Specifications
GEMINI
2
Traffic Outstation Handbook
667/HB/32600/000 Page 216 Issue 11
+ will now display the status for Phases I to 0 and will be remembered as the new
command for ‘.1’
.0 will display input port 0 again.
.1 will display the status for Phases I to O.
The facility is not restricted to just the commands indicated above; any valid handset
facility may be entered in any of the pointers in any order.
Note: On some handset commands it is not advisable to duplicate the command in two
or more dot buffers. If this is done then access to the other duplicate command buffers
will not be serviced. The commands affected are identified in the mnemonic code box.
13.2 HANDSET COMMAND ERROR CODES
Code
Name
Description/Mnemonic
A
Access Level
Access level for this command has not been enabled. Use
PME.
C
Non-configured
The facility to which the command relates is not available
D
Data Integrity
The data cannot be set to the specified value. Data
associated with other handset command must be modified
before this command can be set to the specified value.
F
Fixed Base
The ‘+’ or ‘-‘ keys are not applicable to current command.
I
Inaccessible
The facility to which this command relates is not
accessible.
M
Mnemonic not
recognised
The command mnemonic is not known. The command
may require a later issue of firmware.
P
Premature end
of command line
The <enter> key has been pressed too soon for this
command. Re-enter, with additional data.
R
Range error
Data or index value in preceding command out of range.
S
Syntax error
Invalid character at point preceding the asterisk.
V
Invalid current
address
The <enter>, ‘=’, ‘+’ or ‘-‘ keys have been attempted on
invalid command data.
W
Write protected
Attempt to modify read only data.