Instruction manual
Bulletin 700-HNC
Plug-in Timing Relays
9-74
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P
Accessories/ Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
Description Pkg. Quantity Cat. No.
Screw Terminal Socket – Panel or DIN Rail Mounting. Guarded Terminal
Construction 14-blade miniature socket for use with Bulletin 700-HNC timers.
This socket has coil and contact separation.
10
700-HN104
Cat. No. 700-HN104
Retainer Clip for Cat. Nos. 700-HN103, -HN104 and -HN128 Sockets with Bulletin
700-HNC Timers. Secures Timer in Socket.
10
700-HN263
Cat. No. 700-HN263
Specifications
Ratings
Item 700-HNC
Pilot Duty Rating NEMA B300
Pin type Plug-in
Operating voltage range
85%…110% of rated supply voltage (12V DC: 90%…110% of rated supply voltage)
Reset voltage 10% min. of rated supply voltage‡
Power consumption
24V AC:
Relay ON:
Relay OFF:
1.5 V
A (1.1 W) (at 24V AC, 60 Hz)
0.2 VA (0.1 W) (at 24V AC, 60 Hz)
100…120V AC:
Relay ON:
Relay OFF:
1.5 VA (1.3 W) (at 120V AC, 60 Hz)
0.8 VA (0.5 W) (at 120V AC, 60 Hz)
200…230V AC:
Relay ON:
Relay OFF:
1.8 VA (1.5 W) (at 230V AC, 60 Hz)
1.2 VA (0.9 W) (at 230V AC, 60 Hz)
12V DC:
Relay ON:
Relay OFF:
0.9 W (at 12V DC)
0.07 W (at 12V DC)
24V DC:
Relay ON:
Relay OFF:
0.9 W (at 24V DC)
0.07 W (at 24V DC)
48V DC:
Relay ON:
Relay OFF:
1.0 W (at 48V DC)
0.2 W (at 48V DC)
100…110V DC:
Relay ON:
Relay OFF:
1.3 W (at 110V DC)
0.3 W (at 110V DC)
125V DC:
Relay ON:
Relay OFF:
1.3 W (at 125V DC)
0.3 W (at 125V DC)
Control outputs
4PDT: 5 A at 250V AC, resistive load (cosφ = 1)
Characteristics
120V AC 30 A
Make 240V AC 15 A
120V AC 3 A
Break 240V AC 1.5 A
Hp at 120V AC 1/6 Hp
Hp at 240V AC 1/6 Hp
Accuracy of operating time ±1% FS max. (1 s range: ±1%±10 ms max.)
Setting error ±10%±50 ms FS max.
Reset time Min. power-opening time: 0.1 s max. (including halfway reset)
Influence of voltage ±2% FS max.
Influence of temperature ±2% FS max.
Insulation resistance
100 mΩ min. (at 500V DC)
Dielectric strength
2000V AC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying
metal parts)
1
2000V AC, 50/60 Hz for 1 min (between operating power circuit and control output)
2000V AC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model)
1500V AC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model)
1000V AC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration resistance Malfunction:10…55 Hz, 0.5 mm single amplitude
Shock resistance Malfunction:100 m/s
2
(approx. 10G)
Ambient temperature
Operating:-10 °C…50 °C (with no icing)
Storage:-25 °C…65 °C (with no icing)
Ambient humidity Operating:35%…85%
Life expectancy
Mechanical:10 000 000 operations min. (under no load at 1800 operations/hr)
Electrical:4PDT:
200 000 operations min. (3 A at 250V AC, resistive load at 1800 operations/hr)
1 Single-phase, full-wave-rectified power supplies can be used.
When using the 700-HNC continuously in any place where the ambient temperature is in a range of 45 °C…50 °C, supply 90%…110% of the rated supply
voltages supply 95%…110% with 12V DC type).