Technical data
Cond.
code
byte
Significance
33 The pages required for multiprocessor communication
(numbers 252 to 255) are not or not all available.
34 The pages required for multiprocessor communication
(numbers 252 to 255) are defective.
35 The parameter "automatic/manual" is illegal.
The following errors are possible:
- the "automatic/manual" ID is less than 1,
- the "automatic/manual" ID is greater than 2.
36 The parameter "number of CPUs" is illegal.
The following errors are possible:
- the number of CPUs is less than 2,
- the number of CPUs is greater than 4.
37 The parameter "block ID" is illegal.
The following errors are possible:
- the block ID is less than 1,
- the block ID is greater than 2.
38 The parameter "block number" is incorrect, since it is a data
block with a special significance.
The following errors are possible:
- if block ID = 1 DB 0, DB 1, DB 2
- if block ID = 2 : DX 0, DX 1, DX 2
39 The parameter "block number " is incorrect, since the data
block does not exist.
40 The parameter "start address of the assignment list" is too
high or the data block is too short.
41 The assignment list in the data block is not correctly
structured.
42 The sum of the assigned memory fields is greater than 48.
Errors
The "error" number group cannot occur with the INITIALIZE
function.
Warning
The "warning" number group cannot occur with the INITIALIZE
function.
Total capacity
This parameter specifies how many of the 48 available memory fields
are assigned to links.
In the "automatic" mode, this parameter always has the value 48. In the
"manual" mode, it can have a value less than 48. This means that existing
memory capacity is not used.
10
INITIALIZE Function (OB 200)
CPU 928B Programming Guide
C79000-B8576-C898-01
10 - 37