Product Overview/Product Selection/Specifications
Bulletin 700-PS — Solid State Timing Relay
Solid-state timer
600V AC maximum, 300V DC maximum
Time range 0.1…120 sec
Can be attached to a Bulletin 700 Type P, PK, R and RM relay
Convertible to ON-Delay or OFF-Delay
Table of Contents
Product Selection......
this page
Specifications.............. this page
Approximate
Dimensions...................
9-146
Standards Compliance
UL 508
UL 1604
CSA C22.2 No. 14
C22.2 No. 213
Certifications
cULus Listed (File No.
E10319, Guide NOIV/NOIV7)
CSA Certified (File No.
LR11924)
Bulletin 700-PS
Operating Mode Timing Range1[s]
Timing Relay with Self-
Contained Potentiometer Unit
Timing Relay for Use with
External Potentiometer Unit
Cat. No. Cat. No.
On-Delay
0.1…2
700-PSAA1 700-PSRAA1
0.4…8
700-PSBA1 700-PSRBA1
1.5…30
700-PSCA1 700-PSRCA1
6…120
700-PSDA1 700-PSRDA1
Off-Delay
0.1…2
700-PSPA1 700-PSRPA1
0.4…8
700-PSRA1 700-PSRRA1
Cat. No. 700-PSPA1
1.5…30
700-PSTA1 700-PSRTA1
6…120
700-PSUA1 700-PSRUA1
Accessories
Description Cat. No.
Adapter Plate — For mounting Bulletin 700-PS timers directly on a panel or on Bulletin
700-MP universal mounting strips.
700-N25
Adapter for Bulletin 700-R, -RM Relays
Allows you to mount the Bulletin 700-PS timer on a 1…4 pole Bulletin 700-R or -RM relay.
700-N26
Timing Range
1 Resistance[mΩ]
Cat. No. 700-N25
0.1…2
(0.4…8)
0.75
700-N35
0.1…2
(0.4…8)
0.75
700-N35
1.5…30 2.0
700-N36
Cat. No. 700-N26 6…120 3.5
700-N37
1 The maximum range may be 50% greater and the minimum range may be 50% less than the values specified.
This Cat. No. includes only the potentiometer. Order Cat. No. 800T
-N37 for the potentiometer operator and housing.
Specifications
Bulletin 700-PS
Operation
The timer must be energized continuously (L1-L2). ON-Delay: When the initiating contact closes, timing begins. At time-out, the output
contact closes. OFF-Delay: When the initiating contact closes, the output contact closes instantly. When the initiating contact re-opens,
timing begins. At time-out, the output contact re-opens.
Type PS Timer
110/120V, 50/60 Hz
To Load
Contact
Output
C1 S1 S2
L2L1C2
(See Attention)
Initiating Contact
External
Attention — To avoid damage to timer, do not switch any load
in addition to timing relay at terminals S1–S2. Do not apply an
external voltage to terminals S1–S2.
External Potentiometer units have R1, R2 terminals for
connecting the potentiometer.
Typical Wiring Diagram