Technical data
Possible errors
•• Illegal function number in ACCU-2-L
•• One of the reserved bits in ACCU 1 (no. 4 to 31) is set to ’1’
In the event of error,
OB 31 (other runtime errors) is called. If OB 31
is not loaded, the CPU goes to the STOP mode.
In both cases, the error ID
1A4BH is entered in ACCU-1-L.
Notes
•• You can scan the status of the control word with the following
program sequence:
1. Load the function number 2 or 3 in ACCU-2-L
2. Load the value ’0’ in ACCU 1
3. Call special function OB 123
4. Read out ACCU 1
•• You can determine the status of interrupt processing by reading
out system data word RS 137.
- RS 137 Condition code word "delay individual
time-driven interrupts"
6
OB 123: Enable/Disable "Delay of Individual Time-Driven Interrupts"
CPU 928B Programming Guide
C79000-B8576-C898-01
6 - 27