Installation Instructions

Installation Instructions
Document No. 570-129
October 26, 2016
Smoke Control Listed LCM-OAVS with
Two Fast Acting Venturi Air Valves
(One Exhaust, One Supply) and HW
Reheat including BTU Compensation
Item No. 570-129. Rev. CA Page 1 of 9
Generic Controller I/O Layout. See Wiring Diagram for application specific details.
Control Applications
6750, 6756
Product Description
These instructions explain how to field install or
replace the BACnet Laboratory Controller Module
LCM.
This BACnet LCM-OAVS VAV Room Pressurization
Controller with HW Reheat and Two Fast-acting
Venturi Air Valves One Exhaust, One Supply
features VAV control of a laboratory room with one
supply duct, one exhaust duct, and up to six Fume
Hoods. It uses fast-acting electronic actuators
(shipped separately) to control the supply and
exhaust.
This controller is built on a BACnet Programmable
TEC (PTEC) platform that supports up to two
Offboard AVS signals; however, Onboard AVS
transducers are not supported. Offboard Air
Module(s) (OAM) house AVS transducers and send
signals to the AVS input(s) on the LCM OAVS
board.
The LCM can operate stand-alone, with a field
panel, or as part of a network.
Product Numbers
BACnet LCM-OAVS with HW
Reheat and Two Venturi Air Valves
One Exhaust, One Supply
Applications 6750 (RTS) 6756
(BTU)
This controller requires Offboard
Air Module(s) (ordered and
shipped separately
570-804PKA
Offboard Air Module two
required, order separately
550-819B
Siemens fast-acting Lab Electronic
Actuator(s) order and ship
separately)
GNP191.1U
Shipping carton includes a controller assembly, a
mounting rail, and two self-tapping/drilling screws.

Summary of content (9 pages)