Instruction Manual October 2002 HYDRORANGER 200 HYDRORANGER 200
Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment. These warning notices are accompanied by a clarification of the level of caution to be observed. Qualified Personnel This device/system may only be set up and operated in conjunction with this manual. Qualified personnel are only authorized to install and operate this equipment in accordance with established safety practices and standards.
Table of Contents Specifications ...............................................................................................................................................3 Installation ......................................................................................................................................................7 Mounting ...................................................................................................................................................
Table of Contents mmmmm Using Units or Percent (%) ..................................................................................................................27 Parameters Types ..................................................................................................................................27 Parameter Reset ....................................................................................................................................28 Display Readout .........................
Setting a Rake Control .........................................................................................................................62 Setting the Common Parameters ............................................................................................63 Set Relay 1 (Operate Rake) .......................................................................................................63 Set Relays 2 to 4 (Level Alarms) ..........................................................................
Table of Contents mmmmm Simulating a Level Cycle ......................................................................................................................79 Checking Volume Characterization ..................................................................................................80 Checking OCM Flow Characterization .............................................................................................80 I/O Checkout ..............................................................
Modbus Responses ........................................................................................................................... 105 Error Handling ..................................................................................................................................... 105 Communication Troubleshooting .................................................................................................. 107 Generally ......................................................................
Table of Contents mmmmm Relays (P100 to P119) .........................................................................................................................126 P100 Preset Applications...................................................................................................... 126 P110 Level Source.................................................................................................................. 127 P111 Relay Control Function.............................................
mmmmm vii Table of Contents P270 Discrete Input Function............................................................................................... 145 P275 Scaled Discrete Input Value...................................................................................... 146 Standard Data Logging (P300 to P321) .........................................................................................146 Record Temperatures (P300 to P303) .................................................................
Table of Contents mmmmm P622 Inflow / Discharge Adjust........................................................................................... 165 Totalizer (P630 to P645) ......................................................................................................................166 P630 LCD Totalized Multiplier.............................................................................................. 166 P633 LCD Totalized Decimal Position..................................................
mmmmm ix Table of Contents P773 Parity ............................................................................................................................... 184 P774 Data Bits......................................................................................................................... 184 P775 Stop Bits ......................................................................................................................... 185 P778 Modem Available ....................................
Table of Contents mmmmm P901 Memory .......................................................................................................................... 203 P902 Watchdog....................................................................................................................... 203 P903 Display ............................................................................................................................ 203 P904 Keypad ........................................................
Pump Control Options ....................................................................................................................... 227 Pump Groups ............................................................................................................................. 227 Pump by Rate ............................................................................................................................ 227 Pump Control Algorithms ...........................................................
xii
HydroRanger 200 • • • water and wastewater storage tanks, for measring liquids, sluries, and solids open channels, wet wells, pump totalizer, bar screens The Manual The manual provides instruction for the operation of the HydroRanger 200 and is designed to help you get the most out of your instrument.
HydroRanger 200 mmmmm Manual Symbols Please note their use carefully. Alternating Current Direct Current Earth (ground) Terminal Protective Conductor Terminal Caution (refer to instructions) Infra-red communication port on front of instrument RJ-11 communications port No co-axial cable connections Configuration Examples The configuration examples used in this manual illustrate the versatility of the HydroRanger 200.
Specifications Power AC version • 100-230 Vac ± 15%, 50 / 60 Hz, 36 VA (17W)1 • fuse: F3: 2 AG, Slow Blow, 0.375A, 250V DC version Transmitter fuse • F1: Belling Lee, L754, 4000A HRC, ceramic type, 100mA, 250V Temperature Sensor fuse • F2: Belling Lee, L754, 4000A HRC, ceramic type, 50mA, 250V Mounting Location • indoor / outdoor Altitude • 2000m max.
Range • 0.3m (1 ft) to 15m (50 ft), dependent on transducer Accuracy • 0.25% of maximum range or 6mm (0.24”), whichever is greater Resolution Specifications mmmmm • 0.1% of program range1 or 2mm (0.
Fixed • 0.
Discrete (2) • • • • 10-50Vdc switching level logical 0 = < 0.5 Vdc logical 1 = 10 to 50 Vdc 3mA maximum draw Enclosure • 240mm (9.5") x 1.75mm (6.9"). Width dimension includes hinges. Specifications mmmmm • Type 4X / NEMA 4X / IP 651 • Polycarbonate Weight • 1.37 kg (3.
Installation Notes: • • Installation must only be performed by qualified personnel, and in accordance with local governing regulations. This product is susceptible to electrostatic shock. Follow proper grounding procedures. All field wiring must have insulation suitable for at least 250 V. Hazardous voltage present on transducer terminals during operation. DC terminals shall be supplied from an SELV source in accordance with IEC 1010-1 Annex H.
Mounting Instructions Mount the unit where there is sufficient room to swing lid open and have clear access. Note: When routing cable through a conduit, please follow the Cable Routing instructions on page 9 before mounting the HydroRanger 200. Enclosure Dimensions 14.9mm (0.58") 15.2mm (0.6") 160.3mm (6.325") 130mm (5.125") 4.3mm Dia. (0.17") Four Mounting Holes 91mm (3.58") 6.6mm (0.26") 240mm (9.45") 227mm (8.93") Installation mmmmm Enclosure Screws (6) Mounting the Enclosure 1. 2. 3.
Cable routed through a conduit: 1. 2. 3. 4. 5. Remove the four mounting screws holding the motherboard to the enclosure. Be careful not to damage the electronics with static electricity. Remove the motherboard from the enclosure by pulling the board straight out. Drill the required cable entry holes. Make sure conduit holes do not interfere with the lower areas on the terminal block, circuit board, or SmartLinx card.
Installing the Battery The battery (Rayovac BR2032) has a ten-year life expectancy. Please note the life expectance may be reduced by ambient temperature. If the unit loses external and battery power, a capacitor will power the RAM for about ten minutes. Notes: • Do not install the memory backup battery until the HydroRanger 200 is installed, as it begins operation immediately. • The unit is supplied with one battery.
Wiring Please note: • • • Verify that all system components are installed in accordance with instructions. Connect all cable shields to the HydroRanger 200 Shield Terminals. Avoid differential ground potentials by not connecting cable shields to ground (earth) anywhere. Keep exposed conductors on shielded cables as short as possible to reduce noise on the line caused by stray transmissions and noise pickup.
Terminal Board The terminal board on the HydroRanger 200 allows all inputs and outputs to be connected simultaneously. Note: Recommended torque on terminal clamping screws. • 0.56 - 0.79 Nm • 5 - 7 in.lbs Please do not overtighten the screws.
Transducers Warning: Hazardous voltage present on transducer terminals during operation. Run the transducer cable in a grounded metal conduit, separate from other wiring (except TS-3 temperature sensor wiring, if applicable).
Temperature Sensor Accurate temperature readings are critical to accurate level measurements because the speed of sound changes, depending on air temperature, and all Milltronics Echomax and ST-H transducers have an internal temperature sensor.
Level System Synchronization Note: The HydroRanger 200 CANNOT be synchronized with the MultiRanger Plus or the HydroRanger. When using multiple ultrasonic level monitors, be sure to run the transducer cables in separate grounded metal conduits. When separate conduits are not possible, synchronize the level monitors so that no unit transmits while another is waiting for echo reception.
Digital Communications Wiring the HydroRanger 200 for communications allows it to be integrated into a full SCADA system or an industrial LAN. The HydroRanger 200 can also be directly connected to a computer running Dolphin Plus.
Operating the HydroRanger 200 The HydroRanger has two modes of operation: RUN and PROGRAM. RUN Mode In RUN mode, the HydroRanger 200 detects material level and provides control functions. The HydroRanger 200 automatically starts in RUN mode when power is applied. System status is shown on the unit’s LCD, or on a remote communications terminal.
Icons indicating index type (Item 1) edited in PROGRAM mode: Icon Index Type measurement point or transducer relay secondary index mA input or output Readings in RUN Mode Change the displayed values with the keys on the hand programmer. All readings are shown in the Auxiliary field, except for the totalizer and P920. Key + + + ### P Operation mmmmm P 1. 2.
Status Parameters Status parameters give the operating status of the HydroRanger 200. You can access parameters with the hand programmer (see page 26) or with Dolphin Plus (see page 22). Remote SCADA system access is also possible.
Example To reference the displayed level to sea level, enter the distance in Units (P005), between Empty (P006) and sea level. (Enter a negative value if Empty is below sea level.) P006 P007 Sea Level P062 Reservoir P062 is the distance between sea level and Empty. Auxiliary Reading The Auxiliary Reading area of the LCD displays parameter values while leaving the primary reading on screen.
Setting a Specific Auxiliary Reading To display a second auxiliary reading, press Example: To set P P in RUN mode. to display current temperature, go to P731: Parameter Index Value Description P731 G 912 Shows P912–Transducer Temperature Multiple Readings During differential or average operation (P001 = 4 /5), the display scrolls sequentially through Point Numbers 1, 2, and 3. Point 3 is the difference between (or average of) Points 1 and 2.
Starting PROGRAM Mode Hand Programmer The hand programmer gives you direct access to the HydroRanger 200. Aim the hand programmer and press PROGRAM key. Note: • • The 3v battery in the hand programmer is not replacable The hand programmer is ordered separately from Siemens Milltronics. Go to www.milltronics.com for a contact near you. For your convenience, the programmer has a magnetic mounting strip on the back. Keep programmer nearby for easy access.
Programmer Keys Keys P Programming Mode Run Mode 1 8-digit Totalizer (toggle) 2 Pump Running Time 3 Head 4 Flow based on Head 5 mA Output 6 Temperature 7 Rate of Change 8 Failsafe Time Left 9 N/A 0 N/A Decimal Point (TVT left) Parameter Value Negative Value (TVT right) Material Level (P731) Fire Transducer Distance Run Mode Program Mode (Key 1) Units or % Next Display Field Units or % (Program Mode) (Key 2) Pause Display Toggle Increase Value Next Index Decrease Value Pr
Dolphin Plus Use Dolphin Plus software to configure, monitor, tune, and diagnose the HydroRanger 200 from a PC or directly in the field with a laptop. Dolphin Plus is easy to install and easy to use. Just load the software from the CD onto a desktop PC or Laptop, and then set up or modify complete parameter configurations in a Windows®environment.
Dolphin Plus Toolbar Buttons The toolbar buttons provide quick access to Dolphin Plus features.
Activating the HydroRanger 200 All the instructions in the following procedures apply to the hand programmer and assume that the HydroRanger 200 is activated. 1. Power the HydroRanger 200. 2. 3. Point the programmer at the unit and press PROGRAM Press DISPLAY . .
When P000 is set to 1954, programming is enabled. To disable programming, enter another value. P000 (1954) is a fixed value password. Therefore, you should use other means to secure the HydroRanger 200 if security is a concern. Simulation P000 Lock also controls how simulations affect control relays. By default, control relays are unaffected by simulation levels. But if P000 is set to –1, they react to the simulated level. See parameters P925–P927 on page 208 for running a simulation.
Parameter Reset Returning a parameter to factory default. 1. 2. 3. Display the appropriate parameter number. Display the appropriate index value (if required). Press CLEAR . 4. Press ENTER . Master Reset (P999) Returns all parameters to original values. Use Conditions: • before initial system installation • following a software upgrade If complete reprogramming is required, use Dolphin Plus to store and retrieve parameters. When the dual point option is enabled, P999 is indexed by transducer.
Changing Parameters (Dolphin Plus) The other method for changing parameter values is with Dolphin Plus software. It lets you access the HydroRanger 200 from a PC or on site with a laptop and change HydroRanger 200 parameters. Most examples in this manual use the icons from the hand programmer but nearly all functions are also available through Dolphin Plus. Parameter Indexing Parameters are indexed when they apply to more than one input or output.
HydroRanger 200 Display The index number and the index values are displayed above the parameter indicator on the LCD. Index Value Index Number 1 2 3 4 5 6 Notes • • • An indexed transducer is commonly referred to as a Point (short for ’Measurement Point’). Point Number refers to indexed transducers. To set all indexed values for a parameter to the same value, use index 0. Transducer parameters are indexed only if Operation (P001) is set to Difference (value=4) or Average (value=5).
Primary and Secondary Indexes Primary Index: relates to direct input or output and can refer to relays, communications ports, and other parameters. In parameters that allow secondary indexes, the primary index is often referred to as a point. Secondary Index: relates to previously indexed parameters where the parameter requires a second index, permitting multiple values on an indexed input or output.
Example P054 provides up to 32 breakpoint levels used with P055 (Volume Breakpoint) for universal volume calculation. The illustration indicates how you can set secondary indexes to specific functions. P054 1 [6 = 2m] A A P054 [1.6] = 2m [3 = 1.5m] B B P054 [1,3] = 1.5m C [1 = 0.75m] P054 [1,1] = .
Measurement Conditions The following information will help you configure your HydroRanger 200 for optimal performance and reliability. Response Rate The response rate of the device influences the measurement reliability. Use the slowest rate possible with the application requirements. The response rate is also important to functions connected to the filling or emptying indicators.
Relays mmmmm Relays Relays are the primary controls of external devices such as pumps or alarms. 3 Relay Number Ring indicates relay is configured The HydroRanger 200 comes with extensive control and alarm functions. Dot indicates relay is energized/deenergized General Introduction Six onboard multi-purpose relays are provided on the HydroRanger 200. Each relay may be independently assigned to one function with a corresponding status icon on the LCD.
Temperature The function goes on when the fail-safe timer expires. The function goes OFF when a valid echo is received (fail-safe timer is reset). Pump Level In pump down, the function goes on when the level rises to the ON setpoint and goes off when the level lowers to the OFF setpoint. In pump up, the function goes on when the level lowers to the ON setpoint and goes off when the level rises to the OFF setpoint. Miscellaneous Totalizer and Samplers Refer to Totalizing Pumped Volume on page 58.
Relay Status – Non Run Modes Relays mmmmm When the fail-safe timer expires, pump control relays respond as previously described. However, alarm relays will respond in the following manner: Fail-Safe Mode Fail-Safe High Fail-Safe Low Fail- Safe Hold Relay Status High Alarm ON OFF HOLD Low Alarm OFF ON HOLD Upon entering the program mode, all pump control relays will be turned OFF. Alarm relays will hold their prior status.
P111–Control Functions The control function energizes the relay coils. When the instrument is at rest (no controls operating) the relay coils are de- energized. Sets the process point at which the relay is tripped. P113–Relay OFF Setpoint Sets the process point at which the relay is reset. P115–Relay Interval Setpoint Sets length of time between starts. P116–Dead Band Sets distance above and below the bound alarm setpoints. P118–Relay Output Logic Affects relay reaction.
• • • Relays mmmmm Functions affected by setpoint are configured by parameters that determine the application requirements such as timing. P111 Pump and Control functions (see page 127 sets the function requirements. Other function parameters: P132–Pump Start Delay P133–Pump Power Resumption Delay P645–Relay Duration Relay Logic is Modified Normal operating conditions means that alarms are off and pumps are on. This can be reversed using P118–Relay Output Logic.
Value # Parameters Affected Reservoir 1 4 Screen 5 Alarms 6 7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 39 mmmmm Reservoir 2 Relays 3 Pump up with the following level settings: Relay # Parameter 1 2 3 4 5 6 P111 52 52 1(H) 1(L) 0 0 P112 30% 20% 90% 10% – – P113 80% 80% 85% 15% – – Pump up with the following level and rate settings: Relay # Parameter 1 2 3 4 5 6 P111 52 52 1(H) 1(L) 0 0 P112 20% 20% 90% 10% – – P113 80% 80% 85% 15% – – P121 1 Because the pumps are started by rate yo
Backup Level Override Backup level override provides the option of overriding the ultrasonic input with another contacting point level device, for example, the Pointek CLS 200. The ultrasonic reading is fixed at the programmed switch level until the discrete input is released and the ultrasonic device makes its decisions based on the override value. Backup Level Override mmmmm Backup Level Override Parameters P064: Reading Override Enable Sets the discrete input as the source of a level reading override.
Discrete Inputs Wiring the Discrete Inputs Normal state is standard operation, with the HydroRanger 200 sensing the material level and controlling the pumps. The discrete input contacts are either normally-open or normally-closed when the system state is normal. Example: Normal state for a backup high level switch is open, and the contacts on the discrete input are wired as normally-open.
mA I/O To integrate the HydroRanger 200 with other equipment, use the mA input and outputs. Note: When a mA input parameter is accessed, a mA symbol appears in the upper left corner of the LCD display. The mA input can be used as a level measurement or can be passed on to a SCADA system.
Calibrating 4 mA Output 1. 2. 3. 4. 5. 6. Connect the mA receiving device to the HydroRanger 200. Put the HydroRanger 200 into PROGRAM mode. Set P911–mA Output Value to 4.0. View the mA level on the receiving device. If there is a discrepancy, use P214–4 mA Output Trim to correct the value. Press MODE and then the ARROWs to increase or decrease the trim. Repeat until the mA level on the receiving device equals 4.0 mA. The unit is now calibrated for 4 mA for the receiving device.
Volume Volume is used in two situations: 1. Calculate and display volume instead of level. For programming all setpoint parameters in terms of volume units rather than level units. Calculate pumped volume to accomplish the following: • Totalize the volume of material that is pumped out of the wet well 2. If you require this functionality, please contact your local Siemens Milltronics representative at www.milltronics.com.
Characterization Chart If you cannot use a pre-defined tank, then use one of the universal tank shapes and program the characterization curve. 1. 2. 3. Plot a volume to height chart. Usually a tank supplier will provide this chart. However, if you have a custom-built wet well then you will need access to complete drawings of the well or accurate measurements. Enter the curve values from this chart into P054 and P055. Ensure extra points are added around sharp transitions in the wet well volume (e.
Parameter Transducer Index Value Description P054 1 0.0 0.8 2.0 3.5 4.1 4.7 5.1 5.2 5.3 5.4 5.5 5.6 6.0 7.2 9.0 0.0 2.1 4.0 5.6 5.9 6.3 6.7 7.1 7.8 8.2 8.8 9.2 10.9 13.0 15.0 Determines the Level breakpoints at which the volumes are known. Determines the volumes which correspond to the level breakpoints. The universal calculations interpret between the breakpoints to produce an accurate model of the volume at all level readings.
Alarms The level alarm is the most common. Use this alarm to warn you when your process is in danger of being upset due to high or low levels. Generally, the four alarms used are Hi, Hi Hi, Lo, and Lo Lo. Set the Common Parameters P006 hi hi hi P007 lo lo lo Prerequisite: You must know the details of your application and substitute the values for the sample values provided. If you are bench testing the unit, then set your test values to be the same as the sample values.
Setting Simple Level Alarms Alarms mmmmm To set Relay Five to a standard level alarm (Hi Hi, Hi, Lo, Lo Lo) do the following: Parameter Index Value Description P111 5 1 • Set P111, indexed to relay, to the value 1 for level alarm • Press UNIT symbol. • Press ARROW keys to display the Auxiliary Function as required to scroll to the alarm designation ( , , , or ). P112 P113 • 1.2m • 1.15m • 5 5 Press ENTER to enter the value.
In Bounds / Out of Bounds Range Parameter Index Value P111 P112 P113 P116 5 5 5 5 3 1.3 0.3 0.05 Results: • • Trips alarm above 1.35m and below 0.25m Resets alarm below 1.25m and above 0.35m Setting an In Bounds Alarm Parameter Index Value P111 P112 P113 P116 5 5 5 5 2 1.3 0.3 0.05 Results: • • Trips alarm below 1.25m and above 0.35m Resets alarm above 1.35m and below 0.25m Cable Fault Activates an alarm if transducer cable circuit enters a shorted or opened state.
With P112 and P113, you can set a high alarm (P112 > P113) or a low alarm (P112 < P113). Alarms mmmmm This table shows a high alarm Parameter Index Value P111 P112 P113 P110 5 5 5 5 5 45 43 1 Description Alarm on temperature ON setpoint at 45 °C OFF setpoint at 43 °C Take the temperature reading from Transducer One The temperature source can be the temperature sensor built into the transducer or an external TS-3, as set by P660.
Pump Control Setting a Pump Down Group Example: Sewage Wet Well Setting a group of three pumps to pump down a wet well. P006 Outflow Inflow P007 Set the Common Parameters Prerequisite: Substitute the details of your application in place of the sample values provided. If you are bench testing the unit, set your test values to be the same as the sample values. Parameter Index P001 P002 P003 P004 P005 P006 P007 G G G G G G G 7ML19981FC01 Value Description 1 1 2 102 1 1.8 1.
Set Relays to ALTERNATE DUTY ASSIST Parameter Index P111 P111 P111 1 2 3 Value Description 52 52 52 Sets the pump relays (index 1, 2, and 3) to ALTERNATE DUTY ASSIST. Pump Control mmmmm Set the ON Setpoints Parameter Index P112 P112 P112 1 2 3 Value Description 1.0m 1.1m 1.2m Sets the three setpoints for the pump relays. The first cycle will use these setpoints. Subsequent cycles rotate the setpoints among the pumps. Set the OFF Setpoints Parameter Index Value P113 0 0.
Set the Common Parameters Prerequisite: Substitute the details of your application in place of the sample values provided. If you are bench testing the unit, set your test values to be the same as the sample values. Index P001 P002 P003 P004 P005 P006 P007 G G G G G G G Value Description 1 1 2 102 1 1.8 1.4 Operation = level Material = liquid Maximum Process Speed = medium Transducer = XPS-10 Units = meters Empty = 1.8m Span = 1.
Other Pump Control Algorithms Set Relays to ALTERNATE DUTY BACKUP Parameter Index P111 P111 P111 1 2 3 Value Description 53 53 53 Sets the pump relays (index 1, 2, and 3) to ALTERNATE DUTY BACKUP. Pump Control mmmmm Set the Relay ON Setpoints Parameter Index P112 P112 P112 1 2 3 Value Description 0.4m 0.3m 0.2m Sets the three setpoints for the pump relays. The first cycle will use these setpoints. Subsequent cycles rotate the setpoints among the pumps.
Set Relays to FIXED DUTY BACKUP Parameter Index P111 P111 P111 1 2 3 Value Description 51 51 51 Sets the pump relays (index 1, 2, and 3) to FIXED DUTY BACKUP. Only one pump will ever run at one time. Set the Relay ON Setpoints Index P112 P112 P112 1 2 3 Value Description 0.4m 0.3m 0.2m Sets the three setpoints for the pump relays. The setpoints remain attached to the pump relays. Parameter Index Value P113 0 1.
Set Relays to FIRST IN FIRST OUT (FIFO) ASSIST Parameter Index P111 P111 P111 1 2 3 Value Description 56 56 56 Sets the pump relays (index 1, 2, and 3) to FIFO DUTY ASSIST. Pump Control mmmmm Set the Relay ON Setpoints Parameter Index P112 P112 P112 1 2 3 Value Description 0.4m 0.3m 0.2m Sets the three setpoints for the pump relays. The first cycle will use these setpoints. Subsequent cycles rotate the setpoints among the pumps. Set the Relay OFF Setpoints Parameter Index Value P113 0 1.
When the first ON setpoint is reached, the pumps will start, one by one, until the material level rate of change is set at the same value or greater than the value in: • • P703 – Emptying Indicator (pump down applications) P702 – Filling Indicator (pump up applications) Set delay between pump starts using P132 – Pump Start Delay. Single Point Mode • Single Point Mode: one pump by rate control available that affects all pumps.
Totalizing Pumped Volume Pump Control mmmmm Prerequisite: the volume of the vessel must be known. Parameter Index P001 P002 P003 P004 P005 P006 P007 P050 P051 G G G G G G G G G Value Description 7 1 2 102 1 1.8 1.4 1 17.6 P111 P111 P111 P112 P112 P112 P113 1 2 3 1 2 3 0 52 52 52 1.0 1.2 1.4 0.2 Operation = pumped volume These parameters are as shown above. Tank shape is Flat Bottom. Max volume is 17.6m3 or 17,600 liters.
Setting a Pump to Run On When you need to pump below the normal OFF setpoint, use P130 (Pump Run-On Interval) and P131 (Pump Run-On Duration) to control this event. Example: The pump connected to Relay Three is set to pump for an extra 60 seconds every five times it is triggered. Index P130 3 Value Description 5 P131 3 60 Wait for Relay Three to pump five times and then run on. Run on for 60 seconds.
Example : A range of 0.5 meters is used to vary the setpoint. The randomly-selected setpoints are always inside the ON and OFF setpoints. Level Setpoint ON Wall Cling Value Pump Control mmmmm Random Setpoint Range Level Setpoint OFF Grouping Pumps You can group pumps and use the same pumping algorithm separately on each group. If you specify different pumping algorithms then the pumps are already grouped by algorithm and you do not need to use this parameter.
Example: The flush valve connects to Relay Four and the watched pump is on Relay One. Parameter Index P170 P171 P172 P173 G G G G Value Description 1 3 10 120 Watch Relay One to count pump cycles. Open the flush valve for 3 cycles. Use the flush value every 10 cycles. Open the flush valve for 120 seconds. Relay Controlled by Communications Parameter Index P111 5 Value Description 65 Sets Relay Five to communications control.
Rake (Screen) Control Screens or rakes are mounted on the inflow channel of the wastewater treatment plant to prevent debris from clogging the equipment. When material builds up on the screen, a level differential is created, and the water level is higher in front of the screen than behind it. When this differential reaches the programmed setpoint, the HydroRanger 200 activates a relay to operate mechanical rakes that clean the screen and ensure a steady flow.
Setting the Common Parameters Prerequisite: Substitute the details of your application in place of the sample values provided. If you are bench testing the unit, set your test values to be the same as the sample values. Parameter Index P001 P002 P003 P004 P005 P006 G G 1,2 1,2 G 1 2 1 2 P007 Value Description 4 1 2 102 1 1.8 2.2 1.4 1.4 Operation Material Max. Process Speed Transducer Units Empty Empty Span Span = Differential = liquid = medium = XPS-10 = meters = 1.8m = 2.2m = 1.4m = 1.
External Totalizers and Flow Samplers External totalizers are simple counters which count the number of relay clicks produced by the HydroRanger 200. This is generally used to keep track of OCM or pumped volume totals. Note that both of these values are also stored in the HydroRanger 200 and are available through communications. Flow samplers are devices which take a sample of liquid when triggered by a relay click. These samples are used to monitor water quality over time.
The source of units depends on the operation: Operation OCM (P001=6) Pumped Volume (P001=7) Units Source Parameter P604–Maximum Flow, or P608–Flowrate Units P051–Max Volume Flow Sampler Based on Volume and Time To trigger a flow sampler relay based on flow, use P111[r]=41 and set the other parameters: Counter Formula 1 Contact per P641 x 10P642 units Operation Units Source Parameter OCM (P001=6) P604 – Maximum Flow, or P608 – Flowrate Units By using a mantissa (P641) and an exponent (P642), the rela
Open Channel Monitoring (OCM) An OCM installation is defined one of three ways, based on the Primary Measuring Device (PMD): 1. Dimensional (P600 = 2,3,6,7) For some common weir and flume types. PMD dimensions (P602) are entered directly. • • • • BS-3680 / ISO 1438/1 Thin plate V notch weir on page 68 BS-3680 / ISO 4359 Rectangular Flume on page 69 Palmer Bowlus Flume on page 70 H Flume on page 71 2. Exponential (P600 = 1) For most other weir and flume types.
Setting Zero Head Many PMDs start flowing higher than the traditional empty distance of the application. You can account for the flow in one of two ways: 1. Use P605 (Zero Head) to have OCM calculations ignore levels below that value. Possible head = P007 – P605. Note: P603 (Max. Head) is preset to P007 and is not updated when P605 is used. Make sure you set P603 to the correct value when using P605. P006 P603 P007 2.
Setting Totalized Volume To display the totalized volume on the LCD use the following parameters: Parameter Index P737 G Value Description 2 Show the eight digit totalizer in the primary display Applications Supported by HydroRanger 200 BS-3680 / ISO 1438/1 Thin plate V notch weir Front View Side View Transducer notch angle P006 P603 P007 P602 P801 4 to 5 x hmax (hmax = P007) Open Channel Monitoring mmmm m Plan View Page 68 Parameter Index P600 P602 (view only) P603 P801 P608 G 1 2 G G
BS-3680 / ISO 4359 Rectangular Flume Diagonal View h Plan View 4 to 5 x hmax (hmax = P007) L Flow Front View Side View Transducer P006 h Flow P605 (p) G 1 2 3 4 5 6 7 G G (view only) (view only) (view only) P605 P608 7ML19981FC01 Value 6–ISO 4359 Rectangular Flume Approach width (B) Throat width (b) Hump Height (p) Throat length (L) Velocity coefficient (Cv) Discharge coefficient (Cd) Cross sectional area Zero Head Flowrate Units HydroRanger 200 – INSTRUCTION MANUAL Page 69 mmmmm Index P6
Palmer Bowlus Flume Plan View Flow Front View D/2, point of measurement Transducer Side View P006 P007 P603 P605 Parameter Index P600 P602 P603 P604 P605 P606 G 1 G G G G Value 2–Palmer Bowlus Flume Flume width (D) Maximum Head (preset = P007) Maximum Flow Zero Head Time Units Open Channel Monitoring mmmm m Application Information • • • • • Page 70 Sized by pipe diameter D Flume relief is trapezoidal Designed to install directly into pipelines and manholes Head is referenced to bottom of the
H Flume Transducer Flow Point of Measurement Plan View P006 P007 D Front View • • • • Parameter Index P600 P602 P603 P604 P606 G 1 G G G Value 3–H Flume Flume height (D) Maximum Head (preset = P007) Maximum Flow Time Units Sized by maximum depth of flume Approach is preferably rectangular, matching width and depth for distance 3 to 5 times the depth of the flume May be installed in channels under partial submergence (ratio of downstream level to head).
PMDs with Exponential Flow to Head Function For Primary Measuring Devices (PMDs) that measure flow by an exponential equation, use these parameters. Ensure that you use the correct exponent for your PMD; the values below are samples only. Standard Weirs Transducer 3 to 4 hmax h Weir Profile Applicable Weir Profiles Open Channel Monitoring mmmm m V-notch or triangular suppressed rectangular Parameter Index P600 P601 G G P603 P604 P606 P801 G G G G 1.
Non-Applicable Weir Profiles contracted rectangular compound Poebing approximate exponential Flows through these weirs can be measured using the Universal Flow Calculation P600 = 4 or 5. See Universal Calculation Support on page 76. Parshall Flume Note: C = Converging Dimension.
Leopold Lagco Flume Plan View Throat Front View Converging Diverging Transducer Point of Measurement Side View 0 Head Parameter Index P600 P601 P603 P604 P605 P606 G G G G G G Value 1–Leopold Lagco Flume 1.
Flume Size (pipe diameter in inches) Point of Measurement cm inches 4-12 15 18 21 24 30 42 48 54 60 66 72 2.5 3.2 4.4 5.1 6.4 7.6 8.9 10.2 11.4 12.7 14.0 15.2 1 1¼ 1¾ 2 2½ 3 3½ 4 4½ 5 5½ 6 Cut Throat Flume Plan View Application Information • • Similar to Parshall flume except that the floor is flat bottomed and throat has no virtual length. Refer to manufacturer’s specifications for flow equation and point of head measurement. G G G G G 7ML19981FC01 Value 1–Cut Throat Flume 1.
Universal Calculation Support When the primary measuring device (PMD) doesn’t fit one of the standard types, it can be programmed using a universal characterization. When Universal is selected as the PMD type (P600), then both P610 and P611 must be entered to define the flow. Two curve types are supported: • • P600 = 4–linear (piece wise linear) P600 = 5–curved (cubic spline) Both are shown in the following chart.
Example Flumes These example flumes would both require a universal calculation. Trapezoidal Dual Range (nested) Parshall Example Weirs These weirs could require universal calculation.
Open Channel Monitoring mmmm m Notes Page 78 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
Simulation In simulation mode, the LCD display reacts to the simulated level changes. Alarm relays will also react to the simulation, but any pump or control relays will not react. To allow pump or control relays to operate on the simulated level, set P000 to –1. Simulating a Single Measurement Access the appropriate parameter: (press PROGRAM and then key in the parameter number).
Testing the Configuration mmmmm The effect of the ARROW key is determined by the state (rate of rise or fall) immediately before the key is pressed. Action Press Press State (prior to pressing key) Effect Stop Rise at 1% of Span / second Rise at 1% of Span / second Rise at 4% of Span / second (max.) Rise at 4% of Span / second (max.
After you have installed the unit, we recommend that you perform a test to verify the wiring. Use P119 to force a state change and verify that the results are as expected (pump starts, alarm sounds, etc.). Discrete Inputs Use P270 to force the input value and verify that the results are as expected. 1. 2. 3. 4. 5. 6. 7. 8.
Testing the Configuration mmmmm Monitor system performance carefully, under all anticipated operating conditions. 1. When the HydroRanger 200 performs exactly as required, programming is complete. 2. If alternate Reading units, Failsafe action, or relay operation is desired, update the parameters for the new functionality. 3. If the system performance experiences problems, seeGeneral Appendix C: Troubleshooting, on page 218.
HydroRanger 200 Communications HydroRanger 200 Communication Systems The HydroRanger 200 is an integrated level controller capable of communicating process information to a Supervisory Control and Data Acquisition (SCADA) system, via a serial device such as a radio modem, leased line, or dial-up modem. HydroRanger 200 The standard HydroRanger 200 supports the following two communication protocols: Modbus Modbus is an industry standard protocol used by SCADA and HMI systems.
Communication Systems Communications mmmmm The HydroRanger 200 is capable of communicating with most SCADA systems, PLCs, and PCs. The supported protocols are: • Modbus RTU/ASCII – base unit on RS-232 or RS-485 transport • Profibus-DP – optional SmartLinx® module • Remote I/O – optional SmartLinx module • DeviceNet – optional SmartLinx module Communication Ports The HydroRanger 200 comes with two communication ports on the base unit.
Parameter P770 P771 P772 P773 P774 P775 P778 P782 Index Value 2 3 2 1 2 9.6 2 0 2 8 2 1 2 0 2 0 Description Modbus RTU slave Network address, only used for RS-485 Data rate of 9600 baud No parity, common setting 8 data bits, common setting 1 stop bit, common setting No modem connected Index parameter values globally Dolphin Plus Dolphin Plus software makes it easy to record and compare parameter sets for all the HydroRangers in your company.
Communications Installation Wiring Guidelines • • • • the RJ-11 cable maximum length is 3 meters RS-485 maximum length is 1,200 meters (4,000 feet) use 24 AWG (minimum) use good quality communication grade (shielded twisted pairs) cable that is recommended for RS-485 for port 2 (Belden 9842) run the communication cable separately from power and control cables (do not tie wrap your RS-232 or RS-485 cable to the power cable or have them in the same conduit) use shielded cable and connect to ground at one end
Port 1: RS-232 RJ-11 Jack To connect the unit to a PC using an RS-232 jack, use the cable as shown: RJ-11 to DB 9 converter TX 4 RG 3 SG 2 6 5 4 3 2 1 4 6 7 8 RX 5 TG 3 SG 2 6 5 4 3 2 1 6 6 1 6 1 1 6 1 RJ-11 jack Modular cable with RJ-11 plug RJ-11 on HydroRanger 200 Computer DB-9 (male) Note: Jumper pins 4-6 and 7-8 at the DB-9.
To connect the unit to a modem using an RS-485 port: COM Modem HydroRanger 200 Terminal Block A B Configuring Communication Ports (Parameters) The 11 parameters listed are indexed to the two communication ports, unless otherwise noted: An asterisk (*) identifies the preset value.
P772 Baud Rate The communication rate with the master device. Primary Index Communications Port Values 4.8 4800 baud 9.6 9600 baud 19.2 * 19,200 baud (preset for port 2) 115.2 * 115,200 baud (preset for port 1) This specifies the rate of communication in Kbaud. Any value may be entered, but the only values supported are those shown above. The baud rate should reflect the speed of the connected hardware and protocol used. P773 Parity The serial port parity.
P778 Modem Available Sets the HydroRanger 200 to use an external modem. Primary Index Communications Port 0 Values * 1 No modem connected Answer only P779 Modem Inactivity Timeout Sets the time that the unit will keep the modem connected with no activity. Primary Index Communications Port Values Range: 0-9999 seconds Communications Installation mmmmm 0 * No timeout To use this parameter, ensure that P778 (Modem Available) =1.
Modbus Register Map Features affecting volume, mA input, and Average or Difference readings apply to the HydroRanger 200 only. They are clearly marked. The memory map of the HydroRanger 200 occupies the Modbus holding registers (R40,001 and up). This map is used when the protocol is Modbus RTU slave or Modbus ASCII slave. Register Map for Most Common Data Legend Type The type of data held in the group of registers. Start The first register to hold the referenced data.
Type Point Data I/O Pump Control Description Start Temperature (2) 41,030 Discrete Inputs (2) 41,070 Relay Outputs (3 or 6) 41,080 mA Input (1) 41,090 mA Output (2) 41,110 2 1 1 Data Type Read/ Write –50 to 150 R Bit Mapped R Bit Mapped R/W 1 0000 to 20,000 R 2 0000 to 20,000 R/W Pump on Setpoint (3 41,420 or 6) 6 0000 to 10,000 R/W Pump off Setpoint (3 41,430 or 6) 6 0000 to 10,000 R/W UINT32 R 12 UINT32 R 6 0000 to 10,000 R Pumped Volume (2) 41,440 Pump Hours
Product ID (R40,064) Identifying Milltronics device type: Device Type Value HydroRanger 200 4 Point Data (R41,010 – R41,031) Measurement point data contain the current instrument readings. These are the values shown for the reading measurement for each measurement point. The reading is based on the setting for P001 (operation). P001 can be set to level, distance, OCM flow, or volume. See HydroRanger 200 Parameter Reference section on page 113 for details. The measurement registers are 41,010 to 41,012.
Discrete Inputs (R41,070) This table shows the current status of the discrete inputs. Only register 41,070 is used. Discrete Input Data Address 1 41,070, bit 1 2 41,070, bit 2 Relay Outputs (R41,080) This table shows the current status of the relays. A reading of 0 means that the relay function is not asserted and a 1 means that it is asserted. For example, a 1 for a pump relay means that the pump is running.
Pump OFF Setpoint (R41,430 – R41,435) The OFF setpoint level (P113) for the referenced pump relay. The setpoint is scaled from 0 to 10,000 (0 to 100% of span multiplied by 100). So 54.02% is shown in the register as 5402. Pumped Volume (R41,440 – R41,443) The pumped volume registers hold the current total for all of the pumps associated with a level point. These registers are available only if operation is set to pumped volume (P001 = 7). These volumes can become very large.
Usually, the parameters are all read / write. Note: • • • Parameters P000 and P999 are read only. If P000 is set to lock activated then all of the parameters are read only Parameter P999 (Master Reset) cannot be used via Modbus See Data Types on page 101 for a description of the different types of data associated with different parameters Each parameter register has a corresponding format register that holds the format information required to interpret the value.
Global Index Method (P782 = 0) Global format method sets index values for all parameters simultaneously. Use this method to read multiple values set to the same index values. 1. Write the primary index value into R43,999. This is a value between 0 and 40 which specifies the input or output indexed by the parameter. Examples are: • • • 2. Transducer 1 is index 1 Discrete input 2 is index 2 Relay 5 is index 5 Write the secondary index value into R43,998.
2. Read the value from the appropriate parameter register (the example uses 44,921). Types of values are: • Numeric Values on page 101 • Bit Values on page 101 • Split Values on page 102 • Text Messages on page 103 • Relay Function Codes (P111 Only) on page 104 A value of 22,222 indicates that an error occurred. Specify a different format type and try again. Writing Parameters The method of writing parameters is similar to the method of reading them.
Global Index Method (P782 = 0) Only the final digit of the format word determines the decimal offset (below). Parameter-Specific Index Method (P782 = 1) All three decimal fields are used to determine the parameter value’s primary index, secondary index, and decimal offset.
Examples of using the format word for both the index values and the decimal offset value are shown below: Format Primary Index Secondary Index Decimal 00000 00 00 0 01003 01 00 3 right 02038 02 03 3 left 05159 05 15 percent Modbus Register Types mmmmm To write these values you can use a decimal offset as follows: format word = (primary index x 1000) + (secondary index x 10) + (decimal).
Data Types The HydroRanger 200 parameters do not always use integers to hold values. For the convenience of the programmer, those values are converted to and from a 16-bit integer number. This section describes the conversion process. The sections that follow describe where those values are in the discrete I/O and block transfer addresses, and how to get the parameters you need. Numeric Values Numeric parameter values are the most common.
For example, if R41,442 is read as a UINT32, the 32 bits would look like this: R41,442 16 MSW 32 R41,443 1 16 LSW 32-bit integer value (UINT32) 1 1 The two registers are read as a 32-bit integer. The most significant word (MSW) and least significant word (LSW) can be reversed to accommodate some Modbus drivers. See Word Order (R40,062) on page 92 for details. The position of the decimal place is dependent on the register. For more details see the description of the register.
Text Messages If a Milltronics device parameter returns a text message, that message is converted to an integer and provided in the register.
Relay Function Codes (P111 Only) If a Milltronics device parameter returns a relay function code, that message is converted to a number and is then provided in the register.
Error Handling When polled by a Modbus Master, a slave device will do one of the following: 1. Not reply. This means that something went wrong with the transmission of the message. 2. Echo back the command with the correct response (see the Modbus specification for more details). This is the normal response. 3. Return an Exception Code. This reflects an error in the message.
Error Handling mmmmm • If P000 is activated, then the value will be ignored and no error response will be made. However, the current value will not reflect the desired new value. • If the host attempts to write one or more registers that are out of range, an exception response code 2 or 3 is generated, depending if the start address is valid. • If the host used an unsupported function code, an exception response code of 01 should be generated.
Communication Troubleshooting 1. Check the following: • • • There is power at the unit The LCD is showing the relevant data The device can be programmed using the hand programmer 2. Check the wiring pin outs and verify that the connection is correct. 3. Verify that values in the set-up parameters (P770 to P779) match the settings in the computer used to communicate with the unit. 4. Check that the port on the computer is correct. Sometimes trying a different Modbus driver will solve the problem.
Communication Appendix A: Single Parameter Access (SPA) This Appendix is intended to provide someone with advanced communications knowledge the ability to access any parameter value in any available format. Built into HydroRanger 200 is an advanced handshaking area that can be used to read and write single registers to the HydroRanger 200. This section performs a similar function to the Parameter access section. The differences are: 1. Advanced section is more powerful and harder to program. 2.
Writing Parameters To set parameters through Modbus do the following steps: 1. Send the parameter, its primary index, and its secondary index (usually 0) to registers 40,090, 40,091, and 40,092. 2. Write the value to registers 40,096 and 40,097. 3. Write the desired format word to register 40,093 to enable the HydroRanger 200 to interpret the value correctly.
Error Codes The error codes returned in the format area are 8-bit integers found in the lowest eight bits of the format word. This allows for 256 potential error codes. Currently the HydroRanger 200 has two error codes available.
Parameter Reference The HydroRanger 200 is configured through its parameters, and the application determines the parameter values which are entered into the unit. Please check your value entries carefully before operating the HydroRanger 200 to ensure optimum performance.
Parameters mmmmm Notes Page 112 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
P000 Lock Secures the HydroRanger 200 from changes. Primary Index Global 1954 Values * -1 other Related • OFF (programming permitted) Simulation Controls (relays energize based on simulated level) lock activated (programming secured) Simulation WARNING: Use this lock as backup security only. It uses a fixed value which can be discovered by unauthorized personnel. Access this parameter directly (type 000) and enter any value (except 1954) to secure programming lock.
For these operations any of three level points (transducer 1, transducer 2, or the calculated point) can be used to trigger relays (see P110 on page 127). The points must be globally set to either 4 or 5 (as required). Point 3 becomes the calculated value as shown above. See Rake Control example on page 62. P002 Material Specifies material type.
P004 Transducer Specifies the Siemens Milltronics transducer connected to the unit. Values Related Global 0 * No transducer attached (preset for Dual Point) 1 ST-25 2 ST-50 100 STH 101 XCT-8 102 * XPS-10 (preset for Standard Mode) 103 XCT-12 104 XPS-15 112 XRS-5 250 mA input • mA Input (P250 to P260) • P842 Short Shot Frequency • P843 Long Shot Frequency • P844 Short Shot Width • P845 Long Shot Width • P852 Short Shot Range P005 Units Specifies measurement units used for dimensional values.
P006 Empty Enter distance in units (P005) from the face of the transducer to the process empty point. Primary Index Values Transducer Range: 0.000 to 9999 Preset: 5.000m (or equivalent depending on units) Alters • Altered By • P005 Units Related • • • P800 Near Blanking P921 material Measurement P927 Distance Measurement P007 Span Setting this value also sets Span (P007) unless Span was already set to another value. For distance operation (P001=3), Span is preset to Empty.
Always prevent the monitored surface from approaching within 0.33m (1 ft) of the transducer face as this is the minimum blanking for most Siemens Milltronics transducers (some require more blanking – see your transducer manual). Many other parameters are set as a percentage of span (even if they are entered in units).
Parameters mmmmm Values Alters Page 118 4 Half Sphere Bottom 5 Flat Sloped Bottom 6 Flat Ends 7 Parabola Ends 8 Sphere 9 Universal Linear 10 Universal Curved • • • • • P001 Operation P051 Maximum Volume Pump Efficiency (P180-P186) Pumped Volume Totalizer (P622-P623) P920 Reading Measurement HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
P051 Maximum Volume For Readings in volumetric units (rather than percent), enter the vessel volume between Empty (P006) and Span (P007). Primary Index Global Range: 0.000 to 9999 Values Preset: 100.0 Alters P060 Decimal Position Related • • • P006 Empty P007 Span P924 Volume Measurement Any volume units can be chosen because volume is calculated from empty to maximum span and is scaled according to the Tank Shape (P050) value.
P054 Level Breakpoints (Universal Volume Calculation) When the tank shape is too complex for any of the preconfigured shapes, you can specify the volume based on segments. Primary Index Global Secondary Index Breakpoint Values Range: 0.0 to 9999 Related • P055 Volume Breakpoints Enter the following: • up to 32 level breakpoints (where volume is known) if P050 = 9 or 10 Entering a Level Breakpoint 1. 2. 3. Go to Parameter P054. For each index enter a breakpoint in measurement units.
Entering a Volume Breakpoint 1. 2. 3. Go to Parameter P055. For each index enter a volume. Ensure that each volume corresponds to the same index for P054. For more on Volume Characterization, go to page 44.
Examples: • • If the measured value is in feet, enter 0.3333 to display the number of yards For simple linear, volume conversions set POO5 to 1 (meters) and then enter the volume measurement per unit to get the correct conversion. For example, if the reservoir contains 100 litres per vertical meter, use 100 to get the reading in litres. Notes: • • This method does not calculate volume.
P065 Reading Override Value This value is substituted for the current reading when the selected discrete input is enabled and activated. Primary Index Transducer Values Range: 0.
Failsafe (P070 to P072) P070 Failsafe Timer The time for invalid measurements to elapse before Failsafe State activates. Primary Index Values Global Range: 0.0 to 9999 Preset 10.00 minutes Altered by • P003 Maximum Process Speed Related • P129 Relay Failsafe Once activated, the Failsafe State initiates the following: 1. 2. The material level is reported based on P071 Failsafe Material Level.
Selecting HI, LO, or HOLd 1. Press FUNCTION 2. Press ARROWS 3. Press ENTER to display the Auxiliary Function symbol. to scroll to the desired option. to set the value. Entering a Measurement To enter a specific Failsafe Material Level within -50 to 150% of Span (P007), in Units (P005). Relay reaction The way in which relay programming reacts to the failsafe level depends on P129 Relay Failsafe (page 132). By default: • • Alarm relays have P129 = OFF and so react to the Failsafe Material Level.
Relays (P100 to P119) The HydroRanger 200 has six relays (or digital outputs) used to control devices and alarms. While the number of devices is limited by the relays, all control functions are accessible through software and each parameter is indexed to the three or six relays. See the Relay section on page 34. Preset Applications (P100) The HydroRanger 200 makes standard applications easier to program by providing an extensive list of presets.
P110 Level Source Sets the level source on which the indexed relay is assigned to a measurement point.
Values For P111 Control #1 Type Fixed Duty Assist 50 Fixed Duty Backup 51 Alternate Duty Assist Alternate Duty Backup Service Ratio Duty Assist Service Ratio Duty Backup First In First Out (FIFO) Pump 52 53 54 55 56 Flush Valve 64 Communication 65 Control 1.
P113 Relay OFF Setpoint Sets the process point at which the relay returns to its NORMAL state. Primary Index Relay Range: -999 TO 9999 Values Preset: ---- Altered by • P007 Span Related • • • P100 Preset Applications P111 Relay Control Function P112 Relay ON Setpoint For most applications, the relay is reset at this point. For IN-BOUNDS and OUT-OFBOUNDS alarms, it is the low point in the specified range.
P118 Relay Output Logic The logic applied to relays to determine the contact open or closed state. Primary Index Relay Value Values 2 3 Related • * Logic Alarm Contact Pump or Control Contact Positive Normally Closed Normally Open Negative Normally Open Normally Closed P111 Relay Control Function The relay contact operation is NORMALLY CLOSED for alarms and NORMALLY OPEN for controls. See P111 Relay Control Function for more information.
P119 Relay Logic Test Forces the relay control logic into an ACTIVATED or DE-ACTIVATED state. Primary Index Relay 0 Values * 1 Activate relay control 2 Related • • OFF - Control from HydroRanger 200 algorithms De-activate relay control P111 Relay Control Function P910 Toggle Relays This parameter tests site wiring and control logic programming. Forcing the relay to an activated or de-activated state is similar to the HydroRanger 200 detecting an event and responding to it.
P122 Pump Service Ratio Selects pump usage based on the RUN time ratio rather than last used. Primary Index Values Related Relay Range: 0.000 to 9999 Preset: 20.00 • P111 Relay Control Function This parameter only relates to relays with P111 = 54 or 55. To make this parameter useful, assign it to all of the pump relays. The number assigned to each pump relay represents the ratio applied to decide the next pump to start or stop.
Relay Function (P111) Preset (P129) 1 – level alarm 2 – in bounds alarm 3 – out of bounds alarm OFF 4 – rate of change alarm 5 – temperature alarm 50 to 56 – all pump controls dE To select an independent Relay Failsafe value: 1. Press FUNCTION to display the Auxiliary Function symbol. 2. 3. Press ARROWS to scroll through the failsafe options. Select option and press ENTER . Advanced Pump Control Modifiers (P130 to P137) These parameters only affect relays set to pump operation (P111 = 50 to 56).
P131 Pump Run-On Duration Sets the number of seconds that the pump runs on. Primary Index Values Related Global Range: 0.0 to 9999 Preset: 0.000 • Advanced Pump Control Modifiers (P130 to P136) Your pump capacity determines the amount of material that can be removed. Choose a value long enough to clean out the vessel bottom, yet short enough not to run the pump dry. Also be sure that this value does not overlap with P130 (Interval).
P133 Pump Power Resumption Delay Sets the minimum delay before the first pump restarts after power failure. Primary Index Global Range: 0.000 to 9999 Values Preset: 10 seconds • • Related Advanced Pump Control Modifiers (P130 to P136) P132 Pump Start Delay This reduces the surge from the first pump starting immediately on power resumption. When this delay expires, other pumps will start as per P132.
P137 Pump Group Puts pumps into groups for multiple pump rotations on one transducer. Primary Index Relay Range: 1 to 2 Values 1 2 • Alters * group 1 group 2 P111 Relay Control Function when P111=52 (Alternate duty assist) or 53 (Alternate duty backup) This feature groups pumps (relay points 1 - 6) into groups 1 or 2. It is applied to pump rotation and occurs independently within each group.
P170 Flush Pump Picks the number of the pump relay which triggers the flushing device. Primary Index Global Range: 0 to 6 Values Preset: 0 Related • P111 = 64, Flush Valve Enter the relay number of the pump with the flush valve. The activation of this pump relay drives the usage of the flush system. Both P172 Flush Interval and P171 Flush Cycles are based on the operation of this relay and controls any relay set to P111 = 64, Flush Valve.
P173 Flush Duration The length of time for each flush cycle that the flush control is active. Primary Index Values Related Global Range: 0.000 to 9999 s Preset: 0.000 • P111 = 64, Flush Valve mA Output (P200 to P219) P200 mA Output Range Determines the mA output range.
P201 mA Output Function Alters the mA output/measurement relationship. Primary Index Values mA output value mA function Operation (P001) 0 OFF 1 level level, differential, or average 2 space space 3 distance distance 4 volume level or space 5 flow OCM 6 head 7 volume rate 8 mA input 9 comms input Related • • P202 mA Output Allocation P911 mA Output Value Altered By • P001 Operation P202 mA Output Allocation Sets the input source from which the mA output is calculated.
P203 mA Output Value / Transducer Displays current mA output value for the Point Number. Primary Index Level Values Range: 0.000 to 22.00 (view only) This displays as an Auxiliary Reading when key is pressed in the RUN mode and does not include adjustments made using Trim features (P214 / P215). Note: This parameter is applicable only if any mA output has the transducer Point Number as its input source (see P201 and P202).
P210 0/4 mA Output Setpoint Sets the process level corresponding to the 0 or 4mA value. Primary Index mA output Values Range: -999 to 9999 Related • P211 20 mA Output Setpoint Enter the value (in applicable units or %) to correspond to 0 or 4 mA. P211 20 mA Output Setpoint Sets the process level that corresponds to the 20 mA value. Primary Index mA output Values Range: -999 to 9999 Related • P210 0/4 mA Output Setpoint Enter the value (in applicable units or %) to correspond to 20 mA.
P213 mA Output Max Limit Sets the maximum mA output value (in mA) to be produced. Primary Index Values Related mA output Range: 0.000 to 22.00 Preset: 20.2 mA • P200 mA Output Range / P212 mA Output Min LImit mA Output Trim (P214 to P215) This does not affect the P203 value shown, and is used when recalibration of an external device is impractical. P214 4 mA Output Trim Calibrates the 4 mA output.
mA Output Failsafe (P219) P219 mA Output Failsafe Use for failsafe operation, independent of the Failsafe Material Level (P071). Primary Index mA output Range: 0.000 to 22.00 OFF Values Related * mA output responds to Failsafe Material Level (P071). HOLd last known value is held until normal operation resumes LO produce the Empty mA output immediately HI produce the Span mA output immediately • P201 mA Output Function Selecting an independent mA Failsafe option: 1. Press MODE 2.
P251 0 or 4 mA Input Level Shows the process level corresponding to the 0 or 4 mA value. Primary Index Values Related Global Range: -999 to 9999% Preset: 0% • • P006 Empty P007 Span When using an external mA signal to determine level, the input range must be scaled to give accurate results. P252 20 mA Input Level Shows the process level corresponding to the 20 mA value.
P254 Scaled mA Input Value Shows the resulting level value after scaling. Primary Index Values Global Range: -999 to 9999 (view only) Preset: calculated from the input mA signal This parameter is calculated from the input mA signal. P260 mA Raw Input Shows the raw mA input supplied by the external device. Primary Index mA input Values Range: 0.000 to 20.
P275 Scaled Discrete Input Value Shows the current value of the discrete input after any scaling is applied. Primary Index Discrete input Display: view only Values: dependent on the function of the discrete input Range of Values Values Function (P270) 1 Forced ON 0 Forced OFF 0 (DI open), 1 (DI closed) Normally Open 0 (DI closed), 1 (DI open) Normally Closed Readings are updated continuously even in PROGRAM mode. The value signals a level override event.
P300 Temperature, Transducer Maximum Shows the highest temperature encountered, as measured by the temperature sensor in the transducer (if applicable). Primary Index Values Related Press CLEAR Transducer Range: - 50 to 150°C (view only) Preset: - 50°C • P301 Temperature, Transducer Min keys to reset the log after a short circuit on the transducer wiring.
P303 Temperature, Sensor Minimum Shows the lowest temperature encountered, as measured by the TS-3 Temperature Sensor (if applicable). Primary Index Global Range: - 50 to 150°C (view only) Values Preset: 150°C Related Press CLEAR • P302 Temperature, Sensor Max keys to reset the log after an open circuit on the transducer wiring. Record Readings (P304 and P305) This identifies the occurrence of the record high and low level readings.
Pump Records (P310 to P312) These features to identify pump usage and if the associated Relay Function (P111) is set for any pump control feature. The value is that of the pump connected to the associated terminals. Enter a value to set the current record to that value. Use this if a pump is added with a known number of hours logged, or the value can be reset to zero 0 after maintenance. P309 Pump RUN Time Displays the amount of time in minutes since a relay was last activated.
P312 Pump Run Ons View or reset the accumulated number of times the displayed Relay Number has been held ON via Run On Interval (P130). Primary Index Relay Values Range: 0 to 9999 Related • Relay Function (P111) set for any pump control feature Flow Records (P320 and P321) These features are enabled if Operation is set for OCM (P001 = 6), or an OCM device is defined (P600 ≠ 0).
LCD Totalizer (P322 and P323) Use these features to view, reset, or preset the eight-digit display totalizer when Operation is set for OCM or Pumped Volume (P001 = 6 or 7). The eight-digit totalizer is divided into two groups of four digits. The four least significant totalizer digits are stored in P322, and the four most significant digits are stored in P323. Adjust these values separately to set a new total. Example: P323 = 0017 P322 = 6.294 Totalizer Display = 00176.
Profile Records (P330 to P337) WARNING: These parameters are for authorized service personnel or technicians familiar with Siemens Milltronics echo processing techniques. These features can record up to ten Echo profiles, initiated manually (P330), or automatically (P331 et al). See Scope Displays (P810) for echo profile viewing hardware / software requirements. If ten Profiles are already saved, addresses 1 through 10 are filled, the oldest automatically initiated record is overwritten.
Recording a profile manually Press TRANSDUCER to fire the transducer and record the echo profile into the internal scope buffer for display. For differential or average operation (P001 = 4 or 5), access scope Displays (P810) parameter to select the transducer number. Saving a manual record Press ENTER to copy the echo profile record in the scope buffer and save it in the selected address in the record library. The parameter value field displays the new record information.
P332 Auto Record Transducer Specifies the Transducer Point Number for which Auto Profile Records are saved. Primary Index Global Range: 0 to 2 Values Altered By 0 1 Any transducer * Transducer One 2 Transducer Two • P001 Operation = 4 or 5 This feature is preset to Point Number 1. (Alteration is only required if differential or average Operation [P001 = 4 or 5] is selected.
P334 Auto Record ON Setpoint Enter the critical level which, in conjunction with Auto Record OFF Setpoint, defines the boundaries for Auto Profile Records to be saved. Primary Index Global Values Range: -999 to 9999 Related • • • P335 Auto Record OFF Setpoint P336 Auto Record Filling / Emptying P337 Auto Record LOE Time P335 Auto Record OFF Setpoint Enter the critical level which, in conjunction with Auto Record ON Setpoint, defines the boundaries for Auto Profile Records to be saved.
P337 Auto Record LOE Time Limits Auto Profile Records from being saved unless extended LOE occurs. Primary Index Global Range: 0.0 to 9999 (seconds) Values Preset: 0.0 • • • Related P334 Auto Record ON Setpoint P335 Auto Record OFF Setpoint P336 Auto Record Filling / Emptying If the LOE condition exceeds the period entered, the Echo Profile is saved. When set for 0 LOE is not required for an Auto Profile Record to be saved.
P342 Start Ups The number of times power has been applied since the Date Of Manufacture. Primary Index Global Values Range: 1 to 9999 (view only) Related • • P340 Date of Manufacture P342 Run Time Open Channel Monitoring (P600 to P621) If the HydroRanger 200 is used to monitor open channel flow, alter the following parameters as required and run a calibration as described in P621. Note: See Open Channel Monitoring (OCM) on page 66 for application examples involving common weirs and flumes.
Alters • • • P601 Flow Exponent P602 Primary Measuring Device Dimensions P608 Flowrate Units Altered By • P001 Operation Related • • • • • P603 Maximum Head P604 Maximum Flow P605 Zero Head P610 Head Breakpoints P611 Breakpoint If your PMD is not listed, select the appropriate Universal Flow Calculation. Associated parameters Max Head (P603), Max Flow (P604), and Min Head (P605) may be scroll accessed. If Operation is not set for OCM (P001 = 6), this value is preset to 0.
Example Exponents PMD Type Exponent (sample only) Suppressed Rectangular Weir 1.50 Cipolletti Weir 1.50 Venturi Flume 1.50 Parshall Flume 1.22 to 1.607 Leopold Lagco 1.547 V-Notch Weir 2.50 P602 Primary Measuring Device Dimensions The dimensions of the Primary Measuring Device (PMD).
P603 Maximum Head The level value associated with Maximum Flow, in Units (P005). Primary Index Values Global Range: -999 to 9999 Preset: Span (P007) value Altered By • • P005 Units P600 Primary Measuring Device (PMD) Related • • P604 Maximum Flow P605 Zero Head Represents the highest head level supported by the PMD and works in conjunction with Maximum Flow (P604) to define the highest point in the exponential curve. Use it when the PMD requires a maximum head and flow reference point.
P605 Zero Head The distance above Empty (P006) in Units (P005) representing zero head (and zero flow). Primary Index Global Range: -999 to 9999 Values Preset: 0.000 Altered By • • P005 Units P007 Span Related • • P006 Empty P801 Range Extension • P926 Head Measurement Use for most weirs and some flumes (e.g. Palmer Bowlus) where the zero reference is at a higher elevation than the channel bottom.
P607 Flowrate Decimal The maximum number of decimal places to be displayed. Primary Index Values Altered By Global 0 no digits after the decimal point 1 1 digit after the decimal point 2 2 digits after the decimal point 3 3 digits after the decimal point • P060 Decimal Position (sets max. number) In RUN mode, the number of decimal places displayed is automatically adjusted (if necessary) to prevent the number of Flowrate digits from exceeding display capabilities.
This parameter is enabled only if the primary measuring device (PMD) supports absolute calculations (P600=6,7). For absolute PMDs (P600=6,7) volume units can be specified using this parameter. If needed, absolute PMDs can still use ratiometric (P608=0) to accommodate other units. P610 Head Breakpoints The head breakpoints for which flowrate is known. Primary Index Global Secondary Index Breakpoint Values Range: 0.
P620 Low Flow Cutoff Eliminates totalizer activity for flows at or below the cutoff value. Primary Index Values Global Range: 0.000 to 9999 Preset = 5.000 %, or equivalent units Altered By • P005 Units Related • P007 Span Use this to enter the minimum head in units (P005) or as a percent of span. P621 Auto Zero Head Calibrates Zero Head (P605) based on actual head measurements.
Pumped Volume Totalizer (P622) The Pumped Volume Totalizer is a HydroRanger 200 feature only. If the eight-digit totalizer display or a remote totalizer contact closure are desired, alter the following parameters. P622 Inflow / Discharge Adjust The method used to calculate the volume pumped, for pumped total Operation (P001 = 7).
Totalizer (P630 to P645) P630 LCD Totalized Multiplier Use this feature if the LCD Total increments by too large (or too small) an amount. Primary Index Values Values Related Global -3 .001 -2 .01 -1 .1 0 * 1 1 10 2 100 3 1000 4 10,000 5 100,000 6 1,000,000 7 10,000,000 • LCD Totalizer (P322 and P323) Enter the factor (powers of 10 only) by which actual volume is divided, prior to display on the LCD.
P633 LCD Totalized Decimal Position Enter the maximum number of decimal places to be displayed. Primary Index Global 0 Values no digits after the decimal point 1 1 digit after the decimal point * 2 3 Related • 2 digits after the decimal point 3 digits after the decimal point LCD Totalizer (P322 and P323) Note: Set the decimal position during initial commissioning of the MultiRanger 200.
P641 Flow Sampler Mantissa Use this feature in conjunction with Flow Sampler Exponent (P642) to establish the number of flow units required to increment the Flow Sampler (device connected to the HydroRanger 200 relay set for the flow sampler operation) (Relay Function, P111 = 41). Primary Index Values Related Global Range: 0.001 to 9999 Preset = 1.
P645 Relay Duration Use this feature (if desired) to adjust the minimum contact closure duration of a relay set as a totalizer, flow sampler, time [control], or aeration (P111 = 40 or 41) Primary Index Global Range: 0.1 to 1024 Values Preset = 0.2 (sec) Related • P111 Relay Control Function Enter minimum contact closure duration (in seconds) required by the device connected. For the flow sampler function this value is used for both the ON time of the relay and the OFF time between contacts.
Before using this feature, verify the following parameters are correct: • • • • Empty (P006) Temperature (P664) Offset Reading (P062) Zero Head Offset (P605), if using OCM Offset Calibration Begin with a steady level. 1. 2. 3. 4. Press TRANSDUCER to display the calculated reading. Repeat Step One at least five times to verify repeatability. Measure the actual reading (use tape measure). Enter the actual value.
P652 Offset Correction The value altered when an Offset Calibration is performed. Primary Index Global Values Range: -999 to 999.0 Related • P650 Offset Calibration Alternatively, if the amount of Offset Correction required is known, enter the amount to be added to the Reading before display. P653 Velocity The value adjusted based on the Sound Velocity at 20 °C (P654) vs. Temperature (P664) characteristics of air. Primary Index Global Values Range: 50.01 to 2001 m/s (164.
Temperature Compensation (P660 to P664) P660 Temp Source Source of the temperature reading used to adjust the speed of sound.
P663 Temperature Transducer Allocation This feature may only be used for differential or average Operation (P001 = 4 or 5). Primary Index Transducer 1 Values Transducer One 2 Transducer Two 1:2 Transducer One and Two average • • • Related * P651 Sound Velocity Calibration P653 Velocity P654 Velocity at 20°C As preset, the temperature measurements of Ultrasonic / Temperature Transducer One and Two are allocated to Points 1 and 2 respectively.
Rate (P700 to P708) These parameters determine how material level changes are reported. P700 Max Fill Rate Adjusts the HydroRanger 200 response to increases in the actual material level (or advance to a higher Failsafe Material Level, P071). Primary Index Global Values Range: 0.000 to 9999 Altered by • P003 Maximum Process Speed Related • • P005 Units P007 Span • P071 Failsafe Material Level Enter a value slightly greater than the maximum vessel filling rate.
P702 Filling Indicator The fill rate required to activate the LCD Filling indicator ( ). Primary Index Global Values Range: -999 to 9999 Altered by • P003 Maximum Process Speed Related • • P005 Units P007 Span • P700 Max Fill Rate This value (in Units (P005) or % of Span (P007) per minute) is automatically set to 1/10 of the Max Fill Rate (P700). P703 Emptying Indicator The empty rate required to activate the LCD Emptying indicator ( ).
Alters • P707 Rate Value Altered by • P003 Maximum Process Speed Related • P705 Rate Update Time/ P706 Rate Update Distance Enter the time or distance interval over which the Rate Value is to be calculated before the display updates. This is automatically altered along with Maximum Process Speed (P003). This value automatically alters the Rate Update Time (P705) and / or Rate Update Distance (P706). Alternatively, these parameter values may be altered independently.
P708 Volume Rate Display The rate of change of volume in percent of maximum volume per minute. Primary Index Global Values Range: -999 to 9999 (view only) Related • P622 Inflow / Discharge Adjust This value is used internally to calculate inflow in pumped volume applications (P622=3). Press READING to toggle between percent and volume.
If a material agitator (mixer) is used in the vessel monitored, set Echo Lock for maximum verification or material agitator to avoid agitator blade detection. Ensure the agitator is always on while the HydroRanger 200 is monitoring the vessel to avoid stationary blade detection. When set for max verification or material agitator, a new measurement outside of the Echo Lock Window (P713) must meet the sampling criterion (P712). For total lock, Echo Lock Window (P713) is preset to zero 0.
P713 Echo Lock Window Adjusts the size of the Echo Lock Window. Primary Index Global Range: 0.000 to 9999 Values Preset: 0.000 Altered by • P003 Maximum Process Speed Related • P005 Units • P711 Echo Lock The Echo Lock Window is a distance window (units P005) centred on the echo and used to derive the Reading. A new measurement in the window re-centers the echoe and the new Reading calculated. Otherwise, the new measurement is verified by Echo Lock (P711) before the reading is updated.
This feature may only be used to adjust the delay before the next point is scanned. Enter the amount of delay in seconds. This value is automatically altered when Maximum Process Speed (P003) is altered. P728 Shot Delay The delay, in seconds, between transducer shots. Primary Index Transducer Range: 0.1 to 4.0 Values Preset: 0.5 Use this if transient acoustic noise within the vessel causes measurement difficulties due to echoes from one shot being received on the next.
Selecting the Auxiliary Reading operation 1. Press READING 2. Press ARROWS 3. Press ENTER to display the Auxiliary Function symbol. to access the OFF or HOLd option desired. If necessary, enter the Parameter Number to default in the Auxiliary Reading display. That value will show in the auxiliary reading area by default. Other values are available but will reset to the parameter defined here.
P733 Scroll Access Use this feature to select the parameter scroll access option desired. Primary Index Global 0 Values 1 * 2 Press READING Off Scrolls to all parameters (P001 to P999) Smart for Quick Start, altered, and tagged parameters Tagged Scrolls to operator tagged parameters only to tag/untag any accessed parameter. and display indicates the parameter accessed is tagged. Note: Quick Start parameters (P001 – P007) and those changed from factory default settings cannot be untagged.
SmartLinx Reserved (750 to 769) These parameters are reserved for optional SmartLinx communications cards and vary by card. Refer to the SmartLinx documentation to determine if any of them are used. Communications (P770 to P782) The HydroRanger 200 communication ports are configured by a series of parameters that are indexed by port. See Communications on page 83 for a complete description of communications set-up.
P772 Baud Rate The communication rate with the master device. Primary Index Communications Port Values 4.8 4800 baud 9.6 9600 baud 19.2 * 19,200 baud (preset for port 2) 115.2 * 115,200 baud (preset for port 1) This specifies the rate of communication in Kbaud. Any value may be entered but only the values shown above are supported. The baud rate should reflect the speed of the connected hardware and protocol used. P773 Parity The serial port parity.
P775 Stop Bits The number of bits between the data bits. Primary Index Values Communications Port Range: 1 or 2 1 * Preset: P778 Modem Available Sets the HydroRanger 200 to use an external modem. Primary Index Values Communications Port 0 * 1 No modem connected Answer only P779 Modem Inactivity Timeout Sets the time that the unit will keep the modem connected with no activity.
P782 Parameter Index Location Determines where index information is stored for the parameter access area.
P791 Bus Error Indicates if an error condition is occurring on the bus. Primary Index Global 0 * No error Values Related ý • Error code, refer to the SmartLinx module documentation for explanation of the code P790 Hardware Error • P792 Bus Error Count P792 Bus Error Count A count that changes by increments of one each time a bus error (P752) is reported.
P801 Range Extension Allows the material level to fall below the Empty setting without reporting LOE. Primary Index Values Related Global Range: 0.000 to 9999 Preset: 20% of Span (P007) • • P005 Units P006 Empty • • P007 Span P004 Transducer This feature is useful in OCM applications where the Empty level is set to the bottom of the weir, and above the bottom of the channel, and should be used if the surface monitored can fall past the Empty (P006) level in normal operation.
P803 Shot / Pulse Mode Determines what type of ultrasonic shots are fired. Primary Index Values Related Global 1 2 • • Short * Short and long P006 Empty P805 Echo Confidence • • P804 Confidence Threshold P852 Short Shot Range Use this feature to increase HydroRanger 200 response when the monitored surface is close to the transducer face. Select short and long to have short and long acoustic shots fired for each measurement, regardless of the transducer to surface distance.
P805 Echo Confidence Displays the echo confidence of the measurement echo from the last shot. Primary Index Transducer Format: x:y (view only) Values x = short (0 to 99) y = long (0 to 99) Related • P804 Confidence Threshold • P830 TVT Type Use this feature to monitor the effect of transducer aiming, location, and mechanical transducer / mounting isolation. Both short and long shot Echo Confidence is displayed.
Advanced Echo Processing (P810 to P825) The following parameters are for authorized Siemens Milltronics Service personnel or technicians familiar with Siemens Milltronics echo processing techniques. Anatomy of an Echo Profile The relevant parts of an echo profile are listed here. These are visible in either Dolphin Plus or an oscilloscope. TVT curve Echo profile Selected echo Echo lock window Echo marker P810 Scope Displays Captures echo profiles for display on an oscilloscope.
Any combination of the following Scope Displays is available. Display Symbol P C n u Echo Profile TVT Curve Echo Marker Echo Lock Window Two methods to select Scope Displays: Scrolling 1. Press READING 2. Press ARROWS 3. Press ENTER to display the Auxiliary Function symbol. to access the desired Reading display symbols. with the desired display symbols displayed.
P816 Echo Time Raw The time (in ms) from the transmit pulse to the processed echo. Primary Index Transducer Values Range: 0.0 to 9999 (view only) Related • P815 Echo Time Filtered Profile Pointer (P817 to P825) When one of these parameters is accessed, the scope display changes: The Echo Lock Window becomes the Profile Pointer. The Profile Pointer may be moved to any point on the Echo Profile to gain specific information about the profile according to the selected parameter.
P818 Profile Pointer Distance The distance between the transducer face and the Profile Pointer. Primary Index Global Values Range: 0.000 to 9999 (view only) • • Related • P817 Profile Pointer Time P819 Profile Pointer Amplitude P820 Algorithm • • • • P821 Spike Filter P822 Narrow Echo Filter P823 Reform Echo P825 Echo Marker Trigger P819 Profile Pointer Amplitude The amplitude (in dB above 1 uV) of the Echo Profile at the Pointer position.
• • • • Related • • • • P805 Echo Confidence P817 Profile Pointer Time P818 Profile Pointer Distance P819 Profile Pointer Amplitude P821 Spike Filter P822 Narrow Echo Filter P823 Reform Echo P825 Echo Marker Trigger Use this to select the algorithm(s) the Sonic Intelligence®echo selection is based on. Use P805 Echo Confidence (page 190) to determine which algorithm gives the highest confidence under all level conditions.
P823 Reform Echo Smoothes jagged peaks in the echo profile. Primary Index Values Related Global 0 = OFF (preset) Greater = wider • • • • P002 Material P817 Profile Pointer Time P818 Profile Pointer Distance P819 Profile Pointer Amplitude • • • • P820 Algorithm P821 Spike Filter P822 Narrow Echo Filter P825 Echo Marker Trigger Use this feature, when monitoring solids (P002 = 2), if the reported level fluctuates slightly, though the monitored surface is still.
Advanced TVT Adjustment (P830 to P835) The following parameters are for authorized Siemens Milltronics Service personnel or technicians familiar with Siemens Milltronics echo processing techniques. Advanced TVT control applies to long shots only. P830 TVT Type Selects the TVT Curve used.
P832 TVT Shaper Adjust Allows manual adjustment of the TVT curve. Primary Index Global Range: -50 to 50 Values Preset: 0 • • Related P810 Scope Displays P831 TVT Shaper Use this feature to bias the shape of the TVT curve to avoid selecting false echoes from fixed objects. Adjustment to this parameter is best done while viewing the echo profile with Dolphin Plus. Refer to the Dolphin Plus online help for details. If Dolphin Plus is not available, then an oscilloscope can be used.
P833 TVT Start Min Use this feature to adjust the TVT Curve height to ignore false echoes (or pick up true echoes) near the start of the Echo Profile. Primary Index Global Range: - 30 to 225 Values Preset: 50 Related • P800 Near Blanking • P834 TVT Start Duration Enter the minimum TVT Curve start point (in dB above 1 uV RMS). This feature should only be used if increased Near Blanking (P800) would extend farther than desired into the measurement range.
Advanced Shot Adjustment (P840 to P852) These parameters are for Siemens Milltronics service personnel only. P840 Short Shot Number The number of short shots to be fired (and results averaged) per transmit pulse.
P843 Long Shot Frequency Adjust the long shot transmit pulse frequency (in kHz). Primary Index Global Values Range: 42kHz to 46kHz Altered By • P004 Transducer Related • • P841 Long Shot Number P842 Short Shot Frequency • • P843 Long Shot Frequency P845 Long Shot Width This feature is automatically altered when Transducer (P004) is altered. P844 Short Shot Width Adjust the width (in ms) of the short shot transmit pulse. Primary Index Global Values Range: 0.000 to 5.
P850 Short Shot Bias Use this feature to slant the echo evaluation in favour of the short shot echo when both short and long shots are evaluated (see P803 Shot Mode) .
Test (P900 to P913) Test Parameters are intended for use by Siemens Milltronics Service personnel. P900 Software Revision Number View the EPROM Rev. #. Primary Index Global Values Range: 00.00 to 99.99 (view only) P901 Memory Press ENTER to activate the HydroRanger 200 memory test. Primary Index Global Display: view only Values PASS (memory test successful) F1 RAM F3 FLASH data F4 FLASH code P902 Watchdog Press ENTER to put the CPU into an infinite loop to test the watchdog timer.
P904 Keypad Press ENTER , then press each keypad key in the following sequence: P P As each key is pressed, the associated keypad number is displayed. On successful test completion, PASS is displayed. FAIL is displayed if a key is pressed out of sequence or the programmer keypad malfunctions. P905 Transmit Pulse This feature may be used to monitor the transmit pulse with an oscilloscope connected to the transducer terminals.
P910 Toggle Relays Used to energize and de-energize relays directly. Primary Index Global Values 0 to 6 Related • P119 mA Relay Logic Test Enter the relay number and then toggle between energized and de-energized, as required. Enter 0 to toggle all relays at once. Applies only to relays with P119 = 0 (algorithm control). Use this parameter to confirm that relay contacts are opening and closing. This feature is helpful when P119 does not give expected results even though programming was verified.
P913 Sensor Temperature Access this parameter to display the temperature in °C (as monitored by the TS-3). Primary Index Global Values Range: -50 to 150 OPEn is displayed if a TS-3 is not connected. P914 mA Input Use this feature to display the mA input value (in mA). Primary Index mA input Values Range: 0.000 to 24.00 Measurement (P920 to P927) All of these parameters are available in RUN mode and used to verify programming.
Reading Measurements by Operation P001 P050 = 0 P050 ≠ 0 0 – OFF ---- ---- 1 – Level P921 P924 2 – Space P922 100% - P924 3 – Distance P927 P927 4 – Difference P921 (indexed) P921 (indexed) 5 – Average P921 (indexed) P921 (indexed) 6 – OCM P925 P925 7 – Pump Totalizer P925 P925 P921 Material Measurement The distance in Units (P005) or % of Span (P007) between Empty (P006) and the monitored surface.
P924 Volume Measurement The calculated vessel capacity in Max Volume (P051) or % of Max Volume. Primary Index Global Values Range: 0.000 to 9999 Related • P051 Maximum Volume P925 Flow Measurement The calculated flowrate in Max Flow (P604) units or % of Max Flow. Primary Index Global Values Range: 0.
Master Reset (P999) This feature resets all parameters to original values. Primary Index Global Values Range: 0.000 to 9999 Use this feature prior to initial programming if arbitrary Parameter Values were used during a bench test, or after upgrading the software. Following a Master Reset, complete reprogramming is required. Performing a Master Reset 1. 2. Access P999 and press CLEAR keys C.ALL displays until the reset is complete. . CAUTION: be careful when using this feature.
Parameters mmmmm Notes Page 210 HydroRanger 200 – INSTRUCTION MANUAL 7ML19981FC01
General Appendix A: Index types Index types Name Description # of indexes Global This parameter applies to the entire unit n/a View only This parameter can not be set, only viewed n/a Breakpoint Indexed by breakpoint Parameter dependent Dimension Indexed by PMD dimension up to 7 Discrete Input Indexed by discrete input 2 Echo Profile Indexed by stored echo profile 10 Level Point1 Indexed by level point 1, 2 or 3 mA input1 Indexed by mA input 1 mA output1 Indexed by mA output 0 o
Appendix B: Tech Reference mmmmm General Appendix B: Technical Reference Transmit Pulse The transmit pulse consists of one or more electrical “shot” pulses, which are supplied to the transducer connected to the HydroRanger 200 terminals. The transducer fires an acoustic “shot” for each electrical pulse supplied. After each shot is fired, sufficient time is provided for echo (shot reflection) reception before the next (if applicable) shot is fired.
Cursor Echo Marker TVT Curve Echo Profile Distance Calculation To calculate the transducer to material level (object) distance, the transmission medium (atmosphere) sound velocity (P653) is multiplied by the acoustic transmission to reception time period. This result is divided by 2 to calculate the one way distance.
Appendix B: Tech Reference mmmmm The HydroRanger 200 automatic temperature compensation is based on the sound velocity / temperature characteristics of “air” and may not be suitable for the atmosphere present. If the atmosphere temperature is variable, perform frequent Sound Velocity Calibrations to optimize measurement accuracy. Sound Velocity calibration frequency may be determined with experience.
For combination curves (mostly linear but include 1 or more arcs), enter numerous breakpoints along the arc, for best volume calculation accuracy. Set P050 = 10 This calculation creates a cubic spline approximation of the level/volume curve, providing best results if the curve is non-linear, and there are no sharp angles.
mmmmm Appendix B: Tech Reference Enter a Head Breakpoint at each point where the head/flow curve bends sharply (2 minimum). For combination curves (mostly linear but include 1 or more arcs), enter numerous breakpoints along the arc, for best flow calculation accuracy. Universal, Curved This calculation creates a cubic spline approximation of the head/flow curve, providing best results if the curve is non-linear, and there are no sharp angles.
The HydroRanger 200’s ability to respond to material level changes is designed to exceed even the most demanding installation requirements. Values Dependent on Maximum Process Speed (P003) Parameter (units) 1 (slow) 2 (medium) 3 (fast) P070 Failsafe Timer (min) 100 10 1 P700 Max Fill Rate (m/min) 0.1 1 10 P701 Max Empty Rate (m/min) 0.1 1 10 P702 Filling Indicator (m/min) 0.01 0.1 1 P703 Emptying Indicator (m/min) 0.01 0.
General Appendix C: Troubleshooting Note: Many of the parameters and techniques described here require extensive knowledge of ultrasonic technologies and Milltronics echo processing software. Use this information with caution. Appendix C: Troubleshooting mmmmm If the setup becomes too confusing use P999 to reset and start again. Common Problems Chart Symptom Cause Action Display blank, transducer not pulsing. No power. Check power supply, wiring, or power fuse. No response to programmer.
Reading fluctuates while material level is still (or vice versa). Incorrect measurement stabilization. Reading is fixed, regardless of the actual material level. Transducer acoustic beam obstructed, standpipe too narrow, or transducer ringing (reads over 100%). Alter Maximum Process Speed (P003) or damping (P704) accordingly. See Maximum Process Speed. Relocate and / or re-aim transducer at material level or object. Proceed to Measurement Difficulties below.
Determine the Noise Source Disconnect the transducer from the HydroRanger 200. If the measured noise is below 5 dB, then continue here. If the measured noise is above 5 dB go to Non-Transducer Noise Sources below. Connect only the shield wire of the transducer to the HydroRanger 200. If the measured noise is below 5 dB, continue with the next step. If the noise is above 5 dB, go to Common Wiring Problems. 2. Connect the white and black transducer wires to the HydroRanger 200. Record the average noise. 3.
Filtering cables is an option but is not recommended unless all other options have been exhausted. The HydroRanger 200 is designed to work near heavy industrial equipment such as variable speed drives. Even so, it should not be located near high voltage wires or switch gear. Common Wiring Problems Make sure that the transducer shield wire is connected at the electronics end only. Do not ground it at any other location. • Do not connect the transducer shield wire to the white wire.
Measurement Difficulties If the Failsafe Timer (P070) expires due to a measurement difficulty, LOE flashes alternately with the last known Reading. In rare cases, the HydroRanger 200 may lock on to a false echo and report a fixed or wrong reading. Flashing LOE Display Appendix C: Troubleshooting mmmmm The loss of echo (LOE) display appears when the echo confidence is below the threshold value set in P805 Echo Confidence.
Displaying Echo Confidence in the RUN mode Press and hold for four seconds (Failsafe Time Left changes to the Short:Long Confidence display). To display Echo Confidence in the program mode, access the Echo Confidence (P805) parameter. To update the value displayed after each aiming adjustment.. Press (five times or more to verify stability and overcome any echo lock P711). Increase the Failsafe Timer (P070) value, if failsafe operation will not be compromised by the larger value.
If an obstruction cannot be removed or avoided, adjust the Time Varying Threshold (TVT) Curve to reduce the Echo Confidence derived from the sound reflected by the obstruction. Use Dolphin Plus to adjust the TVT curve or use an oscilloscope and a hand programmer to adjust the required parameters. (See Scope Displays, P810 and TVT Shaper, P832.
Wrong Reading If the Reading is erratic, or jumps to some incorrect value periodically, ensure the: 1. 2. 3. Surface monitored is not beyond the HydroRanger 200’s programmed range or the transducer’s maximum range. Material is not falling into the transducer’s acoustic beam. Material is not inside the blanking distance of the transducer. Types of Wrong Readings Liquid Splashing If the material monitored is a liquid, check for splashing in the vessel.
Normal Ring Down Ring Down Appendix C: Troubleshooting mmmmm Echo Profile TVT curve Time of Correct Echo Poor Ring Down Ring Down Echo Profile TVT Curve Time of false echo from ringing Ring down times that extend past the near blanking area can be interpreted by the HydroRanger 200 as the material level and are characterized by a steady high level being reported.
General Appendix D: Pump Control Reference The HydroRanger 200 has the pump control strategies to solve nearly any water / wastewater application. This section details these strategies for engineers requiring indepth knowledge of the system and how it operates. Pump Control Options The various methods of pump control are made up of a combination of two control variables: Pump Duty The pump duty indicates in what sequence pumps are started.
Alternate Starts pumps based on the duty schedule and always leads with a new pump. Service Ratio Starts pumps based on user-defined ratio of running time. Fixed Duty Assist (P111 = 50) Ties the indexed pump relay directly to the indexed setpoint. Relay Operation (for P118 = 2) The relay contact closes at the ON setpoint and opens at the OFF setpoint. Multiple relay contacts in the pump group can be closed at the same time.
Relay Table The following table shows relay status when each setpoint is reached. Relays Setpoints Index 1 2 3 On 3 Off Off On On 2 Off On Off On 1 On Off Off Off 0 Off Off Off Alternate Duty Assist (P111 = 52) Alternates the lead pump each time the material level cycles and runs all pumps together. Relay Operation (for P118 = 2) Setpoint one does not relate directly to relay one. The pumping algorithm manages the mapping of setpoints to relays.
Setpoints Cycle 3 Relays 1 2 3 On 3 On On On On 2 On Off On On 1 Off Off On Off 0 Off Off Off Alternate Duty Backup (P111 = 53) Alternates the lead pump each time the material level cycles.
Setpoints Cycle 3 Relays 1 2 3 On 3 Off On Off On 2 On Off Off On 1 Off Off On Off 0 Off Off Off Service Ratio Duty Assist (P111 = 54) Selects the lead pump based on number of hours each pump has run and the specified ratios that each pump requires. Multiple pumps can run at one time. Relay Operation (for P118 = 2) The setpoints associated with the relays are grouped so they can be redistributed based on pump RUN time ratios.
First In First Out (FIFO) (P111 = 56) Selects the lead pump based on the Alternate duty but uses staggered off setpoints and shuts down pumps based on the first in, first out rule. This algorithm starts pumps in the same way as Alternate Duty Assist but uses staggered OFF setpoints to shut the pumps down. When the first OFF setpoint is reached the FIFO rule shuts down the first pump started. If the pumps started in sequence 2,3,1 then they would be shut down in sequence 2,3,1.
General Appendix E: Updating Software Updating Software To update the software in the HydroRanger 200, please contact your Siemens Milltronics representative to obtain the software. For a complete list of representatives, go to www.milltronics.com. WARNING: All parameter values will be lost during software upgrade. Record current parameter values manually or using Dolphin Plus before the upgrade. To install the software, please complete the following: 1. 2. 3. 4.
General Appendix F: Upgrading The following procedure will assist you if you are upgrading from a HydroRanger to a HydroRanger 200. If the application is unchanged, copy down the parameters in the HydroRanger before decommissioning the unit. Mounting a HydroRanger 200 Please read the HydroRanger 200 Installation section on page 7 before mounting the new HydroRanger 200 enclosure. Make sure the power is OFF to the unit before following these steps: 1. 2. Remove the old HydroRanger.
Connecting a transducer with RG62 coaxial extension cable If you are replacing an older Milltronics Ultrasonic Level Controller with a new HydroRanger 200 where an RG-62 coaxial extension is fitted and you are unable to replace the extension with a new cable, please refer to connection diagram below. Please note that the noise immunity performance will be similar to our older model ultrasonic level controllers if you use coaxial cable.
HydroRanger to HydroRanger 200 Parameters The HydroRanger 200 uses the current Milltronics standard parameter set which is different than the parameter numbers used in the HydroRanger. The HydroRanger parameters numbers are sequential (P-0 to P-99). The HydroRanger 200 parameters number are also sequential; however, some of the parameters are indexed. Parameters are indexed when they apply to more than one input or output. The index value defines the input/output for that parameter.
Index data types 101 bit values 101 default auxiliary reading 20 dimensions 8, 33 discrete inputs 41, 94 indexing 29 logic 41 wiring 41 display 4 auxiliary 20 controlling 19 distance 18 echo confidence 18 failsafe time left 18 head (OCM) 18 multiple readings 21 pump hours 18 rate of change 18 temperature 18 display readout 28 distance calculation 213 Dolphin Plus 24, 29, 83 changing parameters 29 communication settings 85 updating software 233 B backup level override 40 battery 10 bit values 101 blanking
Index mmmmm cut throat 75 H flume 71 Leopold Lagco 74 Palmer Bowlus 70 Parshall 73, 77 rectangular 69 universal trapezoidal 77 flush valve 60 format words 98 Frequency Input 145 G global index method 97 group pumps 60 H H flume 157 hand programmer 22 head measurement 18 head vs.
Q quick start 32 R rake control 62 randomize setpoints 59 range 4 reading volume 44 HydroRanger 200 – INSTRUCTION MANUAL Page 239 mmmmm 7ML1998IFC01 test 203 totalizer 166 transducer scanning 179 view only 27 volume 117 volume measurement 208 points indexing 29 ports, communication 84 power 15 preprogrammed applications 38 program mode 21 programming 4 alarms 47 by hand 22 relays 34 pump alternate duty backup 52, 53 by rate 56 hours 18 off setpoint 52, 53, 54 on setpoints 52, 53, 54 other controls 5
Index mmmmm recording profiles 153 register map 91 discrete inputs 94 input/output 93 mA output 94 map ID 92 parameter access 95 parameter format words 98 point data 93 product ID 93 pump control 94 pump hours 95 pump setpoint 94, 95 pump starts 95 pumped volume 95 relay outputs 94 UINT32 Order 92 relay 13 activation 37 failsafe 38 flow sampler 65 function codes 104 indexing 29 modifiers 36 modify logic 38 outputs 94 parameters 36 programming 34 totalizer 64 wiring test 37 resolution 4 response rate 33 RS
wall cling 59 weight 6 weir Cipolletti 159 standard 72 V notch 68 wet well 51 wiring 11 communication 86 problems 221 test 37 writing parameters 98 wrong reading 225 7ML1998IFC01 HydroRanger 200 – INSTRUCTION MANUAL Page 241 mmmmm Index W calculation 214 characterization chart 45 dimensions 33 readings 44 tank shape 44 universal example 45
*7ML19981Fc01* Rev. 1.