Bridging times
The following table lists the maximum bridging times (battery operation in case of power
failure) available with the battery pack S30122-K5950-Y200 (48 V/7 Ah) and battery hous-
ing BSG 48/38 (S30122-K5950-F300).
BSG 48/38
You can use a BSG 48/38 battery cabinet in an upright housing instead of the battery pack to
extend the bridging time in the event of a power failure. The BSG 48/38 battery cabinet
(S30122-K5950-F300) consists of
an upright housing
a charging rectifier
a battery set (38 Ah/48 V)
The battery cabinet is designed for direct connection to the HiPath 3800 communication sys-
tem.
Table 2-4 LUNA2 - Bridging Times with Battery Pack 48 V/7 Ah and Upright Battery
Housing BSG 48/38
System Power supply unit Load levels Maximum bridg-
ing time
HiPath 3800 2 x LUNA2 per system cabinet as
PSU
1 x LUNA2 per system cabinet as
battery charger
1 x battery pack 48 V/7 Ah per sys-
tem cabinet
60% nominal
load
25 min
HiPath 3800 5 x LUNA2 boards per system
1 x BSG upright battery housing 48/
38 per system
(LUNA2 is not required as a battery
charger as the BSG 48/38 battery
cabinet features a built-in charger.)
60% nominal
load
1h 30min
Measurement conditions:
All measurements were performed at a room temperature of approximately 22 °C
(71.6 °F).
The batteries were new and fully charged when measurement started.