Instruction manual

Bulletin 700-HXM
Plug-in Timing Relays
9-107
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P
Accessories/Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Description Pkg. Quantity Cat. No.
Replacement Flush Mounting
Adapter
(One shipped with each 700-
HXM66Z24)
1
700-HN141
Cat. No. 700-HN141
Electrical Ratings
Pilot Duty Rating NEMA B300
Rated Supply Voltage 24V DC
Operating Voltage Range 85…110% of rated supply voltage
Power Consumption 1.5 W max. (for max. DC load) (Inrush current: 15 A max.)
120V AC 30 A
Make 240V AC 15 A
120V AC 3 A
Break 240V AC 1.5 A
Hp at 120V AC 1/4 Hp
Hp at 240V AC 1/3 Hp
Mechanical
Mounting Method Flush mounting (Panel or door)
Terminal Screw Tightening Torque 0.5 N•m max.
Display
Seven-segment, negative transmissive LCD; time display (hr, min, s); CMW,
OUT, RST, TOTAL
Present value (red, 7 mm high characters); Set value (green, 3.4 mm high
characters)
Digits
PV: Four digits
SV: Four digits
When total count value is displayed: eight digits
(Zeros suppressed)
Memory Backup EEPROM (non-volatile memory) (number of writes: 100 000 times)
Counter
Maximum counting speed 30 Hz or 5 kHz
1
Counting range -999…9,999
Input modes Increment, decrement, individual, quadrature inputs
Output modes N, F, C, or K
Timer
Time ranges
0.000…9.999 s, 0.00…99.99 s, 0.0…999.9 s, 0…9999 s, 0 min
00 s…99 min 59 s, 0.0…999.9 min, 0 h 00 min…99 h 59 min,
0.0…999.9 hr, 0 h…9999 hr
Timer modes Elapsed time (Up), remaining time (Down)
Output modes A, B, D, E, F, or Z
Inputs (OV input)
Input signals
For Counter: CP1, CP2, and reset
For Timer: Start, gate, and reset
Input method
No-voltage input (contact short-circuit and open input)
Short-circuit (ON) impedance: 1 KΩ max. (Approx.
2 mA runoff current at 0Ω)
Short-circuit (ON) residual voltage: 2V DC max.
Open (OFF) impedance: 100 kΩ min.
Applied voltage: 30V DC max.
Start, reset, gate Minimum input signal width: 1 or 20 ms (selectable)
Power reset Minimum power-opening time: 0.5 s
Control Output
SPDT contact output: 5 A at 250V AC/30V DC, resistive load (cos φ = 1)
Minimum Applied Load 10 mA at 5V DC (failure level: P, reference value)
Reset System External, manual, and power supply resets (for timer in A, B, D, E, or Z modes)
Sensor Waiting Time
260 ms max. (Inputs cannot be received during sensor wait time if control
outputs are turned OFF.)
1 The figures given for maximum counting speed are for incrementing or decrementing operation with a prescale value of x1. If prescaling is used and 5 kHz is
set, the maximum counting speed will be reduced to about half. The non-prescaling maximum counting speed will also be reduced to about half when the
up/down mode is selected.
“700-HXM User Manual” pub. no. 700-UM001*
Specifications
Accessories