Data Sheet for Product
Siemens
Data Sheet 6169
Building Technologies Division usa.siemens.com/fire
Product Overview
The Siemens – Fire Safety Intelligent Remote Lamps (Models ILED-XC | ILED-XW) are
specifically tailored for use with initiating devices that are concealed or otherwise
not easily within view (e.g. – above suspended ceilings; under sub-floors, in
unexposed ventilating ducts, normally locked vaults or closed rooms, etc.)
The Intelligent Remote Alarm Lamps can connect to Siemens addressable fire-alarm
control panels (FACPs). Model ILED-XC is mounted on a 4-inch (10.2 cm.) octagon
outlet box. Model ILED-XW is fastened on a single-gang electrical box. The module
uses one (1) address on the loop.
1
27(: Refer to installation manual: P/N – A6V101055484 to ensure Model ILED-XC | ILED-
XW compatibility with the Siemens FACPs intended for use in the given application.
Models ILED-XC and ILED-XW provide intelligent built-in, dual isolation, meeting Class X
(Style 7) survivability requirements for shorts while providing reliable alarm
communication to the Siemens FACP. Up to 190 isolators are allowed per loop and up
to 30 devices can be connected between isolators (via wiring in a polarity-insensitive
mode). The devices between isolators can be CH’-series or later CX’ generation devices.
Specifications
The isolation feature found on the Intelligent Remote Alarm
Lamps gives information as to the location of the short.
When a short occurs, the panel can identify the short
automatically, and the module recognizes the short location
(in front of the device or behind the device). Overall, the
dual, built-in isolators improve the diagnostics and area of
the short and report when a Class X module is misconfigured.
The modules are configurable by compatible panel(s) in an
isolator (polarity sensitive) or non isolator (polarity
insensitive) mode. When a Model ILED-X-series lamp is
configured as an isolator it may serve a dual purpose by
simultaneously functioning as an input / output device and
an isolator. Advanced troubleshooting is provided by
compatible panels by identifying when an ILED-X-series
device is configured as an isolator but is wired incorrectly in
a polarity-insensitive mode.
Although there is no regulatory limitation for mounting the
lamps, be advised that Model ILED-XC is often ceiling
mounted, and Model ILED-XW is intended for wall mounting.
These intelligent remote lamps can be mounted on a
Siemens compatible-panel device loop.
Each LED can be controlled by FACP logic
ņ even on different
device loops or on another panel in the network
configuration
ņ since Model ILED-XC or Model ILED-XW is
given its own unique address.
Peripheral and Detection Devices
Initiating Device
Intelligent Remote Alarm Lamps
Models ILED-XC | ILED-XW
Model ILED-XC
Remote Alarm Lamp, Ceiling
Architect & Engineer Specifications
Multi-color intelligent light-emitting
diode (ILED) mimics the detector:
- Illuminates in any variation of
G
REEN | AMBER | RED
Dual, built-in isolators
Meets Class X (Style 7)
survivability requirements
Low current draw
Restriction of Hazardous
Substances (RoHS) compliant
Additional-accessory capability:
- when used an audible
base or relay base
Wall and ceiling lamps can be
addressed and independently
controlled by fire-alarm control
panel (FACP) logic
Ceiling and wall can be mounted
anywhere on a device loop :
- e.g. – communication loop
or the wiring on that loop
UL864 | UL2572 | UL2017 Listed;
CAN/ULC-S527 & CAN/ULC-S576 Listed
- File S24304, Vol. 3
Model ILED-XW
Remote Alarm Lamp, Wall