Instruction manual
Bulletin 700-CF
IEC Industrial Control Relays
9-155
Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Control Circuit General
Cat. No. 700-CF
Rated Insulation Voltage U
i
IEC 690V
UL; CSA 600V
Rated Impulse StrengthU
imp
6 kV
High Test Voltage
1 minute (per IEC 60947-4)
2500V
Rated Voltage U
e
AC 115, 230, 400, 500, 690V
DC 24, 48, 110, 220, 440V
Short-Circuit Protection gG Fuse 10 A
Rated Frequency 50/60 Hz, DC
Ambient Temperature
Storage –55…+80 °C (–67…176 °F)
Operation at nominal current –25…+60 °C (–13…140 °F)
15% current reduction
for AC-12 at > 60 °C
–25…+70 °C (–13…158 °F)
Corrosion Resistance
humid-alternating climate, cyclic,
per IEC 60068-2-30 and
DIN 50 016, 56 cycles
Altitude
2000 m above mean sea level, per
IEC60 947-4
Type of Protection
IP2X (IEC 60529 and DIN 40050) in connected state
Shock Resistance
IEC 60068-2: Half sinusoidal shock
11 ms, 30 G (in 3 directions)
Vibration Resistance
IEC 60068-2: Static >2 G, in normal
position no malfunction <5 G
Verification of Making and Breaking Capacities of Switching Elements Under Normal Conditions
Corresponding to the Utilization Categories
Utilization
Category
Normal Condition of Use
Make‡ Break‡
Number and Rate of Making and Breaking
operations
I
/
I
e
U/U
e
cos ψ
I
/
I
e
U/U
e
cos ψ
No. operating
cycles§
Operating cycles per
minute
ON time [s]
®
AC-12
1 1 0.9 1 1 0.9 6050 6 0.05
AC-13
2 1 0.65 1 1 0.65 6050 6 0.05
AC-14
6 1 0.3 1 1 0.3 6050 6 0.05
AC-15
10 1 0.3 1 1 0.3 6050 6 0.05
DC
— —
T
0.95
——
T
0.95
———
DC-12 1 1 1 ms 1 1 1 ms 6050 6 0.05
®
DC-13 1 1
6 x P♣
11
6 x P♣
6050 6 0.05
®
DC-14
10 1 15 ms 1 1 15 ms 6050 — 0.05
®
I
e
Rated operational current,
I
Current to be made or broken
U
e
Rated operational voltage, U Voltage before make
PU
e
I
e
Steady-state power consumption (W)
T
0.95
Time to reach 95% of the steady-state current (ms)
See sub-clause 8.3.3.5.2.
‡ For tolerances on test quantities, see sub-clause 8.3.2.2.
§ The first 50 operating cycles shall be run at U/U
e
=1.1 with the loads set at U
e
.
♣ The value “6 x P” r
esults from an empirical relationship which is found to represent most DC magnetic loads to an upper limit of P = 50 W, e.g., 6 x P= 300 W.
® The ON time shall be at least equal to T
0.95
.
Where the break current differs from the make current value, the ON time refers to the make current value after which the current is r
educed to the break
current value for a suitable period e.g., 0.05 s.
Utilization Category Table from EN 60947-5-1
Cat. No. 700-CF
Operating Voltage
AC 50/60 Hz
Pickup
[x U
s
]
0.85…1.1
Dropout
[x U
s
]
0.3…0.6
DC
1
Pickup
[x U
s
]
0.8…1.1
Dropout
[x U
s
]
0.1…0.6
Coil Consumption
AC 50/60 Hz
Inrush [VA/W] 70/50
Seal [VA/W] 8/2.6
DC (conventional) Inrush/Seal [W] 6.5
DC (electronic)
Inrush (avg./
peak)
[W] 10/17
Seal [W] 1.7
Operating Times
AC 50/60 Hz
Pickup Time [ms] 15…30
Dropout Time [ms] 10…60
DC (conventional)
Pickup Time [ms] 40…70
Dropout Time [ms] 7…15
DC (electronic)
Pickup Time [ms] 25…50
Dropout Time [ms] 25…50
Min OFF time [ms] 200
Max. ripple ± 15%
Latch Attachment Release, 100-FL
Coil Consumption
AC [VA/W] 45/40
DC [W] 25
Contact Signal Duration [min./max] 0.03…15 s
Timing Attachment
Reset Time, 100-
ETA, 100-ETB
at min. time
setting
[ms] 10
at max. time
setting
[ms] 70
Repeat Accuracy ± 10%
1 For 9V DC, code ZR, use operating voltage 0.65…1.3 x U
s
.
For 24V DC, code ZJ, DJ, or EJ use operating voltage 0.7…1.25 x U
s
.
For 110V DC, code ED use operating voltage 0.7…1.25 x U
s
.
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P