Technical data
Parameters
1. Specifying the source:
1a) ACCU-2-L
Number of the first data word in the open data block to be transferred
2. Specifying the destination:
2a) ACCU-1-LH
First flag byte to be written to,
possible values: 0 to 255
2b)
ACCU-1-LL
Last flag byte to be written to,
possible values: 0 to 255
(The last flag byte must be ≥ the first flag byte)
Result
If special function OBs 191/193 are processed correctly, the RLO is
cleared (RLO = 0). The ACCUs remain unchanged.
In the event of an
error, the RLO is set (RLO = 1), the ACCUs
remain unchanged.
Possible errors
•• No DB or DX data block open
•• Incorrect flag area (last flag byte < first flag byte)
•• Data word number does not exist
•• DB or DX data block not long enough
6
OB 191/OB 193: Transferring Data Fields to a Flag Area
CPU 928B Programming Guide
C79000-B8576-C898-01
6 - 73