Instruction manual

Bulletin 700-HL
Interposing/Isolation Relays
9-48
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P
Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Cat. No. 700-HLS… (Solid State Output)
Electrical
Rated Thermal Current (
I
th
)
2 A (DC output) 1 A (AC output)
Rated Insulation Voltage (U
i
)
250V IEC, 300V UL/CSA
Control Circuit
Min. Control Voltage 80% nominal voltage
Maximum Control Voltage 110% nominal voltage
Control Current 9 mA ±10% (24V) 4 mA ±10% (120/240V)
Release Voltage 0.4 x nominal voltage (24V), 0.35 x nominal voltage (120/240V)
Min. Control Circuit Resistance
3200 ohms (24V), 16k ohms (120V), 32k ohms
(240V)
2500 ohms (24V), 12k ohms
(120V), 24k ohms (240V)
Outputs
Load Voltage Range 0…24V DC 24…240V AC
Max. Repetitive Blocking Voltage 33V 600V
Max. Switching Current
(inductive/resistive)
2 A DC 1 A AC
On State Voltage Drop @ Max.
Switching Current
<120 mV DC <1V AC
Leakage Current
max. 100 μA (@U = 24V)
Power Consumption
±10%
AC 0.6 VA (120V), 1 VA (240V)
DC 0.2 W 0.3 W
Design Specification/Test Requirements
Dielectric Withstand Voltage
Pole to Pole (VRMS) 2500V
Contact to Coil (VRMS) 2500V
Input Voltage 24V DC 48V DC 120V AC/DC 240V AC/DC 120V LCSC 240V LCSC
Impedance (Ohms) 2K 9 K 26 K 58 K 16 K 35 K
Mechanical
Degree of Protection IP20
Input Voltages See Overview/Product Selection
Operating Time at Nominal
Voltage at 20 °C (ms)
Turn on Time
30 μs (DC only input voltage), 7 ms (AC/DC input voltage)
Drop Out Time
350 μs (DC only input voltage), 10 ms (AC/DC input voltage)
Maximum Operating Rate 300 Hz
Environmental
Temperature Operating –20…+55 °C
Storage –40…70 °C
Altitude 2000 m (6560 ft)
Construction
Insulating Material Molded High-Dielectric Material
Enclosure Relay IP67
Terminal Markings on Socket In accordance with EN50 0005
Certifications cULus Listed (File No. E14843, Guide NLDX/NLDX7), CE Marked, ABS (American Bureau of Shipping)
Standards UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -5-1
Hazardous Location Approvals
Class 1, Zn 2, Groups IIC, Ex nC IIC T5 Ta < 55 °C
UL Listed
(UL 60079-15)
700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply)
700-HLT1U1-EX, 700-HLS1U1-EX (110V/125V AC/DC supply)
CSA Certified
1
(CAN/CSA 60079-15)
700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply)
1 Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by
transient disturbances of more than 40%.