Instruction manual

Bulletin 700-HX
Plug-in Timing Relays
9-101
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P
Timing Charts
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Output Mode B: Repeat Cycle (Timer resets when power comes ON.)
Sustained Output
Power
Start signal
Gate*
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Basic Operation
Timing
Timing
Timing
Timing
Power
Start Signal
Input
Output
**
* Normal output operation will not be possible if the
set time is too short.
Set the value to at least 100 ms (contact output type).
** Start signal input is disabled diring timing.
One-Shot Output
Power
Start Signal
Gate*
Reset
Control Output
Set Value
Timing
Diagram
UP
DOWN
Set Value
0
0
Timing starts when the start signal goes ON.
The control output is turned ON when time is up.
While the start signal is ON, the timer starts when the
power cones ON or when the reset input goes OFF.
Basic Operation
Timing
Timing
Timing
Timing
Power
Start Signal
Input
**
Output
* Normal output operation will not be possible if the
set time is too short.
Set the value to at least 100 ms (contact output type).
** Start signal input is disabled during timing.
Output Mode B-1: Repeat Cycle 2 (Timer does not reset when power comes ON)
Sustained Output
Power
Start signal
Gate*
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
Timing
Sustained
Timing
Power
Start Signal
Input
**
Output
Basic Operation
* Normal output operation will not be possible
if the set time is too short
Set the value to at least 100 ms (contact
output type).
** Start signal input is disabled during.
Timing starts when the start signal goes ON.
The status of the control output is reversed when
time is up (OFF at the start).
While the start signal is ON, the timer starts when the
power comes ON or when the rest input goes OFF.
One-Shot Output
Power
Start signal
Gate*
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
Timing starts when the start signal goes ON.
The control output comes ON when time is up.
While the start signal is ON, the timer starts when
the power comes ON or when the reset input goes OFF.
Basic Operation
Timing
Timing
Sustaining
Power
Output
**
Start Signal
Input
* Normal outout operation will not be possible if the
set time is too short.
Set the value to at least 100 ms (contact output type).
** Start signal input is disabled during timing.
1 Gate not included on any mode of this relay.