Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Type 700-P, PL, PT 700-PK, PKL, PKT 700-PH
Electrical
Contact Rating Continuous
10 A @ 600V AC
5 A @ 600V DC
20 A @ 600V AC
10 A @ 600V DC
35 A @ 600V AC
20 A @ 600V DC
Ratings
Make/Break
AC NEMA A600 2 x NEMA A600 2 x NEMA A600
DC NEMA P600 2 x NEMA P600 2 x NEMA P600
Additional Contact Ratings for
AC single-phase loads
3 Hp @ 240V AC - N.O.
2 Hp @ 240V AC - N.O./N.C.
1 Hp @ 120V AC - N.O./N.C.
20 A Resistive Heating to 600V AC
20 A Tungsten Lighting Load to 480V AC
5 Hp @ 240V AC - N.O.
3 Hp @ 240V AC - N.O./N.C.
2 Hp @ 120V AC - N.O./N.C.
35 A General Use At 0.75 PF to 600V AC
35 A Tungsten Lighting Load to 480V AC
DC Current
Ratings Make/Break
Cartridge Cat. No. 700-CP1 Cartridge Cat. No. 700-CPM Cartridge Cat. No. 700-CPH
DC Switching
Contacts in
Series
Volts DC
24 64 125 250 500 600 24 64 125 250 500 600
24 64 125 250 500 600
480W 480W 275W 138W 135W 120W
1 5 A 2.2 A 1.1 A .55 A .24 A .2 A 10 A 5 A 2.2 A .55 A .24 A .2 A 10 A 5 A 2.2 A .55 A .24 A .2 A
2 10 A 10 A 5 A 2 A .7 A .5 A 20 A 10 A 5 A 2 A .7 A .5 A 20 A 10 A 5 A 2 A .7 A .5 A
3 7 A 3 A 1.5 A 1.0 A 15 A 7 A 3 A 1.5 A 1.0 A 15 A 7 A 3 A 1.5 A 1.0 A
4 10 A 5 A 2.5 A 1.5 A 20 A 10 A 5 A 2.5 A 1.5 A 20 A 10 A 5 A 2.5 A 1.5 A
Coil Voltage
Range
AC 85…110% 85…110% 85…110%
DC 80…110% 80…110% 80…110%
Battery
Charging
85…115% 85…115% 85…115%
Coil
Consumption
P-PH-PK
50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz
A
C
Inrush
132VA
138VA 132VA 138VA 132VA 138VA
Sealed
19.3V
A 19VA 19.3 VA 19VA 19.3VA 19VA
D
C
Inrush
12.7V
A 12.7VA 12.7VA
Sealed
12.7VA 12.7VA 12.7VA
PLL - PKLL
AC Latch Unit
Inrush
15V
A 15.6VA 5VA 15.6VA 15VA 15.6VA
Sealed
5.4VA 5.5VA 5.4VA 5.5VA 5.4VA 5.5VA
PLL - PKLL
DC Latch Unit
Unlatch
35V
A 35VA
Intermittent
35 W 35 W
Reset Time PT – PKT 75 ms 75 ms
Minimum Pulse PLL–PKLL 75 ms 75 ms
Mechanical
Operating Time
Pickup
AC – 10…20 ms
DC – 30…50 ms
AC – 10…20 ms
DC – 30…50 ms
AC – 10…20 ms
DC – 30…50 ms
Dropout
AC – 10…20 ms
DC – 20…33 ms
AC – 10…20 ms
DC – 20…33 ms
AC – 10…20 ms
DC – 20…33 ms
Mechanical Life 10 million operations
Construction
Contact Arrangement
Up to 12 Poles, Convertible to N.O. or
N.C. (8 N.C. Maximum)
Up to 12 Poles, Convertible to N.O. or
N.C. (8 N.C. Maximum)
Up to 6 Poles, Convertible to N.O. or
N.C. (4 N.C. Maximum)
Contact Material Nickel Silver Silver Cadmium Oxide Silver Cadmium Oxide
Mounting
Panel or Strip Mount
Horizontal Mounting Recommended
Panel or Strip Mount
Horizontal Mounting Recommended
Panel or Strip Mount
Horizontal Mounting Recommended
Environmental
Temperature
Operating
1
–20…+65 °C (–4…149 °F) –20…+65 °C (–4…149 °F) –20…+65 °C (–4…149 °F)
Storage –40…+65 °C (–40…149 °F) –40…+65 °C (–40…149 °F) –40…+65 °C (–40…149 °F)
Certifications CSA Certified, CSA File #LR1234, UL Listed, UL File #E14840, Guide NKCR, CE Certified, ABS
Standards UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -5-1
Wire Terminations
Wire size per UL/CSA #18 AWG…(2) #12 AWG
Tightening Torque 8…12 lb•in (0.9…1.4 N•m)
1 Temperature inside the panel.
Average value for all coils within range. For values on a specific coil voltage, contact your local Rockwell Automation sales of
fice or Allen-Bradley distributor.