Commissioning Instructions

Before You Begin
Verifying Power
3 | 9
Siemens Industry, Inc.
A6V10801613
Restricted
07.06.2016
Before You Begin
WARNING
A fume hood is a safety device.
Anyone attempting to start up a Fume Hood Controller and its related equipment
must have completed Operations Training.
WARNING
DO NOT connect to the USB port of the SOAM while the fume hood is in
operation.
At the job site, locate the major control system and the mechanical and electrical
drawings. This should include any components working in conjunction with the
Sash Open Area Module (SOAM).
Verify that the SOAM input/output (I/O) points are wired per the installation
instructions.
Verifying Power
1.
Verify that the controller has 24 Vac power and that the fuse has been
inserted into the trunk or that power to the transformer is ON.
2.
Verify the RUN LED is green.
If any error condition exists the LED is solid red. If no error condition exists,
then the LED is solid green when not communicating and flashing 80-20
when communicating.
Installing USB Driver
1. Open Windows Explorer and navigate to Standard Apps.
2. Find the USB device/drive
(VCP_V1.3.1_Setup.exe/VCP_V1.3.1_Setup_x64.exe) in the drives list.
3. Double-click the appropriate executable to launch the application. Follow the on
screen instructions.
4. Plug in the USB on both ends (the device side to the Sash Aggregator; the host
side to the computer).
Verifying Slave Mode Application
Open WCIS and verify that Application 2950 (Slave Mode) is running at the
controller.
NOTES:
Only WCIS 4.1 or higher is compatible with this device.
In order to save configuration values, you must either change WCIS settings
(select Write to EEPROM only) or double-click a subpoint to open a dialog box.