Specifications
GEMINI
2
Traffic Outstation Handbook
667/HB/32600/000 Page 320 Issue 11
Code
Major
Index
Minor
Index
Data
Range
Description
Access
Level
GLT
-
-
0 – 143
Input
number
Lamp Test
Setting this value to a valid input
number provides a lamp test
facility (for use with a green wave
box). If the allocated input is
active (i.e. “1”) then all the OTU
output relays are energised.
Default: 255 – lamp test facility
disabled.
Maint
GMO
0-255
Assigns a bit position in the UTC
control word to indicate MOVA
fallback.
Condition '1' will enable MOVA to
send force bits to the traffic
controller in place of the UTC
control bits. Condition '0' will
select normal UTC operation i.e.
all the UTC control bits will be
sent to the traffic controller
Default value is 255 indicating
that the function is disabled.
Maint
GFT
-
-
4 - 60
Overrides default UTMC OTU
timeout of 3 seconds to between
4 and 60 seconds.
Maint
Data Value
Meaning for GRL Command
0
The reply bit is driven directly from the corresponding input,
starting from the first BUS/MOVA I/O card detected.
1 to 12
Not used (was Red Lamp Monitor groups 0 to 3 on TC12)
13
OTU handset attached
14
OTU Fault present in Log
15 to 20
Not used (was count/queue/occ units on TC12 – use 60 etc)
21 to 32
Not used (was SCOOT loops on TC12 – use 100 etc)
33 to 44
Not used (was Red Lamp Monitor groups 4 to 7 on TC12)
45
Any lamp failure (future use with OMU lamp monitor)
46
Any Red failure (future use with OMU lamp monitor)
Note: These bits are also set if the lamps are switched off at
the controller.
47
combined Direct input or OTU fault present –
used to provide a single reply bit for controller or OTU fault
48
DFM failure indication
49
unit 0, HIOCC alarm bit,
50
unit 1, HIOCC alarm bit,