Product Overview

Technical Instructions OpenAir Spring Return 20 lb-in, Rotary GQD Series, Electric Damper Actuators
Document Number 155-760
June 23, 2008
Page 10 Siemens Building Technologies, Inc.
Start-Up/
Commissioning
GQD151
Spring Return
Modulating Control
24 Vac/dc
1. Check Operation:
a. Connect wires 1 (red) and 2 (black) to the 24 Vac/dc power supply.
NOTE: With no input signal present, the GQD151 actuator with input signal inversion
switch set to Inverse Acting, will start driving towards 90°.
b. Use a Digital Multimeter (DDM) and set the dial to Vdc for the actuator input signal.
c. Connect wires 2 (black) and 8 (gray) to the DMM.
d. Apply to input signal wire 8 (gray):
Y = 10 Vdc (GQD151 with input signal inversion switch set to Direct Acting).
Y = 2 Vdc (GQD151 with input signal inversion switch set to Inverse Acting).
Allow the actuator shaft coupling to rotate from 0° to 90°.
e. Apply to input signal wire 8 (gray):
Y = 2 Vdc (GQD151 with input signal inversion switch set to Direct Acting).
Y = 10 Vdc (GQD151 with input signal inversion switch set to Inverse Acting).
The shaft coupling returns to the "0" position.
2. Check Spring Return:
a. Set the DMM dial to Vdc.
b. Connect wires 2 (black) and 8 (gray) to the DMM.
c. Apply to input signal wire 8 (gray):
Y = 6 Vdc (GQD151)
Allow the actuator shaft coupling to rotate halfway.
d. Disconnect wire 1 (red).
The spring returns the actuator shaft coupling to the fail-safe "0" position.
e. Connect wire 1 (red) and the actuator moves.
3. Check Feedback:
a. Set the DMM dial to Vdc.
b. Attach wires 2 (black) and 9 (pink) to the DMM.
c. Apply the input signal as in Step 1d, to wire 8 (gray).
The reading at the DMM should increase (decrease for GQD151 with output signal
inversion switch set to Inverse Acting Feedback).
The reading at the DMM should decrease (increase for GQD 151 with output signal
inversion switch set to Inverse Acting Feedback) and the actuator shaft coupling
returns to the fail-safe "0" position.
GQD121.1P
Spring Return
2-Position
24 Vac/dc
1. Check Operation:
a. Connect wires 1 (red) and 2 (black) to 24 Vac/dc power supply.
Allow the actuator shaft coupling to rotate from 0° to 90°.
b. Disconnect wire 1 (red) and the actuator shaft coupling returns to the "0" position.
2. Check Spring Return:
a. Connect wire 1 (red).
Allow the actuator shaft coupling to rotate halfway.
b. Disconnect wire 1 (red).
The spring returns the actuator shaft coupling to the fail- safe "0" position.