Instruction manual
Bulletin 700S-P
Heavy-Duty Industrial Safety Relays
9-129
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P
Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Type 700S-PK
Electrical
Contact Rating
Continuous
20 A @ 600V AC
10 A @ 600V DC
Ratings
Make/
Break
AC NEMA A600
DC NEMA P600
Additional Contact
Ratings for AC
Single-Phase Loss
3 Hp @ 240V AC - N.O.
2 Hp @ 240V AC - N.O./N.C.
1 HP @ 120V AC - N.O./N.C.
20 A resistive heating to 600V AC
20 A Tungsten lighting load to 480V AC
DC Current Ratings
Make/Break
Cartridge Cat. No. 700-CMS
DC
Switching
Contacts
in Series
Volts DC
24V 64V 125V 250V 500V 600V
1 10 A 5 A 2.2 A 0.55 A 0.24 A 0.2 A
2 20 A 10 A 5 A 2 A 0.7 A 0.5 A
3 — 15 A 7 A 3 A 1.5 A 1.0 A
4 — 20 A 10 A 5 A 2.5 A 1.5 A
Coil
Voltage
Range
1
AC 85…110%
DC 80…110%
Battery
Charging
85…115%
Coil Consumption 50 Hz 60 Hz
AC
Inrush 132 VA 138 VA
Sealed 19.3 VA 19 VA
DC
Inrush 12.7 W
Sealed 12.7 W
Mechanical
Mechanically Linked
Contacts
All contacts are mechanically linked per IEC 947-5-1
annex L for 2 to 12 poles
Operating
Time
Pickup
AC – 10…20 ms
DC – 30…50 ms
Dropout
AC – 10…20 ms
DC – 20…33 ms
Construction
Contact Arrangement
2 to 12 Poles, Convertible to
N.O. or N.C. (8 N.C. Maximum)
Contact
Material/Design
Silver Cadmium Oxide
Mechanical
(Mechanically-Linked
Contacts)
All contacts, are mechnically linked per IEC 947-5-1
Annex L for 2 to 12 poles
Mounting Panel mount or strip mount recommended
Environmental
Operating‡
Temperature
-20…+65 °C (-4…+149 °F)
-40…+65 °C (-40…+149 °F)
CSA certified, CSA file #LR1234, UL listed, UL file
#E14840, Guide NKCR, CE certified IEC 947-5-1, IEC
336-1 CENELEC, BS 4794, VDE 0660, Listed: U.S.
Coast Guar
d and American Bureau of Shipping, UL
508, CSA22.2
Wire Terminations
Wire size per UL/CSA #18 AWG…(2) #12 AWG
Tightening Torque 8…12 lb•in (0.9…1.4 N•m)
1 Coil voltage required for proper operation (percent of rated coil voltage).
‡ Temperature inside the panel.
Type 700S-P
Electrical
Contact Rating
Continuous
10 A @ 600V AC
5 A @ 600V DC
Ratings
Make/
Break
AC NEMA A600
DC NEMA P600
Minimum Contact
Switching Ratings
10V, 50 mA
DC
Switching
Contacts
in Series
Volts DC
24V 64V 125V 250V 500V 600V
1 5 A 2.2 A 1.1 A 0.55 A 0.24 A 0.2 A
2 10 A 10 A 5 A 2 A 0.7 A 0.5 A
3 — — 7 A 3 A 1.5 A 1.0 A
4 — — 10 A 5 A 2.5 A 1.5 A
Contact Electrical Life—
Resistive Loads
1.5 million operations at 10A break at 120V AC
14 million operations at 1A break at 120V AC
6 million operations at 1A break at 24V DC
Coil
Voltage
Range
1
AC 85…110%
DC 80…110%
Battery
Charging
85…115%
Coil Consumption 50 Hz 60 Hz
AC
Inrush 132 VA 138 VA
Sealed 19.3 VA 19 VA
DC
Inrush 12.7 W
Sealed 12.7 W
Mechanical
Mechanically Linked
Contacts
All contacts are mechanically linked per IEC 947-
5-1 annex L for 2 to 12 poles
Operating
Time
Pickup
AC – 10…20 ms
DC – 30…50 ms
Dropout
AC – 10…20 ms
DC – 20…33 ms
Mechanical Life 10 million operations
Construction
Contact Arrangement
2 to 12 Poles, Double Break Contacts
N.O. or N.C. (8 N.C. Maximum)
Contact Material/Design Silver Nickel/Bifurcated
Mounting
Panel mount or mount on 700-MP Relay or DIN
Rail Horizontal Mounting Recommended
Environmental
Operating Temperature‡ -20…+65 °C (-4…+149 °F)
Storage T
emperature -40…+65 °C (-40…+149 °F)
Wire Terminations
Wire size per UL/CSA #18 AWG…(2) #12 AWG
Tightening Torque 8…12 lb•in (0.9…1.4 N•m)
1 Coil voltage required for proper operation (percent of rated coil voltage).
‡ Temperature inside the panel.