Instruction manual

Bulletin 700-CF
IEC Industrial Control Relays
9-152
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P
Accessories
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Description (Relays)
Connection
Diagrams
For Use With
(Relays) Cat. No.
DC Interface (electronic)
Interface between the DC control signal (PLC)
and the AC operating mechanism of the
control relay.
Control (input) voltage
12V DC
18…30V DC (24V nominal)
48V DC
Requires no additional surge suppression on
the relay coils
Input:
18…30V DC
Output:
110…240V AC
E1, E2 = DC Signal
700-CF with
110…240V AC
coils
100-JE
Input:
12V DC
Output:
110…240V AC
100-JE12
Input:
48V DC
Output:
110…240V AC
100-JE48
Cat. No. 100-JE
Cat. No. 100-JE Cat. No. 100-JE12 Cat. No. 100-JE48
Electrical
Input Voltage 24V DC 12V DC 48V DC
Input Voltage Range 18…30V DC 6…12V DC 35…48V DC
Output Voltage 110…240V AC 110…240V AC 110…240V AC
Power Consumption 0.1…0.4 W 0.02…0.12 W 0.2…0.5 W
Minimum Actuation 5V DC, 2 mA DC 5V DC, 2 mA DC 5V DC, 2 mA DC
Mechanical
Finger Protection IP20 IP20 IP20
Pickup Time
0…10 ms + pickup time
of the
contactor
0…10 ms + pickup time
of the
contactor
0…10 ms + pickup time
of the
contactor
Dropout Time
0…10 ms + dropout time
of the contactor
0…10 ms + dropout time
of the contactor
0…10 ms + dropout time
of the contactor
Max. Cycles Per Second 2
1 21 21
Isolation/Breakdown Voltage In: 50V, Out: 250V In: 50V, Out: 250V In: 50V, Out: 250V
Rated Impulse Withstand Voltage 4 kV 4 kV 4 kV
Environmental
Ambient Temperature Range -25…60 °C -25…60 °C -25…60 °C
Storage Temperature Range -50…+80 °C -50…80 °C -50…80 °C
Operating Life 100+ million ops 100+ million ops 100+ million ops
Construction
Wire Size Range
Flexible wire
1 Wire 0.5…2.5 mm
2
0.5…2.5 mm
2
0.5…2.5 mm
2
2 Wire 0.75…2.5 mm
2
0.75…2.5 mm
2
0.75…2.5 mm
2
Solid wire
1 Wire 1.0…2.5 mm
2
1.0…2.5 mm
2
1.0…2.5 mm
2
2 Wire 1.0…2.5 mm
2
1.0…2.5 mm
2
1.0…2.5 mm
2
Solid and Stranded 18…14 AWG 18…14 AWG 18…14 AWG
Tightening Torque 1…1.5 N•m/7…15 lb•in 1…1.5 N•m/7…15 lb•in 1…1.5 N•m/7…15 lb•in
Type of Light LED LED LED
1 To consider the maximum operations/hour of the relays.
Assembly Components
Description For Use With Pkg. Quantity1 Cat. No.
Protective Covers
Provides protection against unintended manual operation
700-CF all 1
100-SCCA
Cat. No. 100-SCCA
Protective Covers
Provides protection against unintended manual operation
For front mounted auxiliary contacts, pneumatic timers and latches
100-FA, -FB, -FC, -
FP, -FL;
10
100-SCFA