Specifications
ST900 Family General Handbook
667/HB/32900/000 Issue 10 Page 69 of 265
Note
NO MORE than 3 cores should be connected in parallel. The numbers in the cells within the tables indicate the number
of cores required to meet the voltage drop requirement.
Length of Cable Run (metres) – 1.0 mm
2
Cable
5m
10m
15m
20m
25m
30m
35m
40m
45m
50m
60m
70m
80m
90m
100m
110m
120m
130m
140m
160m
180m
200m
225m
250m
275m
300m
325m
350m
375m
400m
Lamp Load (Watts)
7 W
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2
10 W
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2
12 W
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 3 3 3
18 W
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 3 3 3 3
20 W
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 3 3 3 3
25 W
1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 3 3 3
30 W
1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 3 3 3 3
35 W
1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 3
40 W
1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 3 3 3 3
45 W
1 1 1 1 1 1 1 1 1 2 2 2 2 2 3 3 3 3
50 W
1 1 1 1 1 1 1 1 2 2 2 2 2 3 3 3 3
60 W
1 1 1 1 1 1 2 2 2 2 2 3 3 3 3
80 W
1 1 1 1 1 2 2 2 2 2 3 3
100 W
1 1 1 1 2 2 2 2 3 3 3
120 W
1 1 1 2 2 2 3 3 3 3
Table 16 – ST900 ELV Cable Lengths: 1.0mm
2