Data Sheet for Product

Technical Specification Sheet
Document No. 149-499
August 15, 2014
Siemens Industry, Inc.
Page 1 of 11
Zero Casing Leakage Laboratory Exhaust Air
Terminal
Figure 1. External Shaft Seal of Model LGZ Exhaust
Terminal.
The Siemens Zero-Casing Leakage Laboratory
Exhaust Air Terminal is an industrial grade, easy-to-
install, pre-packaged airflow measurement and
control terminal unit designed for the requirements of
ductwork in biocontainment facilities. When used with
the Laboratory Controller, it provides stable and
precise exhaust airflow control over the entire range
of airflow requirements.
Features
All units leak less than 0.1% per minute of internal
volume per ASME N510 Pressure Decay test.
Individually factory leak tested to 15” W.C. (3750
Pa).
External shaft seals ensure zero casing leakage.
Solid stainless steel damper shaft on Teflon®.
bushings for smooth, maintenance free operation.
20 Gauge 316L stainless steel construction with
flanges meeting SMACNA industrial standard.
Orifice plate airflow measurement resists fouling.
Flow signal tubing sealed with 2-valve manifold
Optional 5-valve manifold with HEPA filters.
Low non-recoverable static pressure loss
Sizes 4, 6, 7, 8, 9, 10, 12, 14, 16 & 18 inch
diameter. Airflow capacities from 35 to 5655 cfm.
Factory-mounted measurement and control
devices to simplify installation (optional).
Figure 2. Flow Signal Manifold Options.
Materials (within air stream) Standard
Duct Casing
20 gauge 316 stainless steel with
SMACNA RIDCS flanged ends.
Airflow Sensor Orifice ring, 20 ga. 316 stainless
steel with pressure signal taps.
Damper Blade
20 ga. 316 stainless steel with Volara
edge seals. 90 degree rotation.
Damper Shaft
½-inch (1.27 cm) diameter, solid
stainless steel; shaft end marked
with the damper position.
Damper Bushings
Teflon
Materials (outside air stream) Standard
Control Enclosure
22 gauge galvanized steel
Pneumatic Tubing
UL rated 94 V-2 fire retardant
Pneumatic Fittings
in enclosure only
Brass, dual barbed
Airflow Measurement Accuracy
Flow Measurement
±2% of actual flow @ listed ranges
(sensor only. Does not include
accuracy of controller or transmitter)
Installation
Requirements
Rigid duct of the same diameter 1 x
duct diameters upstream from the
sensor is required.
Environmental
Operating
Temperature/% RH
40 to 120°F (4 to 50°C)
0 to 95% non-condensing
Storage
Temperature/% RH
-10 to 150°F (-23 to 65°C)
0 to 95% non-condensing
Dimensions
Weight
20 to 32 lbs.(9.1 to 14.5 kg)