Technical data

Example:
Evaluating the BSTACK function:
BLOCK NO BLOCK ADDR RETURN ADDR REL ADDR DB NO DB ADDR
OB 23
FB 5
FB 6
OB 1
0063
006A
008A
009D
0064
0072
0091
009E
0001
0008
0007
0001
13
13
100
0078
078
098
In the example above, the stoppage occurred in OB 23 when processing the
STEP 5 statement at the absolute memory address "0064 - 1 = 0063".
OB 23 (QVZ error OB) was called in FB 5 at the relative address "0008 -
1 = 0007".
The data block DB 100 was opened in FB 6. When the CPU went into the
stop mode, data block DB 13 was valid.
Data block DB 13 was opened in FB 5.
5
Error Information
CPU 928B Programming Guide
C79000-B8576-C898-01
5 - 9