Legend (cont’d)
Lockout indication positions when there is no input signal (see Control sequence in the event of faults):
No start
Abortion of startup sequence
Abortion of startup sequence
Lockout (fault in the flame supervision circuit)
1
Lockout (no flame)
2
Lockout (no flame)
P
Lockout (no air pressure)
Time table
t1 Prepurge time with air damper fully open
TSA Safety time or first safety time with burners using a pilot burner
TSA´ Safety time or first safety time with burners using a pilot burner
t3 Preignition time
t3´ Preignition time
t3n Postignition time (ignition transformer connected to terminal 15)
t4 Interval between the start of safety time (TSA/TSA´) to the valve connected to terminal 19
t4´ Interval from the start of safety time (TSA/TSA´) to the release of the valve connected to terminal 19
t5 Interval from the end of interval (t4/t4´) to the release of the load controller or valve at terminal 20
t6 Postpurge time (identical with the permissible afterburn time (t13))
t7 Switch-on delay for fan motor M2
t8 Duration of startup sequence excluding running time (t11/t12)
t9 Second safety time with burners using a pilot burner
t10 Interval from the start to the beginning of the air pressure check
t11 Running time of air damper into the fully open position
t12 Running time of air damper into the low-fire position
t13 Permissible afterburn time
t16 Interval from the start to the OPEN command for the air damper
t20 Interval to the self-shutdown of the sequence switch
max. Safety time in the event of loss of flame during operation
* Times safety time (TSA´), long preignition time (t3´) and interval (t4´) are only programmed by burner
controls LGK16.335... and LGK16.635...