Specifications

3U Traffic Outstation Handbook
667/HB/26568/000 Page 210 Issue 15
11.15 FLOW FACILITY COMMAND TABLE
CODE
MAJOR
INDEX
MINOR
INDEX
DATA
RANGE DESCRIPTION AND REMARKS
ACCESS
LEVEL
FOC
- 0 – 15 0 –
65535
Flow Count – The flow count value
prior to applying the smoothing
algorithm
RO
FOD
- 0 – 15 0 –
65535
Flow Down Threshold – The down
threshold of the flow detector,
shown as a count value
RO
FOF
- 0 – 15 0 – 100
Flow Smoothing Factor – The
percentage of the flow count
average that is used to calculate
the new flow average
RO
FOH
- 0 – 1 8 bits
binary
Flow High – Shows 16 flow
detectors, 1 = High Threshold last
achieved, 0 = Low Threshold last
achieved (Hysteresis). Inverse of
Flow Low. Index 0 shows bits 0 –
7, index 1 shows bits 8 – 15
RO
FOL
- 0 - 1 8 bits
binary
Flow Low – Shows 16 flow
detectors, 1 = Low Threshold last
achieved, 0 = High Threshold last
achieved (Hysteresis). Inverse of
Flow High. Index 0 shows bits 0 –
7, index 1 shows bits 8 – 15
RO
FOP
- 0 – 15 0 – 100
Flow Count Period – Time in
minutes, over which to calculate
flow
RO
FOS
- 0 – 15 0 –
65535
Smoothed Flow Result – The
smoothed detector flow value
RO
FOU
- 0 – 15 0 –
65535
Flow Up Threshold – The up
threshold of the flow detector,
shown as a count value
RO