Function and Connection Diagrams
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Special Function Flasher (Repeat Cycle Starting with Pulse or Pause) Timing Relays
Description
1 Range Setting
700-FSH3U
t
2
Setting
Seperate Range
Settings
t
1
Setting
Up
Down
Switch
700-FSH3V
Supply Voltages (A1/A2)
Z12 12V DC
U23 24…48V DC, 24…240V AC, 50/60 Hz
Function Diagram / Connection Diagram
Supply Voltage Controlled, Oscillating Mode Starting with Pause
— Switch
is Up
U
S
Output
LED
A1/A2
A1/B1
18
16
15
t1 t1
t2 t2
A1
A2
B1
15
18
16
Supply Voltage Controlled, Oscillating Mode Starting with Pulse
— Switch
is Down
U
S
Output
LED
A1/A2
A1/B1
18
16
15
t1
t1
t2
t2
A1
A2
B1
15
18
16
Pulse Controlled, Output Starts With Pause (Min. Pulse AC 50
ms — DC 30 ms) — Switch
is Up One Cycle Mode — Voltage
Supplied at A1 and A2, then Pulsing “s” to Energize B1 will
Initiate One Cycle.
U
S
Output
LED
A1/A2
A1/B1
18
16
15
t1
t1
t2
t2
A1
S
A2
15
18
16
B1
Pulse Controlled, Output Starts with Pulse (Min. Pulse AC 50 ms
— DC 30 ms) — Switch
is Down One Cycle Mode — Voltage
Supplied at A1 and A2, then Pulsing “s” to Energize B1 will
Initiate One Cycle.
U
S
Output
LED
A1/A2
A1/B1
t1
t2
t2
t1
18
16
15
s
A1
A2
B1
15
18
16
Note: If B1 is pulsed, a one full time cycle consisting of t
1
and t
2
is completed.
LED Operation Chart Ñ Green LED
LED
LED
LED
LED
Output at Shelf State, No Timing - LED OFF
Output at Shelf State, Time is Running - LED Flashing
Output NO Contact is Closed, No Timing - LED On
Output NO Contact is Closed, Time is Running - LED Long Flashing
(H) Flasher (Repeat Cycle Starting with Pulse or Pause)
The repeat cycle timer permits different settings for on and off times. The following operating modes are possible:
Oscillating mode; repeat cycle starts with voltage applied at A1 and B1, and continues to repeat until voltage is off.
One cycle mode; started by energizing B1 with voltage on A1 and A2.
Output starts with pulse or pause (switch Up or Down).
700-FSH3U provides (1) range setting for t
1
and t
2
.
700-FSH3V provides (2) range settings for t
1
and t
2
.