Product Overview/Product Selection/Specifications
Bulletin 700-PS — Solid State Timing Relay
Solid-state timer
600V AC maximum, 300V DC maximum
Time range 0.1…120 sec
Can be attached to a Bulletin 700 Type P, PK, R and RM relay
Convertible to ON-Delay or OFF-Delay
Table of Contents
Product Selection......
this page
Specifications.............. this page
Approximate
Dimensions...................
9-146
Standards Compliance
UL 508
UL 1604
CSA C22.2 No. 14
C22.2 No. 213
Certifications
cULus Listed (File No.
E10319, Guide NOIV/NOIV7)
CSA Certified (File No.
LR11924)
Bulletin 700-PS
Operating Mode Timing Range1[s]
Timing Relay with Self-
Contained Potentiometer Unit
Timing Relay for Use with
External Potentiometer Unit
Cat. No. Cat. No.
On-Delay
0.1…2
700-PSAA1 700-PSRAA1
0.4…8
700-PSBA1 700-PSRBA1
1.5…30
700-PSCA1 700-PSRCA1
6…120
700-PSDA1 700-PSRDA1
Off-Delay
0.1…2
700-PSPA1 700-PSRPA1
0.4…8
700-PSRA1 700-PSRRA1
Cat. No. 700-PSPA1
1.5…30
700-PSTA1 700-PSRTA1
6…120
700-PSUA1 700-PSRUA1
Accessories
Description Cat. No.
Adapter Plate — For mounting Bulletin 700-PS timers directly on a panel or on Bulletin
700-MP universal mounting strips.
700-N25
Adapter for Bulletin 700-R, -RM Relays
Allows you to mount the Bulletin 700-PS timer on a 1…4 pole Bulletin 700-R or -RM relay.
700-N26
Timing Range
1 Resistance[mΩ]
Cat. No. 700-N25
0.1…2
(0.4…8)
0.75
700-N35
0.1…2
(0.4…8)
0.75
700-N35
1.5…30 2.0
700-N36
Cat. No. 700-N26 6…120 3.5
700-N37
1 The maximum range may be 50% greater and the minimum range may be 50% less than the values specified.
This Cat. No. includes only the potentiometer. Order Cat. No. 800T
-N37 for the potentiometer operator and housing.
Specifications
Bulletin 700-PS
Operation
The timer must be energized continuously (L1-L2). ON-Delay: When the initiating contact closes, timing begins. At time-out, the output
contact closes. OFF-Delay: When the initiating contact closes, the output contact closes instantly. When the initiating contact re-opens,
timing begins. At time-out, the output contact re-opens.
Type PS Timer
110/120V, 50/60 Hz
To Load
Contact
Output
C1 S1 S2
L2L1C2
(See Attention)
Initiating Contact
External
Attention — To avoid damage to timer, do not switch any load
in addition to timing relay at terminals S1–S2. Do not apply an
external voltage to terminals S1–S2.
‡ External Potentiometer units have R1, R2 terminals for
connecting the potentiometer.
Typical Wiring Diagram‡