Specifications
3000sb2.fm
P31003-H3560-X100-1-7618, 09/05
HiPath 3000/5000 V6.0, System Description
2-101
For internal use only
HiPath 3000 System Overview
HiPath 3300
● Bridging times
The following table lists the maximum bridging times (battery operation in case of power
failure) available with four batteries V39113-W5123-E891 (4 x 12 V/7 Ah batteries).
2.10.3.3 LIM
The LAN Interface Module (LIM - S30807-Q6930-X) is an optional plug-in card for all HiPath
3000 central control boards (see also Section 4.4).
The board provides an Ethernet (10BaseT/10 Mbps) LAN connection via an 8-pin RJ45 jack.
The LIM module can be used for administration via HiPath 3000 Manager E and for CTI func-
tions (TAPI 120 V2.0). However, bear in mind that the number of BHCAs (Busy Hour Call At-
tempts = number of connection attempts during busy traffic hours) is restricted to 400 at a max-
imum of six TAPI ports. The use of "power dialers" is not approved.
You cannot operate the LIM module and a HG 1500 board simultaneously in one system.
Table 2-45 UPSC-DR - Bridging Times with four Batteries V39113-W5123-E891 (4 x
12 V/7 Ah Batteries)
System Power supply
unit
Load levels Maximum bridg-
ing time
HiPath 3300 UPSC-DR Normal output load = 5 V/3 A;
–48 V/0.5 A; ringing approx. 2 VA
7h 30min
Measurement conditions:
● All measurements were performed at a room temperature of approximately 23 °C
(73.4 °F).
● The batteries were fully charged when the measurement was started.