700-HA Relay Performance Graphs
Time Module Cat. No. 700-HT3
Electrical Ratings
Operating Voltage Range 12…240V AC (50/60 Hz) 12…240V DC
Power Consumption
0.1 W (12V)
1.0 W (230V)
Mechanical
Degree of Protection of Input (B1) Terminal IP 20 (Guarded Terminal)
Input Terminal Wire Range
1.0 x 0.2 mm
2
…2.5 mm
2
(24 AWG…14 AWG)
2.0 x 0.2 mm
2
…1.5 mm
2
(24 AWG…16 AWG)
Input Terminal Torque Range 0.45…0.8 Nm (4…7 lb-in.)
LED Indicator Red
Repeat Accuracy
±1%
Recovery Time
<50 ms
Selectable Timing Ranges
Three DIP switches, seven ranges (set from 5…100% of range):
1 s, 10 s, 100 s, 10 min, 100 min, 10 h, 100 h
Selectable Timing Modes
Three DIP switches, eight modes:
1. Power On–Delay
2. Power On One-Shot
3. Power On Repeat Cycle, On Start
4. Signal On-Delay and Signal Off-Delay
5. Signal Off-Delay
6. Signal On-One-Shot
7. Signal Off-One-Shot
8. Signal On and Signal Off Watchdog Monitor
Adjustable Trimmer Scale Accuracy ±5% of Time Range
Environmental
Temperature
Operating –20 °C…+50 °C (–4 °F…+122 °F)
Storage –55 °C…+85 °C (–67…+185 °F)
Altitude 2000 m (6560 ft)
Construction
Enclosure Gray Plastic Housing
Mounting with Socket Only 8- or 11-Pin Socket with Module Plug
Sockets
700-HN204 (8-Pin with Plug)
700-HN205 (11-Pin with Plug)
Certifications cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), CE Marked
Standards UL508, CSA C22.2 No. 14, EN 61810-1, EN 60255-23
1 Performance Data - See this publication, Important 3.
At constant voltage and temperature.
Load (kVA)
Cycles
k Reduction Factor
Voltage DC (V)
Max. Switching Current (A)
COS
Contact life vs. AC1 load at 1,800 cycles/h
Breaking capacity for DC1 load at 1,800 cycles/h.
Load reduction factor vs. cos
φ
A = load applied to one contact
B = load applied to two contacts in series
C = load applied to three contacts in series
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Specifications
9-15
Bulletin 700-HA
General Purpose Relays
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P