Application

Point Database Application 6759
37
Siemens Industry, Inc.
Application Note, Application 6759
Object Type
Object
Instance
(Point
Number)
Object Name (Descriptor)
Factory
Default (SI
Units)
Eng Units
(SI Units)
Range
Active Text
Inactive
Text
AO
97
SUPDUCT AREA
1.0
(0.09292)
SQ. FT (SQ
M)
0-6.375
--
--
AO
98
LOOP TIME
5
SEC
0-255
--
--
AO
{99}
ERROR STATUS
0
--
0-255
--
--
AO
104
SENSOR SEL
0
--
0-255
--
--
AO
106
MODHTG FLO
300 (1.524)
FPM (MPS)
0-4095
--
--
AO
107
DO DIR.REV
0
--
0-255
--
--
AI
{108}
RM RH
50
PCT
0-102
--
--
AO
109
FAIL TIME
60
SEC
0-510
--
--
AO
110
MTR SETUP
0
--
0-255
--
--
AO
{111}
SUP DMP POS
0
PCT
0-102
--
--
AO
112
MTR1 TIMING
95
SEC
0-511
--
--
AO
113
MTR1 ROT ANG
90
--
0-255
--
--
AO
{114}
GEX DMP POS
0
PCT
0-102
--
--
AO
115
MTR2 TIMING
95
SEC
0-511
--
--
AO
116
MTR2 ROT ANG
90
--
0-255
--
--
AO
117
MINHOODVOLTS
1
VOLTS
0-10.23
--
--
AI
{118}
RM CO2
1000
PPM
0-8191
--
--
AO
125
SUP MAX RATE
0 (0.0)
FPM (MPS)
0-4095
--
--
AO
126
GEX MAX RATE
0 (0.0)
FPM (MPS)
0-4095
--
--
BO
{127}
PPCL STATE
EMPTY
--
Binary
LOADED
EMPTY
1)
Object Types are; Analog Input (AI), Analog Output (AO), Binary Input (BI) and Binary Output (BO).
2)
A single value in a column means that the value is the same in English units and in SI units.
3)
Point numbers that appear in brackets { } may be unbundled at the field panel.