Instruction manual

Bulletin 900-TC
Digital Temperature Controller
9-209
Wiring Terminals
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Wiring Terminals — General Guidelines
Bulletin 900-TC16 Option Unit Terminals, refer to Option Unit Wiring
Bulletin 900-TC32 — Wiring Terminals
Note: Input power supply available: 100…240 V AC, or 24 V AC/DC
Bulletin 900-TC32
The voltage output (SSR control output) is not electrically isolated from the controller’s internal circuits. When using a grounded
thermocouple, do not connect the control output terminals to earth ground. If the control output terminals are connected to earth ground,
errors will occur in the measured temperature values as a result of ground loop leakage current.
Standard insulation ratings exist between any of the following: power supply terminals, input terminals, output terminals, and
communication terminals. If reinforced insulation is required, provide additional insulation, such as spacial distance or material insulation,
as defined by IEC 60664.
Separate input leads and power lines to protect the Bulletin 900-TC8/900-TC16 and its lines from external noise.
Option Units
Bulletin 900-TC8 — Option Unit Wiring
Cat. No. 900-TC8232
RS-232C Communications Unit (Series B) §
Personal
Computer
RS-232C *
Cat. No. 900-TC8EIM
Event Input Unit
11
12
13
EV
EV2
CT1/CT2
Cat. No. 900-TC8COM
RS-485 Communications Unit (Series B) ‡§
1 With 900Builder Lite Software
900-CP1x or equivalent cable provides the physical connection between the PC and controller.
Typically, an RS-232 to RS-485 converter such as the Cat. No. 900-CONVZ25 (see page 9-213) will be required between the personal computer (with
900Builder Lite softwar
e) and the Bulletin 900-TCx controller. In that case, a 900-CPx or equivalent cable provides the physical connection between the
converter and the PC. RS-485 allows linking up to 31 controllers with a single personal computer.
§ Series B provides baud rates up to 57.6 K bps.
Bulletin 900-TC16 — Option Unit Wiring
CT1
900-TC16PIV2
Control output 2/
CT
+
12
11
15
14
13
900-TC16NCOMV2
Communications/
Control output 2 §
+
B
A
RS-485
12
11
15
14
13
900-TC16NCOMP3
Communications/
Two CTs §
CT2
CT1
13
14
15
11
12
B
A
RS-485
900-TC16NACCOM
Communications §
Do not
use.
Do not
use.
Do not
use.
Do not
use.
Do not
use.
B
A
RS-485
12
11
15
14
13
900-TC16NACEIM
Event inputs
EV1
EV2
12
11
15
14
13
900-TC16NEIM
Event inputs/
CT
CT1
13
14
15
11
12
EV2
EV1
Attach the appropriate terminal labels.
900-TC16NCOM
Communications/
CT §
CT1
13
14
15
11
12
B
A
RS-485
Do not
use.
Do not
use.
Do not
use.
Control
output 2
Control
output 2
12 VDC,
21 mA
Voltage
output
12 VDC,
21 mA
Voltage
output
+
+
+
+
§ Series B provides baud rates up to 57.6 K bps.
1
7
12
12
11
11
10
10
9
8
2
4
3 5
6
Input
Input
Power
Power
Supply
Supply
Control
Control
Output 1
Output 1
Auxillary
Auxillary
Output 1
Output 1
DO NOT
DO NOT
USE
A
B
B
Universal
TC/Pt Input
DO NOT
DO NOT
USE
B(+)
A(-)
RS-495
Communications
+
-
Relay Output 250 VAC, 2 A
(resistive load)
Voltage Output
12 VDC, 21 mA
(for driving SSR)
Relay Output 250 VAC, 2 A
(resistive load)
Control Output 1
Auxillary Output 1
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P