Application

Point Database Application 6759
34
Siemens Industry, Inc.
Application Note, Application 6759
Point Database Application 6759
Object Type
Object
Instance
(Point
Number)
Object Name (Descriptor)
Factory
Default (SI
Units)
Eng Units
(SI Units)
Range
Active Text
Inactive
Text
AO
1
CTLR ADDRESS
255
--
0-255
--
--
AO
2
APPLICATION
6792
--
0-32767
--
--
AO
3
TEMP OFFSET
0.0 (0.0)
DEG F
(DEG C)
-31.75-32
--
--
AI
{04}
ROOM TEMP
74.0
(23.44888)
DEG F
(DEG C)
48-111.75
--
--
AO
5
OCC DIF STPT
400
(188.7599)
CFM (LPS)
-8000-8380
--
--
AO
6
UOC DIF STPT
400
(188.7599)
CFM (LPS)
-8000-8380
--
--
AO
7
RM STPT MIN
55.0
(12.80888)
DEG F
(DEG C)
48-111.75
--
--
AO
8
RM STPT MAX
90.0
(32.40888)
DEG F
(DEG C)
48-111.75
--
--
AO
{09}
TEMP CTL VOL
0 (0.0)
CFM (LPS)
0-32764
--
--
AO
12
OCC ENA
0
--
0-255
--
--
AI
{13}
ROOM STPT
74.0
(23.44888)
DEG F
(DEG C)
48-111.75
--
--
AI
{14}
AI 4
0
PCT
0-102.3
--
--
AI
{15}
HOOD SIG AI3
0
VOLTS
0-10.23
--
--
AO
16
VENT ALM DEL
30
SEC
0-255
--
--
AO
17
ALARM ENA
0
--
0-255
--
--
BI
{19}
OCC BUTTON
OFF
--
Binary
ON
OFF
BO
{21}
OCC.UNOCC
OCC
--
Binary
UNOCC
OCC
BO
{22}
VOL DIF ALM
OFF
--
Binary
ON
OFF
BO
{23}
NET ALM CMD
OFF
--
Binary
ON
OFF
BI
{24}
OCC SWIT DI2
OFF
--
Binary
ON
OFF
BO
{25}
BUTTON CMD
OCC
--
Binary
UNOCC
OCC
AO
26
GEX P GAIN
0.015
--
0-4.095
--
--
BI
{27}
ALM SWIT DI6
OFF
--
Binary
ON
OFF
AO
28
TRACK MODE
0
--
0-255
--
--
BO
{29}
NET OCC CMD
OCC
--
Binary
UNOCC
OCC
AI
{30}
GEX AIR VOL
0 (0.0)
CFM (LPS)
0-32764
--
--
AO
{31}
OCC SUP MAX
3400
(1604.46)
CFM (LPS)
0-32764
--
--