P/N 315-049475-7
Figure 1
HTRI Module
INTRODUCTION The HTRI Series Addressable Modules from
Siemens Industry, Inc., shown in Figure 1, interface
direct shorting devices to the DLC loop circuit of
the FireFinder-XLS or FS-250 System.
The HTRI modules are available in three models.
The HTRI-S and HTRI-R can monitor a normally
open or closed dry contact. The HTRI-S can only
monitor and report the status of the contact, while
the HTRI-R incorporates an addressable Form C
relay. The HTRI-D is a dual input module that
supervises and monitors two sets of dry contacts.
PROGRAMMING INSTRUCTIONS
Refer to Figure 2 to locate the opening on the HTRI cover that allows access to the
programming holes which are on the HTRI printed circuit board.
To connect the HTRI to the DPU
Programmer/Tester, insert the
plug from the DPU cable
provided with the Programmer/
Tester into the opening on the
front of the HTRI. Be sure to
insert the locating tab on the
plug into the slot for the locating
tab on the HTRI as shown in
Figure 2.
To prevent potential damage to
the DPU 
DO NODO NO
DO NODO NO
DO NO
T T 
T T 
T connect an
HTRI to the DPU until at least one
wire is removed from terminals 1
or 2 of the HTRI.
Figure 2
Connecting The DPU Plug
Addressable Switch Interface Modules
Installation Instructions
Models HTRI-S / HTRI-D / HTRI-R
LOCATING
TAB
SLOT FOR
LOCATING TAB
PROGRAMMING
HOLES
HTRI-S/-D/-R
MODULE
PLUG FROM
DPU
PROGRAMMER/
TESTER