Application

Sequence of Operation
Fail Mode Operation
29
Siemens Industry, Inc.
Application Note, Application 6759
* If MAX HOOD VOL is set to 0, a “Failed” status of HOOD VOL will not initiate a failure
in TOTL EXHAUST or VOL DIFFRNC. See
Fume Hood Flow Input
.
Air Velocity Sensors If one or both of the LCM air sensor signals (SUP AIR VOL,
GEX AIR VOL) are out of range (for example, improper wiring to/from the Offboard Air
Module(s), tubing not connected or connected backward), then the actions of the
supply and general exhaust Dampers will depend on the value of AVS FAILMODE.
Once GEX AIR VOL and SUP AIR VOL are normal, the supply and general exhaust
Dampers return to normal operation.
See
Operation of AVS FAILMODE
for more information.
NOTE:
If desired, the LCM can be used without any fume hoods attached. In this case, MAX
HOOD VOL should be set to 0 cfm to disable the alarming that would occur if the
fume hood flow input drops below 1 Vdc.
Laboratory Room Controller If the LCM power fails, all actuators default to their user-
defined fail-safe states. Since there is no power to the controller, no LEDs are
available.
Electronic Actuator If the actuator fails, typically, flow control is lost and alarms are
triggered.
Upon loss of power or control signal to the actuator, it will move to its fail-safe position.
Room Temperature Setpoint Dial If the room temperature setpoint dial fails while CTL
STPT is not overridden or is not being adjusted by a field panel, then ROOM STPT and
CTL STPT both display as “Failed” and the last known good value of ROOM STPT is
used to determine the current value of CTL STPT. The rest of the room temperature
PID loop is unaffected by the setpoint dial failure. If ROOM STPT is unbundled in a
field panel and defined as alarmable, an alarm will be annunciated across the network.
If the room temperature sensor fails while CTL STPT is overridden or is being adjusted
by a field panel, then ROOM STPT displays as “Failed”. CTL STPT will continue to be
overridden or adjusted by the field panel and room temperature control proceeds as
normal. CTL STPT will continue to have a status of NORMAL. If ROOM STPT is
unbundled in a field panel and defined as alarmable, an alarm will be annunciated
across the network.