Instruction manual
Bulletin 700-SF
Solid-State Relays
9-180
Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Specifications
Control/Input Ratings
Cat. No.
Rated Control
Voltage
Max. Operating
Control Voltage
Range [V DC]
Max. Reverse
Control Voltage [V] Impedance
Control Voltage Levels
Pick-up Voltage Drop-out Voltage
700-SFZY3Z25 5…24V DC 4…28V DC –32 15 mA max.
1
4V DC max. 1V DC min.
700-SFTY3Z24 24V DC 19.2…28.8V DC –28.8
2 kΩ ± 20%
19.2V DC max. 1V DC min.
700-SFNY3Z25 5…24V DC 4…28V DC –28.8
1.5 kΩ +
20%/–10%
4V DC max. 1V DC min.
Load/Output Ratings
Cat. No. Rated Load Voltage
Max. Load Voltage
Range
Continuous Load Current (Resistive) [A]
Max. Inrush Current‡Min. Max.§
700-SFZY3Z25
100…240V AC 75…264V AC
0.1 3
45 A @ 50/60 Hz, 1 cycle
700-SFTY3Z24 0.1 3
700-SFNY3Z25 4…48V DC 3…52.8V DC 0.1 3 18 A (10 ms)
Characteristics
Description Cat. No. 700-SFZY3Z25 Cat. No. 700-SFTY3Z24 Cat. No. 700-SFNY3Z25
Load Switching Method/Device Triac Transistor
Pick-up Time
1/2 cycle of load power source cycle
time ♣ + 1 ms max.
1 ms max.
0.5 ms max.
Drop-out Time
1/2 cycle of load power source cycle time♣ + 1 ms max.
2 ms max.
Output ON V
oltage Drop 1.6V (RMS) max. 1.5V max.
Output Leakage Current
5 mA max. (@ 100 V AC);
10 mA max. (@ 200 V AC)
2.5 mA max. (@ 100V AC);
5 mA max. (@ 200V AC)
5 mA max. (@ 50V DC)
Output V
DRM
, V
CEO
(V)
600 600 80
Output di/dt (A/uS) 50 50 —
Output dv/dt (V/uS) 250 250 —
Output
I
2
t (A
2
S)
18 18 —
Output Tj (°C) Max. 125 125 150
Insulation Resistance
100 MΩ min. (at 500V DC)
Dielectric Strength 1,500V AC, 50/60 Hz for 1 min
Vibration Resistance (Max.) 10…55 Hz, 1.5 mm double amplitude (10 G)
Shock Resistance (Max.) 1000 m/s
2
(100 G)
Ambient Temperature
Operating: –30…+80 °C (–22…+176 °F) with no icing or condensation
Storage: –30…+100 °C (–22…=212 °F) with no icing or condensation
Ambient Humidity 45…85% (no condensation)
Standards Compliance UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -4-3, EN/IEC 60950
Certifications cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, VDE Certified
Weight Approx. 50 g
1 With constant curent input circuit system, SSR impedance varies with a change in input voltage.
Input impedance reaches its maximum at the operating voltage.
‡ If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to the “Inrush Current Resistivity” graphs on page 9-181 for mor
e
details.
§ Refer to “Load Current vs. Ambient Temperature Characteristics” on page 9-181 for additional load current details.
♣ 60 Hz full cycle time = 16.6 ms, 50 Hz full cycle time 20 ms.
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P