Installation Instructions
Table Of Contents
A6V101055484_en--_a     
4 
5
6
1b
PROGRAMMING
HOLES
TO   NEXT
ADDRESSABLE
DEVICE
TO   CONTROL   PANEL
OR   PREVIOUS
ADDRESSABLE   DEVICE
LINE   -
LINE   +
LINE   -
LINE   +
Figure 4 
ILED-X isolator mode wiring 
NOTES: 
1.  In the device line, up to 30 of any compatible devices in polarity insensitive mode with 20 ohms 
max line resistance can be isolated between two modules in isolator mode in a Class A Style 6 
wiring. 
2.  In the device line, up to 30 of any compatible devices in polarity insensitive mode with 20 ohms 
max line resistance can be isolated behind one module in isolator mode in a Class B Style 4 
wiring. 
3.  HLIM isolator module and SBGA-34 sounder base cannot be used in the same loop with the 
modules in isolator mode. 
INSTALLATION 
NOTE: 
Be sure to program the ILED before installing the unit. 
The ILED-X may be placed at any location on the device loop. Use a UL-listed/recognized single-gang 
switch box (user supplied) for mounting the ILED-XW. Use a UL-listed/recognized 4-inch octagonal 
conduit box (user supplied) for mounting the ILED-XC. Refer to Figures 5 and 6 for typical ILED-X 
installation. 
SINGLEGANG
SWITCHBOX
(USER SUPPLIED)
DO NOT
USE REAR
CONDUIT
ENTRY
ILED-XW
Figure 5          Figure 6 
Mounting the ILED-XW        Mounting the ILED-XC








