Instruction manual
Bulletin 700-SK
Solid-State Relays
9-192
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P
Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Input Sensor Module
Input Sensor Ratings
Cat. No. Rated Input Voltage
Max. Operating Input
Voltage Range Input Current Pick-up Voltage Drop-out Voltage
700-SKICZ24 12…24V DC 6.6…32V DC 8 mA max. 6.6V DC max. 3.6V DC min.
700-SKICA18 100…240V AC 60…264V AC 15 mA max. 60V AC max. 20V AC min.
Output Logic Ratings
Cat. No. Logic Level Supply Voltage Logic Level Supply Current Draw
700-SKICZ24
4…32V DC 0.1…100 mA
700-SKICA18
Characteristics
Description Cat. No. 700-SKICA18 Cat. No. 700-SKICZ24
Pick-up time 20 ms max. 0.1 ms max.
Drop-out time 20 ms max. 0.1 ms max.
Response frequency 10 Hz 1 kHz
Output ON voltage drop 1.6V max.
Leakage current
5 μA max.
Output V
DRM
, V
CEO
(V)
80 (ref. value) 80 (ref. value)
Output di/dt (A/uS) — —
Output dv/dt (V/uS) — —
Output
I
2
t (A
2
S)
——
Output Tj (°C) Max. 150 150
Insulation Resistance
100 MΩ min. between input and output
Dielectric Strength 4000V AC, 50/60 Hz for 1 min between input and output
Vibration Resistance (Max.) 10…55 Hz, 1.5 mm double amplitude (10 G)
Shock Resistance (Max.) 1000 m/s
2
(100 G)
Ambient Temperature
Operating –30…+80 °C (–22…+176 °F) with no icing or condensation
Storage –30…+100 °C (–22…+212 °F) with no icing or condensation
Standards Compliance UL 508, CSA C22.2 No. 14, EN/IEC 60950
Certifications cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified
Ambient humidity Operating 45…85% (no condensation)
Weight Approx. 18 g
Output SSR Module
Control/Input Ratings
Cat. No. Rated Control Voltage
Max. Operating Control
Voltage Range
Max. Reverse
Control Voltage Impedance1
Pick-up
Voltage
Drop-out
Voltage
700-SKOZ2Z25
5…24V DC 4…32V DC -32V DC
15 mA max.
at 25 °C
(77 °F)
4V DC
max.
1V DC min.
700-SKON2Z25
700-SKOC2Z25
8 mA max.
700-SKOC1Z25
Load/Output Ratings
Cat. No. Rated Load
Voltage
Maximum
Load Voltage Range
Continuous Load Current
(Resistive) [A]
Max. Inrush Current
Min. Max.‡
700-SKOZ2Z25
100…240V AC 75…264V AC 0.05 2
30 A (@50/60 Hz, 1
cycle)
700-SKON2Z25
700-SKOC2Z25 5…48V DC 4…60V DC 0.1 2 8 A (10 ms)
700-SKOC1Z25 48…200V DC 40…200V DC 0.1 1.5 8 A (10 ms)
1 With a constant current input system. SSR impedance varies with a change in input voltage.
If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to the “Inrush Current Resistivity” graphs on page 9-193 for mor
e
details.
‡ Refer to "Load Current vs. Ambient Temperature Characteristics" graphs on page 9-193 for additional details.