Figure 11
HUB-4 Wiring To XL3 System (MMX-1)
NOTES
1. The communication level from the MMX as measured from the
HUB-4 terminals should not exceed -4dBm.
2. Positive or negative ground fault detected at <25K ohms on CC-5
pins 1-16.
3. 14-18 AWG 8 miles max.
20 AWG 5 miles max.
22 AWG 3 miles max.
0.6 μF max line to line.