Instruction manual

Bulletin 700-FE
DIN Rail Mounted Timing Relays
9-64
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P
Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Specifications1
Time Characteristics (according to VDE 0435, part 2021)
1 N.O. SPDT
Setting Accuracy ±5% of full scale
Repeatability ±1% of setting (typical)
Tolerance
By voltage: ±0.01%/%ΔU
By temperature: ±0.25%/°C
By voltage: ±0.001%/%ΔU
By temperature: ±0.025%/°C
Supply
Supply Voltage
24V AC/DC and 110…240V AC, 50/60 Hz
24…48V DC and 24…240V AC, 50/60 Hz
V
oltage Tolerance
AC –15%/+10%
DC –15%/+20%
Power Consumption 0.5 W at 24V DC, 5 VA at 240V AC
Time Energized 100%
Reset Time 100 ms
Cable Length (Supply Voltage Control) Max. 250 m (750 feet)
Pulse Control (B1)
Impulse Duration
250 ms 50 ms (AC), 30 ms (DC)
Input Voltage supply voltage range
Input Current 1 mA
Cable Length
Max. 250 m without parallel load between B1 and A2
Max. 50 m with load (< 3 kΩ) between B1 and A2
Outputs
Contact Type 1 N.O. contact 1 Form C – SPDT contact
Dielectric Withstand
Voltage
Contact-to-coil 4000 V
Switching Capacity
Power 1250 VA
According to IEC 947-5-1
AC-1 5 A /250V AC (resistive load)
AC-14 1 A/250V AC (inductive load)
DC-13 1 A/24V DC (inductive load)
According to UL 508 NEMA D300 - 1 A/300V AC
Short-Circuit Resistance 6 A gL (Fast Blow Fuse)
Life
Mechanical 20 million operations
Electrical
0.4 million at 1 A/250V AC, resistive
0.4 million at 0.5 A/250V AC, cos φ = 0.4
0.4 million at 1 A/24V DC, resistive
State Indicator 1 Bi-Color LED (Supply; Relay)
Certifications cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked
Standards EN/IEC 60947-1, EN/IEC 60947-5-1, UL 508, CSA 22.2 No. 14
1 Performance Data - See this catalog, Important- 3
Voltage is either 24V DC or AC 50/60 Hz.