Instruction manual

Bulletin 700-SF
Solid-State Relays
9-181
Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Note: This data is non-repetitive. Keep the inrush current to half the rated value if it occurs repetitively. Inrush current resistivity is the ability of an SSR to
withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the
inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
Load Current vs. Ambient
Temperature Characteristics
700-SF…
Load Current [A]
Ambient Temperature [° C]
4
3
2
1
0
-30
-20
0
20
40
60
80
100
Inrush Current Resistivity1
700-SFZ… 700SFT…
Energizing Time [ms]
Inrush Current [A Peak]
50
0
10
20
30
40
10
30
50
100
200
500
1000
5000
Inrush Current Resistivity1
700-SFN…
Energizing Time [ms]
Inrush Current [A]
30
2
20
18
0
10
8
6
4
12
14
16
22
24
26
28
10
20
30
50
70
100
300
200
500
1000
2000
1 Inrush current resistivity is defined as the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive
(max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current
will damage the SSR.
EMC Directive Compliance
1. AC-switching models comply with EMC Directives under the
following conditions
2. DC-switching models comply with EMC Directives under the
following conditions
Varistor
Varistor: 470 V, 0.6 W
Film capacitor: 1
μ F, 250 VAC
OutputInput
Load
3 m max.
Connect a varistor between the output terminals.
Connect a film capacitor to the load power supply.
The input cable must be less than 3 m.
Film capacitor
OutputInput
Load
Less than 10 m
The input cable must be less than 10 m.
700-SF
700-SF
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P