® I-T-E Molded Case Circuit Breakers Bulletin SIB 2.
I-T-E® JD & LD-Frame Circuit Breakers 3-Pole, 200-600 Amperes Types SJD6, SHJD6, SLD6, SHLD6, SCJD6, SCLD6 Digital Solid State Circuit Breakers Table of Contents Important Notices 2 Accessories (Cont’d): General Information 3 Side Handle Operator Dimensional Reference Drawings Installation Instructions 4,5 6 Operational Characteristics: 29 Rotary Handle (D11CJU2) 30,31 Rotary Handle (RHOJSD, RHOJVD) 32,33 Max-FlexTM Flange-Mount Handle Operator 34-37 TELEMAND® Electric Motor Operator 38-4
IMPORTANT The information contained herein is general in nature and is not intended for specific application purposes nor is it intended as a training manual for unqualified personnel. Refer to Note for definition of a qualified person.* It does not relieve the user of responsibility to use sound practices in application, installation, operation and maintenance of the equipment purchased or in personnel safety precautions.
Information and Instructions General Information General JD and LD-Frame Solid State Sensitrip style breakers of the Sentron family are for use in individual enclosures, switchboards, and power distribution panel boards. They are available both as 80% and 100% rated devices and in three interruption ranges as shown in the table below.
I-T-E JD and LD-Frame Outline Drawings(1) — 3-Pole Types SJD6, SHJD6, SLD6.
I-T-E JD and LD-Frame Outline Drawings(1) — 3-Pole Types SCJD6, SCLD6 5
I-T-E JD and LD-Frame Installation Instructions General NOTE: This instruction page outlines the recommended installation procedure. The JD and LD-Frame circuit breaker line includes types SJD6, SHJD6, SCJD6, SLD6, SHLD6 and SCLD6 circuit breaker types. These devices are rated for operating voltages up to 600VAC, 50/60 Hz. Installation of Breaker JD and LD circuit breaker devices are for use in individual enclosure, panelboards, switchboards or other approved equipment.
JD and LD-Frame Trip Adjustments 7
JD and LD-Frame Trip Adjustments Figure 1 Breaker Functions In=Nominal Rating of Circuit Breaker AAAA AAAA AAAA AA AAAA AAAA AAAA AAAA AAAA AAAA AAAA AAAA AAAA AAAA AAAA AAAA Function Performance AAAA AAAA AAAA AA AAAA AAAA AAAA AAAA AAAA AAAA AAAA AAAA AAAA AAAA AAAA AAAA AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA AAAA Continuous Ampere (Ir) Varies the level of current the circuit breaker will carry without tripping.
JD and LD-Frame Trip Adjustments Continuous Current (I,) and Long Time Delay Instantaneous Pickup All models have a Continuous Current and Long Time Delay adjustment. This single knob adjusts the Continuous Current setting of the circuit breaker and sets the Long Time Delay. This setting (I,) is a percentage of the Maximum Continuous Current rating (In) Two long time delay bands are available.
JD and LD-Frame Trip Adjustments Short Time Pickup/Short Time Delay (Optional) Ground Fault Pickup (Ig) (Optional) Circuit breakers with the letters “NT” in the catalog number have an adjustment to set both the Short Time Pickup and the Short Time Delay. This single knob sets both pickup and delay at the same time. Circuit breakers with the letter “G” included in the catalog number have integral equipment ground fault protection.
JD and LD-Frame Trip Adjustments The ground fault option has two modes of operation. The modes are set by a switch on the side of the trip unit with the settings identified as GROUND RETURN and RESIDUAL. See Figure 1 for switch location. Residual Setting (Outgoing Circuit Method) This is the standard position to which the breaker is set when shipped from the factory.
JD and LD-Frame Time Current Curves 12
JD and LD-Frame Time Current Curves 13
JD and LD-Frame Time Current Curves 14
JD and LD-Frame Time Current Curves 15
JD and LD-Frame Let-Trhu I2t Curve Types SCJD6, SCLD6 16
JD and LD-Frame Let-Trhu Current (Ip) Curve Types SCJD6, SCLD6 17
I-T-E Rear Connecting Studs Breaker Preparation (Figure 2) A. Remove wire connectors from breaker if present. B. Attach long and short studs (1), (2) to circuit breaker for three pole devices, short studs (1) only for two pole devices. Attach with the 5/,6-18 X 1 in. hex head bolt and the 5/16 in. serrated cone lockwasher (4). Tighten finger tight only. C. Slide one stand-off insulator (5) onto each stud until the stand-off insulator fully covers the square end of the studs.
Installation, Diagrams 19
I-T-E Plug-In Adapters General Mounting Block (Figure 3) A complete plug-in installation requires one line end adapter assembly (consisting of a mounting block, tulip connectors and associated hardware), one load end adapter assembly and one switchboard mounting plate. The switchboard mounting plate is optional and can be replaced by other mounting means to suit customer’s requirements. A.
Installation Diagrams 21
I-T-E Pressure Wire Connectors General Each connector kit contains a solderless connector and associated hardware for making one line or load connection. Installation NOTE: Trip unit must be installed in circuit breaker prior to mounting load end connector. A. Tighten mounting screws (1) to securely attach connector. See table for torque values. B. Tighten set screws (2) securely to prevent overheating of conductor and connector. See table for torque values.
I-T-E Compression Connectors (CCL600) H. Select an appropriate tool and die combination from Table 1 and make the required number of crimps within the boundaries stamped on the connector barrel. Refer to Figure 2 for sequence of multiple crimps. Table 1—Compression Tool and Die Chart For Copper and Aluminum Conductors AAAA AAAA AAA AAAA AAA AAAA AA Wire AAAA Size AAAA ToolAA Tool No. Die No. No. of AAAA AAAA AAAA AA AAAA AAA AAAA AAA AAAA AA Mfgr.
I-T-E Handle Locking Devices ATTACHING I-T-E HANDLE BLOCKING DEVICE (J6HBL) To Block Handle ON Turn Breaker ON. Assemble blocking device to breaker by positioning over handle as shown, with handle opening of blocking device toward the line end. Insert tab A into slot A1. Push toward handle and downward in area shown (Figure 1) until tab B drops into slot B1 (Figure 2). To Block Handle OFF Turn Breaker OFF. Reverse handle blocking device so that handle opening of blocking device is toward the load end.
I-T-E Internal Accessories Circuit Breaker Preparation A. Depress trip button (Figure 1 ) to trip circuit breaker prior to removing cover. Before attaching accessory unit, circuit breaker must be in tripped position. B. Remove two terminal shield screws on load end cover (1), load end cover screws (5 or 9) (2) and, if breaker is mounted, also remove mounting screws (not shown). Remove load end cover only (3). Accessory units can be mounted in right pole only of the circuit breaker.
I-T-E Internal Accessories Recommended Combinations C. D. Slide accessory down to rest on pad (6) trip unit. When accessory is installed correctly, front of accessory (7) will rest on pad (8) of line cover. Pull gently and evenly on accessory wire leads (2 to 6 wires) while lowering accessory into base. Make sure all the slack is removed from leads inside breaker. Replace load end cover (3), cover screws (2) and four mounting screws if mounted. Replace terminal shield with screws (1). E.
I-T-E Shunt Trip and Undervoltage Trip Electrical Check Shunt Trip Undervoltage Trip A. Reset and turn circuit breaker ON. A. B. Attach test circuit to accessory leads. When the test voltage reaches 55 percent or more of the rated coil voltage, the circuit breaker should trip. With breaker in TRIPPED position, connect test circuit to accessory leads. Energize undervoltage trip device at 85 percent of the marked rated voltage of the coil. Reset and turn breaker handle ON. B. C.
I-T-E Auxiliary Switch and Bell Alarm Switch Electrical Check Auxiliary Switch Kits AAAA AAA AAAA AA AAAA AAAA AAAA AAAA AA Catalog Number Ampere Rating of Switch AAAA AAA AAAA AA AAAA AAAA AAAA AAAA Number of AAAA AAA AAAA AA AAAA AAAA AAAAA AAAA Volts AC AAAA Volts DC A Switches AAAA AAA AAAA AA AAAA AAAA A AAAA AA AAAA AAA AAAA AA AAAA AAAA AAAA AAA A AAAA A AAAA 120 240 480 125 250 AAAA AAA AAAA AA AAAA AAAA AAA AAAA AAAAA AAAA AA AAAA AAA AAAA AA AAAA AAAA AAA AAAA A A01JLD64 1 10 10 10 0.5 0.
I-T-E Slide Handle Operator (D11JLU, D11JL4U, D11JRU, D11JR4U)(1) Types 1, 4, 12 A. Cut slot and holes in enclosure flange for operating handle (1), provide mounting holes for circuit breaker (2) and support member (3) as shown. B. Weld interlock latch (4) to inside of cover. Additional cover securing means also required. C. Loosen four cover screws (5) and remove terminal shields (14). Insert four 1/4-20 x 23/4 in.
I-T-E Rotary Handle Enclosure Mechanism Types 1, 12 Variable Depth (D11CJU2) General Handle with permit locking the disconnect device in the OFF position using up to three locks having shackles up to 3/8 in. in dia. Provision for locking in ON position is provided/ but the handle plate must have the material covering the locking notch removed. This can be done with a hacksaw or file. The handle has a voidable interlock.
Installation Diagrams 31
I-T-E Rotary Handle Enclosure Mechanism Types 1, 3, 3R, 4, 4x, 12 Standard Depth (RHOJSD) Variable Depth (RHOJVD) General Information When properly installed, the rotary handle operator provides single point latching of the enclosure door For maximum protection against unauthorized entry into the enclosure, additional latching means should be provided. The handle can be padlocked in the OFF position with up to three 5/16 in. padlocks. The breaker operator can also be padlocked in the OFF position.
Installation Diagrams 33
I-T-E Max-FlexTM Flange-Mount Handle Operator Types 1, 3, 3R, 4, 4x, 12 Application The Max-Flex Operator is designed to work with I-T-E circuit breakers having current ratings through 600A. The Max-Flex unit meets all the industrial criteria such as UL and Automotive Industry Standards. Design GENERAL INFORMATION The new Max-Flex Handle Operator provides maximum flexibility in design and assembly of electrical equipment.
I-T-E Max-FlexTM Flange-Mount Handle Operator Types 1, 3, 3R, 4, 4x, 12 INSTALLATION INSTALLATION DIAGRAMS Mounting Max-FlexTM Handle Operator to Enclosure Frame Assembly A. B. C. Drill the mounting holes in the enclosure flange and file all burrs (Figures 1 and 2). Note the maximum and minimum drill hole distances in Figure 2. Push the rubber gasket (1) down in the groove of the handle assembly (2) (Figure 3). The handle and the interlock mechanism are supplied preassembled from the factory.
I-T-E Max-FlexTM Flange-Mount Handle Operator Types 1, 3, 3R, 4, 4x, 12 Adjusting Door Catch Mechanism A. Close the enclosure door and move the handle into the ON position. Adjust the door catch downward if the handle cannot be moved from the ON position. With the handle in the ON position, try to open the enclosure door without turning the defeater screw in the handle. If the door opens, readjust the door catch and repeat Steps A and B. B.
I-T-E Max-FlexTM Flange-Mount Handle Operator Types 1, 3, 3R, 4, 4x, 12 Tighten Detent Screws B. Secure the cable (16) to the frame assembly (4) by placing it between the cable retainer clip (26) and the shim (27), secure with two #10-32 x 3/8 in. screws and lockwashers. NOTE: Detent (28) in cable retainer must align with the groove (29) in the cable’s metal fitting (Figure 7).
I-T-E TELEMAND(R) Electric Motor Operator General The motor operated mechanism is designed to open, close and reset a circuit breaker or switch by remote control. The customer must supply the circuit breaker or switch, normally ON and OFF momentary type push-buttons, external wiring, a control power source, and all control logic. Consult the wiring diagram (Figure 3, page 40) for a typical control connection.
I-T-E TELEMAND(R) Electric Motor Operator F. With the circuit breaker handle in the OFF position, align the motor operator mechanism rollers (indicator to be in OFF position) and the circuit breaker handle by rotating the lead screw (6) with a screwdriver The lead screw access hole is at the bottom of the motor operator (Figure 2). G. Close and latch the mechanism cover H.
Installation Diagrams 40
I-T-E Panelboard Connector Straps(1) 41
I-T-E Enclosures Types 1, 3, 4x, 12 Type 1—J6N1, L6N1 Type 3R—J6N3R, L6N3R General purpose indoor, sheet-steel enclosure for use in normal atmosphere, listed as service-entrance equipment. An outdoor, sheet-steel enclosure providing protection against driving rain, sleet or snow. Listed as service-entrance equipment. Type 4—LD6SS4 Type 12—J6N12, L6N12 A special-industry, sheet-steel enclosure for indoor use in atmosphere containing particles of lint, dirt, sawdust and other foreign matter.
I-T-E Door Latch Mechanism (DKR2, DKR3, DKL2, DKL3)(1) H. Turn the handle 1/4 turn clockwise (looking from inside the enclosure door) and attach the latch plate roller to the handle shaft, while inserting the bent leg of the spring into the hole in the latch plate. Fasten with a locking-type flange nut. Tighten the nut, then loosen 1/8 turn to allow movement of the roller assemblies (Figure 1). NOTE: Straight leg of spring must rest against pin (12) on handle plate. See inset on Figure 1. I.
Installation Diagrams 44
I-T-E JD and LD-Frame Neutral Sensing Transformer General A. Turn off power feeding this device before starting the installation. B. Also turn off any line power within the immediate vicinity to prevent the incidental or accidental contact of tools by the installer. NOTE: This instruction sheet outlines the recommended installation procedure for the following Neutral Sensing Transformers: AAAA AAAA AA AAAA AAAA AAA AAAA AAAA AA Transformer Ampere Rating Color AAAA AAAA AA AAAA AAAA AAA AAAA AAAA AA Cat.
I-T-E JD and LD-Frame Neutral Sensing Transformer Terminal Connections A. After properly orienting and mounting the neutral sensing transformer, maintain the correct polarity by attaching the white lead from the circuit breaker to terminal x 1 of the neutral sensor, and the black lead to terminal x 2.
I-T-E Universal Test Kit (TS-31) Catalog Number xxxxxx Not Found. Press Enter to Continue and you will be asked to enter another catalog number. E. If valid catalog number has been entered, the TS-31 will prompt for the Breaker switch settings. The TS-31 will respond with: Enter continuous current setting in % Enter instantaneous pickup setting. Enter long time delay in seconds. For breakers with short time functions you may be asked one of the following: Enter short time pickup.
I-T-E Universal Test Kit (TS-31) Enter Test to perform H. If you press ENTER, you will be prompted for the phase to test: The TS-31 will display: Enter phase to test. Enter one of the following letters: “A” - Phase A or left pole. “B” - Phase B or center pole. “C” - Phase C or right pole. I. Press Enter again to start the test. Press any other key to STOP the test. Once a test has been started, the TS-31 will respond with: Testing . . . Be careful at this time. Any key press will abort the test.
Ordering Information Circuit Breaker Catalog Numbers SJD6 3-Pole, 600V AC AAAA AAA AAAA AAAAA AAAA AAAAA AAAA AAAA AAA AAAA AAAAA AAAA AAAAA AAAA AAAAA AAAA AAAAA AAAA AAAAA AAAA AAAA AAAA AAAA AA AAAA AAA AAAA A A AAAA AAA AAAA A A A A A AAAA AAAA AAAA AA AAAA AAA AAAA A AAAA A AAAA AAAA AAA AAAA A AAAA A AAAA A AAAA A AAAA A AAAA AAAA AAAA AAAA AA AAAA AAA AAAA A AAAA A AAAA AAAA AAA AAAA A AAAA A AAAA A AAAA A AAAA A AAAA AAAA AAAA AAAA AA AAAA AAA AAAA A AAAA A AAAA AAAA AAA AAAA A AAAA A AAAA A AAAA A
Ordering Information Circuit Breaker Catalog Numbers SLD6 3-Pole, 600V AC AAAA AAA AAAA AAAAA AAAA AAAAA AAAA AAAA AAA AAAA AAAAA AAAA AAAAA AAAA AAAAA AAAA AAAAA AAAA AAAAA AAAA AAAA AAAA AAAA AA AAAA AAA AAAA A A AAAA AAA AAAA A A A A A AAAA AAAA AAAA AA AAAA AAA AAAA A AAAA A AAAA AAAA AAA AAAA A AAAA A AAAA A AAAA A AAAA A AAAA AAAA AAAA AAAA AA AAAA AAA AAAA A AAAA A AAAA AAAA AAA AAAA A AAAA A AAAA A AAAA A AAAA A AAAA AAAA AAAA AAAA AA AAAA AAA AAAA A AAAA A AAAA AAAA AAA AAAA A AAAA A AAAA A AAAA A
Ordering Information Internal Accessory Combination Shunt Trip AAAA AAAA AAAAA AAAA AAAA AAAA AAAA AA AAAA AAAA AAAA AAAA AAAA AA ControlAAAA VoltageAAAAAAAA 1 Shunt Trip 1Shunt Trip and AAAA AAAA AAAA AAAA A AAAA AAAA AAAA AAAA AA AAAA AAAA AAAA AAAA AAAA AA 1 Auxiliary Switch AAAA AAAA AAAA AAAA A AAAA AAAA AAAA AAAA AAAA AA AAAA AAAA AAAA AAAA AAAA AA AAAA AAAA A AAAA AAAA A AAAA AAAA AAAA AAAA AAAA AA AAAA AAAA AAAA AAAA AAAA AA AC DC Catalog Number Catalog Number AAAA AAAA A AAAA AAAA A AAAA AAAA AAAA
Ordering Information Additional Accessories Item PressureWire Connectors (1-2) #3/0-500 MCM (Cu) (1 -2) #4/0-500 MCM (Al) Catalog No. TA2J6500 Item Side Handle Operators Left Side Right Side (1) 500-750 MCM (Al) (1) 500-600 MCM (Cu) (2) 250 MCM (Al) TA1 L6750 (1) #3/0-600 MCM (Cu) TC1J6600 (1-2) #3/0-500 MCM (Cu) Catalog No.
UL Listings and File Numbers Industry Specifications AAAA AAAA AAA AAAA AAAA AAAA I-T-E UL-489 File AA CSAAAAA Report AA AAAA AAAA AAA AAAA AAAA AA AAAA AAAA AA Number Number AAAA AAAA AAA AAAA AAAA AA AAAA AAAA AA AAAA AAAA AAA AAAA AAAA AA AAAA AAAA AA Breakers E10848 LR13077 Terminal Connectors Plug-ln Connectors Rear Studs Handle Operators Motor Operators Internal Accessories Shunt Trip Undervoltage Trip Aux.
Siemens Energy & Automation, Inc. 3333 State Bridge Rd. Alpharetta, GA 30202 Bulletin SIB2.