Instruction manual
Bulletin 700-HR
Plug-in Timing Relays
9-89
Specifications
0
1
2
3
4
5
6
7
8
9
10
11
12
13
700-HR, -
HRS, -HRV
700-HRP 700-HRC 700-HRM 700-HRF 700-HRY 700-HRQ
700-HRT
(Transistor
Outputs)
Electrical Ratings
Pilot Duty Rating NEMA B300 —
Thermal Current (
I
th
)
5 A
100 mA @ 30V
DC max.
120V AC 30 A —
Make 240V AC 15 A —
120V AC 3 A —
Break 240V AC 1.5 A —
Hp at 120V
1/6 Hp (0.12
kW)
1/4 Hp (0.18 kW) 1/6 Hp (0.12 kW)
1/4 Hp (0.18
kW)
1/6 Hp (0.12
kW)
—
Hp at 240V 1/3 Hp (0.25 kW) —
Resistive Load 5 A at 250V AC/30V DC
Inductive Load AC-15 @ 250V AC, 3 A/DC-13 @ 30V DC, 0.5 A
Accuracy of Operating Time ±0.2 % FS max. (±0.2 % ±10 ms max. in a range of 1.2 s)
Setting Error ±5 % FS ±50 ms (The value is ±5 % FS +100 ms to -0 ms max. when the C or D mode signal of the 700-HRVs are OFF.)
Influence of Voltage ±0.2 % FS max. (±0.2 % ±10 ms max. in a range of 1.2 s)
Influence of Temperature ±1 % FS max. (±1 % ±10 ms max. in a range of 1.2 s)
Permissible Leakage Current
Power Consumption -HR52, -HRS -HRV -HRP, -HRC -HRM -HRF -HRY -HRQ -HRT
240V AC, Output ON 2.1 VA 2.5 VA 2.0 VA 2.1 VA 10 VA 12 VA 0.4 VA —
240V AC, Output OFF 1.3 VA 1.8 VA 2.0 VA 1.3 VA 10 VA 12 VA 0.4 VA —
24V DC, Output ON 0.8 W 0.9 W 0.9 W 0.8 W 1.0 W — 0.2 W 0.3 W
24V DC, Output OFF 0.2 W 0.3 W 0.9 W 0.2 W 1.0 W — 0.2 W 0.2 W
Design Specifications
Dielectric Strength
2000V AC (1000V AC for 700-HRT), 50/60 Hz for 1 min (contact to frame)
2000V AC (1000V AC for 700-HRT), 50/60 Hz for 1 min (between control output terminals and operating circuit)
2000V AC, 50/60 Hz for 1 min (pole-to-pole)
1000V AC, 50/60 Hz for 1 min (between contacts not located next to each other)
2000V AC, 50/60 Hz for 1 min (contact to coil)
Mechanical
Vibration Resistance Malfunction: 10…55 Hz with 0.5 mm double amplitude each in three directions for ten minutes each
Shock Resistance Malfunction: 100 m/s
2
(10 G)
98 m/s
2
(10 G)
294 m/s
2
(10 G)
98 m/s
2
(10 G)
100 m/s
2
(10 G)
Environmental
Noise Immunity ±1.5 kV for ±600V DC ±400V for 12V DC
±1kV for
48V DC
±1.5 kV for
±600V DC
Static Immunity Malfunction: 8 kV
Ambient Temperature
Operating: -10…55 °C (with no icing)
Storage: -25…65 °C (with no icing)
Ambient Humidity Operating: 35…85 %
Construction
Life Rxpectancy
(Min. Operations)
Mechanical:20 000 000. (under no load at 1800 operations/h)
Electrical: 100 000 (5 A at 250V AC, resistive load at 1800 operations/h)
Mech: 10
7
Electrical: 10
4
EMC
(EMI) EN50081-2
Emission Enclosure:EN55011 Group 1 class A
Emission AC Mains: EN55011 Group 1 class A
(EMS) EN50082-2
Immunity ESD:EN61000-4-2:4 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference from AM Radio Waves: ENV50140:10 V/m (80 MHz…1 GHz) (level 3)
Immunity RF-interference from Pulse-modulated Radio Waves:ENV50204:10 V/m (900 ±5 MHz) (level 3)
Immunity Conducted Disturbance:ENV50141:10 V (0.15…80 MHz) (level 3)
Immunity Burst:EN61000-4-4:2 kV power-line (level 3)
Immunity Surge:EN61000-4-52 kV I/O signal-line (level 4)
1 kV line to line
2 kV line to ground (level 3)
Degree of Protection IP40 (panel surface)
Weight Approx. 90 g
Certifications CSA Certified (File No. 70751), UL Recognized (File No. E14843 Guide No. NRNT2), CE Marked, C-Tick Marked
Standards UL 508, CSA C22.2 No. 14, EN 61812-1, EN 61000-6-2, -6-4
www.ab.com/catalogs Preferred availability cat. nos. are b
bold
.
Publication A117-CA001A-EN-P