Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Bul. 700-N Bul. 700-NT
Electrical Ratings
Rated Thermal Current
I
th
10 A
Rated Insulation Voltage 300V
Contact Rating 10 A @ 300V AC, NEMA A300
Coil Voltage Range
AC 85…110% —
DC 80…110% —
Coil Consumption
50 Hz 60 Hz —
AC
Inrush 120 VA 133 VA —
Sealed 24 VA 20 VA —
Mechanical
AC —
Max.
Operating Time
Pickup 14 ms —
Drop Out 13 ms —
Timing Range — 0.2…60 s
Repeat Accuracy — ±15% of setting
Reset Time — 75 ms
Timing Mode —
On-Delay — convertible to OFF Delay, up to 2 poles
convertible to N.O. or N.C.
Construction
Contact Arrangement Up to 8 Poles, Convertible to N.O. or N.C. —
Contact Material Silver Silver
Mounting
Panel or strip mount
Horizontal mounting recommended
On relay only
Environmental
Ambient Temperature (Outside
Enclosure)
Operating –20…+40 °C (–4…+104 °F)
Storage –40…+60 °C (–40…+140 °F)
Operating Temperature Rise
(Inside Enclosure)
+25 °C Max —
Wire Terminations
Wire size per UL/CSA #18 AWG…(2) #12 AWG
Tightening Torque 8…12 lb•in. (0.9…1.4 N•m)