Technical data
Field ID/
length
Parameters
1st/2nd word
Meaning
1)
Table 7-1 continued:
1C00
1C01
Addressing error handling
D System stop when the event occurs and OB 25 is not loaded
No system stop when the event occurs and OB 25 is not loaded
1E00
1E01
Timeout error handling
System stop when the event occurs and OB 23/24 is not loaded
D No system stop when the event occurs and OB 23/24 is not
loaded
2000
2001
Interface error handling
System stop when the event occurs and OB 35 is not loaded
D No system stop when the event occurs and OB 35 is not loaded
EEEE End delimiter
1) D = Default with DX 0 not loaded or block missing
2) xx = field length (number of data words occupied by the parameters)
3) For updating timers, please read the explanation on the following page
4) For parameters and their significance, see the table on page 7-12.
Note
The current PG software (STEP 5/ST Vers. 6 or STEP 5/MT
Vers. 2) for generating DX 0 using a screen form does not transfer
the parameters for interface error handling (2000 or 2001) and for the
selection
"Warm restart or retentive cold restart"
(4000 or 4001).
You can enter these parameters e.g. with the "output block" PG
function (do not forget to change the block length). You can no
longer edit a DX 0 modified in this way using the output screen form
of the current PG software.
Parameters for DX 0
CPU 928B Programming Guide
7 - 10 C79000-B8576-C898-01