Technical data

RS 80
Address: EA50H (high and low):
This contains additional information to define the cause of the error
when bit 5 is set in RS 8 by the system or when control bit FE 5 is
marked in the ISTACK output.
Identifier in RS 80 Cause of error
2460H
Ready signal continuously active on the S5
bus
RS 130
Address EA82 (low):
The system data RS 130 indicates the following statuses of the
program processing level "closed loop control".
Bit no. 0 = 0 : program processing level "closed loop control"
activated
Bit no. 0 = 1 : program processing level "closed loop control"
suppressed
Before you call a restart organization block (OB 20, 21 or 22) the
system program evaluates data block DB 2 (if it exists). Depending on
the result of the evaluation, RS 130 is set or reset by the system
program. Following this, the system program calls a restart OB.
If RS 130 (LOW) is reset, the closed loop controller is processed in
cyclic operation according to the controller list in DB 2.
User Memory Organization in the CPU 928B
CPU 928B Programming Guide
8 - 28 C79000-B8576-C898-01