1 2 ■ Technical specifications Data transmission rate ■ Ordering data 10/100 Mbit/s Autosensing Interfaces • Communication connection, electrical 1 x 15-pin Sub-D socket (10 Mbit/s AUI; 10/100 Mbit/s ITP) 1 x RJ45 (10/100 Mbit/s; TP) Current consumption • from +5 V DC (±5%) approx. 1.4 A • from 24 V DC (±5%) typ. 220 mA, max. 350 mA (depending on the interface used) Power loss 8.
© Siemens AG 2007 PROFINET/Industrial Ethernet System interfacing for SIMATIC and SINUMERIK CP 443-1 ■ Ordering data Order No. • Single license for 1 installation 6GK1 704-1LW64-3AA0 • Software Update Service for 1 year, with automatic extension; requirement: Current software version 6GK1 704-1LW00-3AL0 S7-1613 Edition 2006 Software for S7 and S5 communication, incl.
© Siemens AG 2007 PROFINET/Industrial Ethernet Accessories SICLOCK time synchronization 2 Time synchronization concepts ■ Overview The automation systems and operator stations of a SIMATIC PCS 7 plant or WinCC stations can be synchronized as follows with DCF77 or GPS time signals: • Large plants; for large plants with many network stations and stringent requirements for timekeeping, the time synchronization is performed using a SICLOCK TC 400 or SICLOCK TM/ SICLOCK TS central plant clock on the plant b
© Siemens AG 2007 PROFINET/Industrial Ethernet Accessories SICLOCK time synchronization ■ Ordering data Order No. SICLOCK TC 400 central plant clock N SICLOCK TC 400 preferred packages SICLOCK TC 400 GPS1000 SICLOCK TC 400 central plant clock with four Ethernet interfaces + GPS1000 radio clock Package comprises • SICLOCK TC 400 • SICLOCK GPS1000 system with antenna frame • Lightning protection for GPS Complete solution, e.g.
© Siemens AG 2007 PROFINET/Industrial Ethernet Accessories SICLOCK time synchronization 2 ■ Ordering data Order No.
© Siemens AG 2007 PROFINET/Industrial Ethernet Accessories SICLOCK time synchronization ■ Ordering data Order No. ■ More information 2 Accessories SIEMENS AG Set of materials for SICLOCK TM/TS I&S EDM V ERL Frauenauracher Str.
© Siemens AG 2007 PROFINET/Industrial Ethernet Distributed I/O ET 200S IM 151-3PN interface module 2 ■ Overview • Interface module for linking the ET 200S to PROFINET • Handles all data exchange with the PROFIBUS I/O controller • 3 versions: - IM151-3 PN STANDARD - IM151-3 PN HIGH FEATURE and IM 151-3 PN FO: supports, in contrast to the STANDARD version, the operation of PROFIsafe F modules • with integrated 2-port switch for line topology N Note: Micro Memory Card required for operation.
© Siemens AG 2007 PROFINET/Industrial Ethernet Distributed I/O ET 200S IM 151-3PN interface module ■ Technical specifications (continued) 6ES7 151-3AA22-0AB0 6ES7 151-3BA22-0AB0 6ES7 151-3BB22-0AB0 Yes Yes Yes Yes Yes Yes • Bus error BF (red) Yes Yes Yes • Collective error SF (red) Yes Yes Yes • Monitoring 24 V voltage supply ON Yes (green) Yes Yes • Connection to network LINK (green) Yes Yes Yes • Transmit/receive RX/TX (yellow) Yes Yes Yes between backplane bus and electronic
© Siemens AG 2007 PROFINET/Industrial Ethernet Distributed I/O ET 200S IM 151-3PN interface module 2 ■ Ordering data Order No. Order No.
© Siemens AG 2007 PROFINET/Industrial Ethernet Distributed I/O ET 200S IM 151-3PN interface module ■ Ordering data Order No.
© Siemens AG 2007 PROFINET/Industrial Ethernet ET 200pro IM 154-8 PN/DP CPU interface module 2 ■ Overview • PROFINET IO controller to operate distributed I/Os on PROFINET • Component based Automation (CBA) on PROFINET • PROFINET proxy for intelligent devices on PROFIBUS DP in Component Based Automation (CBA) • CPU with PLC functionality equivalent to S7-315-2 PN/DP, provides distributed intelligence for preprocessing • Interface module to exchange preprocessed I/O data from ET 200pro with a higher-level
© Siemens AG 2007 PROFINET/Industrial Ethernet ET 200pro IM 154-8 PN/DP CPU interface module ■ Technical specifications (continued) 6ES7 154-8AB00-0AB0 Data areas and their retentivity Bit memories • Number, max. • Retentivity available • Number of clock memories 2,048 bytes Yes; MB 0 to MB 2047 8 Data blocks • Number, max. • Size, max. • Retentivity adjustable • Retentivity pre-selected 1,023; from DB 1 to DB 1023 16 KB Yes; from DB 1 to DB 1023 Yes Local data • Per priority class, max.
© Siemens AG 2007 PROFINET/Industrial Ethernet ET 200pro IM 154-8 PN/DP CPU interface module 2 ■ Technical specifications (continued) 6ES7 154-8AB00-0AB0 • Number of remote interconnection partners 32 • Number of master/slave functions 30 • Total of all master/slave connections 1.000 • Data lengths of all incoming master/slave connections, max. 4,000 bytes • Data lengths of all outgoing master/slave connections, max.
© Siemens AG 2007 PROFINET/Industrial Ethernet ET 200pro IM 154-8 PN/DP CPU interface module ■ Technical specifications (continued) 6ES7 154-8AB00-0AB0 PROFINET IO controller • Services - PG/OP communication - Routing - S7 communication - Open IE communication Software libraries Yes Yes Yes Yes • Transmission rate, max. • Number of connectable I/O devices, max. • Addressing range - Inputs, max. - Outputs, max. 100 MB/s 128 • User data consistency, max.
© Siemens AG 2007 PROFINET/Industrial Ethernet ET 200M IM 153-4 PN 2 ■ Overview ■ Technical specifications 6ES7 153-4AA00-0XB0 Supply voltages Rated value • DC 24 V Yes Power supply and voltage jumpering • Mains/voltage failure jumpering 5 ms Current consumption Current consumption, max. 600 mA Power loss, typ.
© Siemens AG 2007 PROFINET/Industrial Ethernet ET 200M IM 153-4 PN ■ Ordering data IM 153-4 PN interface module I/O device to connect an ET 200M to PROFINET Order No. 6ES7 153-4AA00-0XB0 Accessories Bus modules for ET 200M • To accommodate a power supply and an IM 153 for the hotswapping function during RUN, incl.
© Siemens AG 2007 PROFINET/Industrial Ethernet SIMOTION Motion Control System SIMOTION P350-3 2 ■ Overview SIMOTION P350-3 is a PC-based motion control system. The use of an industrial PC platform facilitates the running of the SIMOTION machine application (comprising controller, motion control and HMI functions) alongside standard PC applications on one and the same platform. This is particularly useful in the case of applications that involve complex PC-based data management and analysis systems.
© Siemens AG 2007 PROFINET/Industrial Ethernet SIMOTION Motion Control System SIMOTION P350-3 ■ Integration ■ Technical specifications SIMOTION P350-3 PCI-Slot MCI-PN Board X21 (Port 1...4) PROFINET cable SIMATIC ET 200 e. g. ET 200S (PROFINET version) Programming device PG X4 X2 Iso PROFIBUS board X102 PROFIBUS DP SINAMICS S120 PROFIBUS cable PROFIBUS DP drive e. g. SINAMICS S120 SIMATIC ET 200 e. g. ET 200M (PROFIBUS version) PROFIBUS DP drive e. g.
© Siemens AG 2007 PROFINET/Industrial Ethernet SIMOTION Motion Control System SIMOTION P350-3 2 ■ Ordering data Order No. SIMOTION P350-3, PROFIBUS version with Intel Pentium M, 2 GHz, Windows XP Professional 4.0 English, 512 MB SDRAM, 24 V DC, with IsoPROFIBUS board • without DVD drive 6AU1350-3AK41-1BE2 • with DVD drive 6AU1350-3AK43-1BE2 SIMOTION P350-3, PROFINET version with Intel Pentium M, 2 GHz, Windows XP Professional 4.
© Siemens AG 2007 PROFINET/Industrial Ethernet SIMOTION Motion Control System SIMOTION D410 ■ Overview ■ Design 2 Interfaces Display and diagnostics • LEDs for indicating operating states and faults • 3 measuring sockets Communication • 1 x DRIVE-CLiQ • 2 x PROFINET ports (D410 PN only) • 1 x PROFIBUS DP (D410 DP only) Integrated I/Os • 4 digital inputs • 4 digital inputs/outputs (max.
© Siemens AG 2007 PROFINET/Industrial Ethernet SIMOTION Motion Control System SIMOTION D410 ■ Integration ■ Technical specifications (continued) SIMOTION D410 DP/PN PROFINET1) X200 X201 DRIVECLiQ X100 Order No. Pre-assembled cable PROFINET cables IRT/RT I/Os DRIVE-CLiQ cable PROFINET node, e.g. ET 200S Current consumption, max. (excluding digital outputs and DRIVE-CLiQ supply) 900 mA (digital inputs 10 mA) Making current, typ. 3.
© Siemens AG 2007 PROFINET/Industrial Ethernet SIMOTION Motion Control System SIMOTION D410 ■ Ordering data Order No. SIMOTION D410 DP 6AU1410-0AA00-0AA0 SIMOTION D410 PN 6AU1410-0AB00-0AA0 Backplane mounting plate For installing the SIMOTION D410 in a different location, if you do not wish to connect it directly to the Power Module.
© Siemens AG 2007 PROFINET/Industrial Ethernet SINUMERIK CNC automation systems NCU 730.2 PN 2 ■ Overview ■ Integration The following components can be connected to the SINUMERIK 840D sl: • SINUMERIK operator panel front with TCU, PCU 50.3 and machine control panel, Push Button Panel • SIMATIC CE panel • SINUMERIK handheld units • Distributed PLC I/O via PROFIBUS DP connection or PROFINET IO • SINAMICS S120 drive system • Feed and main spindle motors The NCU 730.
© Siemens AG 2007 PROFINET/Industrial Ethernet SINUMERIK CNC automation systems NCU 730.2 PN ■ Technical specifications Order No. 6FC5371-0AA10-0AA0 6FC5372-0AA00-0AA0 6FC5373-0AA00-0AA0 6FC5373-0AA01-0AA1 Product name SINUMERIK 840D sl; NCU 710.1 with PLC 317-2DP SINUMERIK 840D sl; NCU 720.1 with PLC 317-2DP SINUMERIK 840D sl; NCU 730.1 with PLC 317-2DP SINUMERIK 840D sl; NCU 730.2 PN with PLC 319-3PN/DP Processor Intel Celeron D Intel Pentium 4M Intel Pentium M • Clock frequency 1.
© Siemens AG 2007 PROFINET/Industrial Ethernet ET 200pro — RFID Systems SIMATIC RF180C ■ Overview ■ Application The PROFINET communication module SIMATIC RF180C has been specially designed for a wide range of applications in industrial automation and logistics. Due to the high degree of protection IP67, SIMATIC RF180C can be installed in the process outside the control cabinet.
© Siemens AG 2007 PROFINET/Industrial Ethernet ET 200pro — RFID Systems SIMATIC RF180C ■ Function ■ Technical specifications 2 The SIMATIC RF180C comprises a basic module and a connection block that must be ordered separately. Supply voltage • Rated value 24 V DC The connection block is available in the version M12, 7/8''. PROFINET is connected through an M12 plug, whereas the supply voltage is connected through a 7/8'' plug. There are 2 connections for PROFINET as well as for the power supply.
© Siemens AG 2007 PROFINET/Industrial Ethernet ET 200pro — RFID Systems SIMATIC RF180C 2 ■ Ordering data SIMATIC RF180C communication module For PROFINET, for connecting 2 readers; without a connection block Order No. 6GT2 002-0JD00 Accessories for MOBY Order No.