Instruction manual
Bulletin 700-HXM
Plug-in Timing Relays
9-108
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P
Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Characteristics
Timer Function
Signal start: ±0.03% ±30 ms max.
Power-ON start: ±0.03% ±50 ms max.
Insulation Resistance
100 mΩ min. (at 500V DC)
Dielectric Strength
1500V AC, 50/60 Hz for 1 min between output terminals and non-current-carrying metal parts
510V AC, 50/60 Hz for 1 min between current-carrying terminals (except output terminals) and
non-current-carrying metal parts
1500V AC, 50/60 Hz for 1 min between output terminals and current-carrying terminals (except
output terminals)
500V AC, 50/60 Hz for 1 min between communications terminals and current-carrying terminals
(except output terminals)
1000V AC, 50/60 Hz for 1 min between contacts not located next to each other
Noise Immunity
Square-wave noise by noise simulator;
±480V (between power terminals), ±600 V (between input terminals)
Static Immunity ±8 kV (malfunction), ±15 kV (destruction)
Vibration Resistance Malfunction 10…55 Hz with 0.35 mm single amplitude each in three directions for 10 min.
Shock Resistance Malfunction 100 m/s
2
(approx. 10 G), 3 times each in six directions
Life Expectancy
Mechanical 10 million operations
Electrical 100 000 operations min (3 A at 250V AC, resistive load)
Ambient Temperature
Operating -10…55 °C (with no icing or condensation)
Storage -25…65 °C (with no icing or condensation)
Ambient humidity 25…85%
EMC
(EMI):
Emission Enclosure: EN61326 Class A
(EMS): EN61326
Immunity ESD:EN61000-4-2:4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference:EN61000-4-3:10 V/m (Amplitude-modulated,
80 MHz…1 GHz) (level 3);
10 V/m (Pulse-modulated,
900 MHz ±5 MHz) (level 3)
Immunity Conducted
Disturbance:EN61000-4-6:3 V (0.15…80 MHz) (level 2)
Immunity Burst:EN61000-4-4:2 kV power-line (level 3);
1 kV I/O signal-line (level 4);
1 kV communications-line (level 3)
Immunity Surge:EN61000-4-5:1 kV between lines
(power and output lines) (level 3);
2 kV between grounds
(power and output lines) (level 3)
Enclosure Ratings
Panel surface: IP66 and NEMA Type 4 (indoors)
Rear case: IP20
Terminal block: IP20
Weight Approx. 80 g
Certifications
cURus Recognized Component (File No. E14843, Guide NRNT2/NRNT8), CE Marked, C-Tick
Marked
Standards EN61010-1, EN 61326, UL 508, CSA C22.2 No. 14