Timing Charts
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Output Mode D: Signal OFF-Delay (Timer resets when power comes ON.)
Power
Start signal
Gate*
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
The control output is ON when the start signal is
ON (except when the power is OFF or the reset
is ON).
The timer is reset when the time is up.
Basic Operation
Power
Start Signal
Input
Output
Timing
**
* Output functions only during start signal input
when setting is 0.
** Start signal input is enabled during timing.
Output Mode E: Interval (Timer resets when power comes ON.)
Power
Start signal
Gate*
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
Timing starts when the start signal comes ON.
The control output is reset when time is up.
While the start signal is ON, the timer starts when
power comes ON or when the reset input goes OFF.
Basic Operation
Power
Start Signal
Input
Output
Timing
**
* Output is disabled when the setting is 0.
** Start signal input is enabled during timing.
Output Mode F: Cumulative (Timer does not reset when power comes ON)
Start signal enables timing (timing is stopped when the
start signal is OFF or when the power is OFF).
A sustained control output is used.
Basic Operation
*Output is instantaneous when setting is 0.
Power
Start Signal
Input
Output
Timing
Timing
Sustained
1 Gate not included on any mode of this relay.