Instruction manual
Bulletin 900-TC
Digital Temperature Controller
9-203
Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Bulletins 900-TC8, 900-TC16, and 900-TC32, Continued
Technical/Control Ratings
Influence of Ambient
Temperature and Line Voltage
R, S, B, W
, PL11Thermocouple Inputs: ±1% of PV or ±10°C, whichever is great, ±1 digit max.
Other Thermocouple Inputs: ±1% of PV or ±4°C, whichever is greater ±1 digit max. Note: For a Type-K thermocouple for -
100°C or less ±10°C
RTD Sensors: ±1% of PV or ±2°C, whichever is greater. ±1 digit max.
Analog Inputs: ±1% of full scale ±1 digit max.
Hysteresis (Controller with
Temperature Inputs)
0.1…999.9 EU (in units of 0.1 EU)
®
Hysteresis (Controller with Analog
Inputs)
0.01 to 99.99% FS (in units of 0.01% Full Scale)
Proportional Band (P) Controller
with Temperature Inputs
0.1…999.9 EU (in units of 0.1 EU)
®
Proportional Band Controller with
Analog Inputs
0.1 to 999.9% FS ( in units of 0.1% FS)
Integral Time (I) 0…3999 s (in units of 1 s)
Derivative Time (D)
0…3999 s (in units of 1 s)
Control Period 0.5, 1…99 s (in units of 1 s)
Manual Reset V
alue 0.0…100.0% (in units of 0.1%)
Alarm Setting Range –1999…+9999 (decimal point position depends on input type)
Sampling Period 250 ms
Other Functions According to Controller model
® Engineering Unit (EU) is used as the unit after scaling. For a temperature sensor, the EU is °C or °F.
When Robust Tuning (RT) is on, the differential is is 0.0... 999.9 in units of 0.1 sec.
Conditions: Ambient temperature: -10°C to 23°C to 55°C. Voltage Range: -15% to +10% of rated voltage.
General/Environmental Ratings
Weight (includes carton)
900-TC8 Approx. 360 g (12.7 oz.) with mounting bracket
900-TC16 Approx. 160 g (5.6 oz.) with mounting bracket
900-TC32 Approx. 100 g (3.5 ounces)
900-TC8232, COM, EIM Approx. 20 g (0.7 ounces)
900-TC16COM, EIM Approx. 35 g (1.2 ounces)
Ambient Temperature –10…+55 °C (with no condensation or icing)
Ambient Humidity 25…85%
Storage Temperature –25…+65 °C (with no condensation or icing)
Insulation Resistance
20 MΩ min. (at 500V DC)
Dielectric Strength 2300V AC, 50 or 60 Hz for 1 min. (between terminals with different charge)
Maximum Operating Vibration 10…55 Hz, 20 m/s
2
(2 G) for 10 minutes each in X, Y, and Z directions
Maximum Shock Operating 100 m/s
2
(10 G), 3 times each in X, Y, and Z directions.
Protective Structure
Front panel:IP66 (IEC61010-1)
Rear case: IP20, Terminals: IP00
Installation Environment Installation category II, pollution class 2 (IEC 61010-1 compliant)
Memory Protection EEPROM (non-volatile memory) (number of writes: 100 000)
EMC
EMI EN 61326
Radiated Interference Electromagnetic
Field Strength
EN 55011 Group 1, class A
Noise Terminal Voltage EN 55011 Group 1, class A
EMS EN 61326
ESD Immunity EN 61000-4-2
Electromagnetic Field Immunity EN 61000-4-3
Burst Noise Immunity EN 61000-4-4
Conducted Disturbance Immunity EN 61000-4-6
Surge Immunity EN 61000-4-5
Power Frequency Magnetic Field
Immunity
EN 61000-4-8
Voltage Dip/Interrupting Immunity EN 61000-4-11
Conformed Standards
Conforms to EN61010-1 (IEC 61010-1) and VDE 0106/part 100 (finger
protection) when the terminal cover is installed, Pollution Level 2, Overcurrent
Category II
1 RS-232C communications is only supported for Bulletin 900-TC8 (Cat. No. 900-TC8232 option board installed). All controllers support RS-485 communications
(32 linked/networked devices) by appropriate option unit or correct controller catalog number.
The baud rate, data bit length, stop bit length, or vertical parity can be individually set using the communications configuration function gr
oup.