Installation Instructions

Table Of Contents
A6V101055484_en--_a
4
5
6
1b
PROGRAMMING
HOLES
TO NEXT
ADDRESSABLE
DEVICE
TO CONTROL PANEL
OR PREVIOUS
ADDRESSABLE DEVICE
LINE -
LINE +
LINE -
LINE +
Figure 4
ILED-X isolator mode wiring
NOTES:
1. In the device line, up to 30 of any compatible devices in polarity insensitive mode with 20 ohms
max line resistance can be isolated between two modules in isolator mode in a Class A Style 6
wiring.
2. In the device line, up to 30 of any compatible devices in polarity insensitive mode with 20 ohms
max line resistance can be isolated behind one module in isolator mode in a Class B Style 4
wiring.
3. HLIM isolator module and SBGA-34 sounder base cannot be used in the same loop with the
modules in isolator mode.
INSTALLATION
NOTE:
Be sure to program the ILED before installing the unit.
The ILED-X may be placed at any location on the device loop. Use a UL-listed/recognized single-gang
switch box (user supplied) for mounting the ILED-XW. Use a UL-listed/recognized 4-inch octagonal
conduit box (user supplied) for mounting the ILED-XC. Refer to Figures 5 and 6 for typical ILED-X
installation.
SINGLEGANG
SWITCHBOX
(USER SUPPLIED)
DO NOT
USE REAR
CONDUIT
ENTRY
ILED-XW
Figure 5 Figure 6
Mounting the ILED-XW Mounting the ILED-XC