Instruction manual
Bulletin 700-K
IEC Industrial Control Relays
9-166
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P
Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
700-K
DC-13/Q600
1 pole 24V [A] 2.3
48V [A] 1
110V [A] 0.55
125V [A] 0.55
220V [A] 0.27
250V [A] 0.27
400V [A] 0.15
440V [A] 0.15
600V [A] 0.1
Cross Sections
Coil Data
700-K
Operating Limits
AC control
50 Hz, 60 Hz, 50/60 Hz
pick-up
[x U
s
]
0.85…1.1
dropout
[x U
s
]
0.2…0.75
DC control
pick-up
[x U
s
]
0.8…1.1
9, 12, 24, 110V DC: 0.7…1.25
dropout
[x U
s
]
0.1…0.75
Coil Consumption
AC control
50 Hz, 60 Hz, 50/60 Hz
pick-up [VA/W] 35/32
hold-in [VA/W] 5/1.8
DC control
pick-up [W] cold 3.0, warm 2.6
hold-in [W] cold 3.0, warm 2.6
Operating Times
AC
closing delay [ms] 15…40
opening delay [ms] 15…33
With RC module opening delay [ms] 15…28
DC
closing delay [ms] 18…40
opening delay [ms] 6…12
With integrated diode opening delay [ms] 8…12
With external diode opening delay [ms] 35…50
Conductor Cross Sections
- Main Contacts, Auxiliary Contacts, and Coil
Terminals
700-K 700-KR
Terminal type
1
Fine stranded
with ferrule
(1) Conductor
(2) Conductors
[mm
2
]
[mm
2
]
0.75…2.5
0.75…2.5
0.50…2.5
0.50…2.5
Solid or coarse
stranded
(1) Conductor
(2) Conductors
[mm
2
]
[mm
2
]
1…4
1…2.5 + 1…4
0.75…2.5 §
0.75…2.5 §
Recommended torque [Nm] 1.2 —
Cross section per UL/CSA [AWG]
18…12
18…14 §
Recommended torque [lb-in] 10.6 —
1 Pozidriv No. 2 / Blade No. 3 screw
Use same cross sections
§ Stranded wire only